background image

V

ICTORY 

II

INSTALLATION REQUIREMENTS

The installation must conform to the requirements of the
authority having jurisdiction or, in the absence of such
requirements, to the National Fuel Gas Code , ANSI Z223.1-
latest edition.

This installation must also conform to the additional require-
ments in this Slant/Fin Instruction Book.

NATURAL GAS-FIRED BOILER LOCATION

Provide a level, solid foundation for the boiler.  Location
should be as near as possible to chimney or outside wall so
that the flue pipe from boiler is shor t and direct.  (See Appen-
dix A for vent terminal location restrictions.)  The location
should also be such that the gas ignition system components
are protected from water (dripping, spraying, rain, etc.) during
appliance operation and service (circulator replacement, con-
densate trap, control replacement, etc.).

WARNING

LIQUEFIED PETROLEUM (L.P.) PROPANE GAS-FIRED
BOILER LOCATION

REQUIRES SPECIAL ATTENTION

Liquefied Petroleum (L.P.) propane gas is 

heavier than air.

Therefore, propane boilers, piping, valves must NOT be
installed in locations where propane leaking from def ective
equipment and piping will "pool" in a basement or other
space below the leak.
A spark or flame from the boiler or other source ma y ignite
the accumulated propane gas causing an explosion or fire.
Provide a level, solid foundation for the boiler.  Location
should be as near the chimney as possible so that the flue
pipe from boiler to chimney is short and direct.

The UNIFORM MECHANICAL CODE may be in effect in
your geographic area.

The following precautions are cited by the 1994 UNIFORM
MECHANICAL CODE, section 304.6:

"LPG Appliances.

Liquefied petroleum gas-burning

appliances shall not be installed in a pit, basement or
similar location where heavier-than-air-gas might collect.
Appliances so fueled shall not be installed in an abo ve-
grade under-floor space or basement unless such loca-
tion is provided with an approved means for removal of
unburned gas."

Consult Chapter 5 of the 1994 UNIFORM MECHANICAL
CODE for design criteria of the "approved" means for
removal of unburned gas.

BOILER FOUNDATION 

A. Provide a solid, level foundation, capable of supporting

the weight of the boiler filled with w ater, and extending at
least 2" past the jacket on all sides.  See dimensions of
boilers, page 2.

B. For installation on non-combustible floors only*.
C. If boiler is to be located o ver buried conduit containing

electric wires or telephone cables, consult local codes or
the National Board of Fire Underwr iters for specific
requirements.

* Installation on combustible flooring allowed only with proper Com-

bustible Floor Kit.  Kit part number is printed on boiler rating plate.
In no case may the boiler be installed on car peting.

MINIMUM CLEARANCES FROM COMBUSTIBLE 
CONSTRUCTIONS

A. Minimum clearances to the exterior surfaces of the boiler

shall be as follows:
MINIMUM ALCOVE AND CLOSET CLEARANCE

For Combustible 

Recommended

Surface

Construction

for Service

Front 

6"

18"

Rear 

6"

18"

Left Side

6"

18"

Right Side 

12"

24"

Top  

12"

12"

Flue Connector:

Enclosed —

6"

6"

Unenclosed —

2"

6"

B. Provide accessibility clearance of 24" on sides requir ing

servicing and 18" on sides used for passage.

C. All minimum clearances shown above must be met.  This

may result in increased values of some minimum clear-
ances in order to maintain the minim um clearances of
others.

D. Clearance from hot water pipes shall be 1 inch**.

**  At points where hot water pipes emerge from a floor, wall or ceiling,

the clearance at the opening through the finished floor boards or w all
or ceiling boards may be not less than 1/2 inch. Each such opening
shall be covered with a plate of uncombustible material.

SAFETY

KEEP THE BOILER AREA CLEAR AND FREE FR OM
COMBUSTIBLE MATERIALS, GASOLINE AND OTHER
FLAMMABLE VAPORS AND LIQUIDS.

3

Figure 3.

Summary of Contents for victory II VH series

Page 1: ...is boiler is under positive pres sure when it is connected to the outdoors with 3 diameter pipe Leakage from this system can be hazardous and if not avoided can result in death or ser ious injury In a...

Page 2: ...0 3000 4000 5000 6000 7000 8000 9000 10000 Orifice Size for Sea Level Orifice Sizes for High Altitudes Includes 4 Reduction for Each 1000 Feet Elevation Feet Orifice sizes indicated for sea level abov...

