18
9
General information
9.1 Correspondance table
The currents (
In
) shown are at rated output power.
9.2 Environmental specifications
Operating temperature:
- 10°C à + 55°C housed @ 100 % load
- 10°C à + 60°C housed @ 75% load
Operating maximum altitude:
2000m
Storage temperature:
-25 à + 85°C.
Operating relative humidity:
from 20 to 95%.
Life time: 200 000 h @ 25°C
(ambient T, external to the housing, mains nominal @ 75% load housed)
Pollution degree:
II (according EN 60950-1 and EN 62368-1)
Overvoltage category:
II (according EN 60950-1 and EN 62368-1)
Environmental class:
II (according EN 50131-1)
9.3 Electrical Characteristics
9.3.1
Mains input
Single AC voltage: 110V - 240V
Frequency: 50 - 60Hz.
Class I.
Groundings: TT, TN, IT.
Double pole breaker C curve rated current between 2A and 10A to provide upstream.
12V
50W
75W
Primary current @ 98V
1A
1.52A
Primary current @ 195V
0.51A
0.76A
24V
50W
75W
Primary current @ 98V
0.98A
1.50A
Primary current @ 195V
0.52A
0.78A
9.3.2
Output
Nominal voltage
12V
24V
Output current In
4A
6A
2A
3A
Floating voltage (Un) at half load
and 25°C
13.6V
27.2V
Current limitation – short circuit
current
From In to In+15% for an output voltage > 50% Un.
Battery discharge current with no
mains and no load
17,5mA @ 12V
29,5mA @ 24V
HF p-t-p ripple (20MHz-50
)
< 4% Un
BF rms ripple
< 0.2% Un
Static and dynamic regulation
characteristics
< 5% Un for total added mains and load variations (from 10 to 90%)
50W
75W
12V
4A
6A
24V
2A
3A