Page 3: ...fueled shall not be installed in an abo ve grade under floor space or basement unless such loca tion is provided with an approved means for removal of unburned gas Consult Chapter 5 of the 1994 UNIFOR...

Page 4: ...ith a minimum FREE air passage area of 1 square inch per 1000 Btuh of total appliances input IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT THE AREA OF FREE OPENINGS MUST BE APPROPR...

Page 5: ...ght run would be 20 2 x 3 14 ft 3 Installation A Horizontal Venting Figures 5 and 6 show typical horizontal venting For combustible wall passage of vent piping a U L listed thimble must be used See Fi...

Page 6: ...ltitudes 5500 to 7000 Ft Altitudes 7000 to 10 000 Ft Altitudes Equivalent Length of each 90 Elbow Ft Max Equivalent Length Ft VH 30 30 30 30 6 2 60 90 and 120 VH 150 30 30 15 6 2 VH 180 30 15 15 6 2 F...

Page 7: ...VICTORY II 7 Figure 6 Figure 5 VICTORY II HORIZONTAL VENTING All joints must be liquid and pressure tight Use U L listed single wall 3 dia AL29 4C S S venting materials See page 5...

Page 8: ...VICTORY 8 Figure 7...

Page 9: ...VICTORY Figure 8 9...

Page 10: ...lined masonry chimney If a masonry chimney is exposed to the outdoors on one or more sides below the roof line exposed chimney it must be re lined with a UL listed metallic liner system See Table 2 in...

Page 11: ...height and connector 11 9 VH 180 length restrictions 2 Connector may have to be upsized to 6 diameter to meet requirement of 11 9 Additional National Fuel Gas Code Boiler Gas Appliance Reference Tabl...

Page 12: ...VICTORY 12 Figure 9...

Page 13: ...VICTORY Figure 10 13...

Page 14: ...ional Fuel Gas Code ANSI Z223 1 latest edition C The boiler and its gas connection must be leak tested before placing the boiler in operation Use liquid soap solution for all gas leak testing DO NOT u...

Page 15: ...g arrangement 1 Supply and Return For tapping sizes see dimensions on page 2 Shut off valves are recommended 2 Circulating Systems Victory II boilers are equipped with a water circulating pump mounted...

Page 16: ...VICTORY 16...

Page 17: ...VICTORY Figure 14 Figure 15 Piping Arrangement 17...

Page 18: ...quipment PIPING A HEATING COOLING SYSTEM TO A WATER BOILER AND CHILLER Figure 16 illustrates a method of piping a heating cooling sys tem to a water boiler and a chiller Hand valves shown or automatic...

Page 19: ...sired setting 10 If appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service or gas supplier To Turn Off Gas to Appliance 1 Set thermostat to lowest settin...

Page 20: ...op of main burner tube C Main Burner Ignition Checkout and Pilot Adjustment 1 The pilot flame must not smother or snuff out when tested as follows a Main burner ignition from cold start repeat b Conti...

Page 21: ...m meter to burner including gas valve gas piping manifold and pilot burner DO NOT use open flame CARE AND MAINTENANCE This section must be brought to the attention of the o wner by the installer so th...

Page 22: ...ers are not firing 3 Annual Inspection and Cleaning The following must be done by a competent serviceperson to help insure safe and reliable operation A Flue passage cleaning See Figure 23 It is sugge...

Page 23: ...LVE OPENS IGNITOR OFF BOILER HEATING PERIOD WAIT FOR AIR PROVING SWITCH TO OPEN NO NO NO PILOT AND MAIN VALVE CLOSE NO YES YES YES YES YES NO NO Victory II Boiler Sequence of Operations BOILER WATER T...

Page 24: ...2 High limit of electronic Aquastat open nor mal condition 3 No power 4 Defective Aquastat 5 Defective transformer 6 Harnesses plug in connector is not securely connected at both ends 7 Damaged harne...

Page 25: ...at to call heat Remove connector marked B2 B1 R on Aquastat Check terminal B2 B1 for 24V Follow Smart Valve system troubleshooting in Smart Valve Honeywell Instruction Manual to find out if Smart Valv...

Page 26: ...nting system 4 Condensation trap is not full of water 4 Check and fill with water 5 Venting system is physically damaged 5 Check carefully and repair Also see Venting System Regular Inspection 6 Over...

Page 27: ...Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe conditi...

Page 28: ...VICTORY SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com...

Reviews: