background image

V

ICTORY 

II

CATEGORY 

II

AND

III

VENTING

1. Vent Material

A) The vent system for horizontal or vertical venting 
(Category 

II

and 

III

) must be UL listed single wall 3" 

diameter AL29-4C

stainless steel material. The follow-

ing manufacturers’ systems are approved for use within 
a specified minimum and maximum equivalent vent 
length for each model. Proper adapter must be used as 
a connector between Victory 

II

boilers flue collar and 

venting system as shown below:

Manufacturer 

Type/System 

Adapter Part No.

Heat-Fab, Inc.

Saf-T Vent

Not Required

ProTech System, Inc.

FasNSeal

FAS-V-SLANT

Flex-L International Inc.

Star-34

SRASFA3

Z-Flex Inc.

Z-Vent

02SVSSLA2

Heat-Fab Part Numbers for various items of vent system are
listed in Slant/Fin Part List, Publication No. VH-10PL.

B) When joining the various components of the above

listed vent systems, the manufacturers’ instructions
should be closely followed to insure proper sealing.

C) Use GE-RTV 106 or Dow Corning 732 Sealant for

sealing of pipe and fittings. See Figure 4 for proper
application of vent pipe sealant.

D) All vent connections must be liquid and pressure 

tight.

E) Flue vent system CANNOT be cut to length. Consult

manufacturer’s instructions. For Heat-Fab system, use
slip joint connector (Part No. 7324-GC) to adjust pipe
lengths dimensions.

F) DO NOT use plastic or galvanized flue pipe.

2. Flue Length Restriction

Maximum and minimum equivalent flue length for different

systems are given in the tables on page 6. Equivalent flue
length is sum of straight flue lengths and equivalent
length of elbows. The vent termination is in addition to the
allowed equivalent lengths.

Example: Boiler Model VH-180 is to be installed at sea level 
with 2 elbows using Heat-Fab vent system. Maximum
straight run would be: 40 - 2 x 3 = 34ft. If same boiler is to 
be installed in Colorado Springs (5,980 ft. altitude), the maxi-
mum straight run would be: 20 - 2 x 3 = 14 ft.

3. Installation 

A. Horizontal Venting:

Figures 5 and 6 show typical horizontal venting. For

combustible wall passage of vent piping a U.L. listed
thimble must be used. See Figures 5 and 6 for wall
thimble Part Numbers and more information.

B. Vertical Venting:

Figure 7 shows typical vertical venting. A fire stop is
required for each ceiling and floor penetration. An
existing chimney (see Figure 8) may be used as a
chase for vertical venting. Other appliances CANNOT
be vented into the same chimney or vent pipe within
the chimney.

For both, horizontal and vertical venting, the following
points MUST be followed:
A.  All Victory 

II

boilers are equipped with a built-in con-

densation drain and trap. The trap loop must be filled
with water. DO NOT operate the boiler without filling
the trap with water to prevent flue gas discharge into
space. The drain should extend to a floor drain or to a
container which may require emptying periodically. 

B. The horizontal vent pipe must be sloped upward from

the boiler at a pitch of at least 1/4" per 1 f oot of run, so
that the condensate from the vent system runs to the
drain trap.

C. The horizontal vent pipes must be supported with pipe

straps at intervals no greater than indicated by vent
pipe manufacturer’s instructions. The vertical portion
vent pipe also must be supported per manufacturer’s
instructions.

D.  Minimum clearances of vent pipes from combustible

constructions must be maintained (see Page 3).

E. Common venting with other appliances or another Vic-

tory 

II

boiler is NOT allowed.

F. The vent piping must terminate with a screened elbow

or tee. See Figures 5 and 6 for horizontal and 7 and 8
for vertical termination information. A cap termination
may be used for vertical venting.

G. See Appendix A for vent system location and conden-

sation drain requirements.

H. For roof passage of vent piping a U.L. listed roof flash-

ing must be used.

Figure 4. Vent Sealing Instructions

(Consult vent manufacturer’s instructions.)

5

:  AL 29-4C is a registered tr ademark of Allegheny Ludlum Corp.

Summary of Contents for victory II VH series

Page 1: ...is boiler is under positive pres sure when it is connected to the outdoors with 3 diameter pipe Leakage from this system can be hazardous and if not avoided can result in death or ser ious injury In a...

Page 2: ...0 3000 4000 5000 6000 7000 8000 9000 10000 Orifice Size for Sea Level Orifice Sizes for High Altitudes Includes 4 Reduction for Each 1000 Feet Elevation Feet Orifice sizes indicated for sea level abov...

Page 3: ...fueled shall not be installed in an abo ve grade under floor space or basement unless such loca tion is provided with an approved means for removal of unburned gas Consult Chapter 5 of the 1994 UNIFOR...

Page 4: ...ith a minimum FREE air passage area of 1 square inch per 1000 Btuh of total appliances input IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT THE AREA OF FREE OPENINGS MUST BE APPROPR...

Page 5: ...ght run would be 20 2 x 3 14 ft 3 Installation A Horizontal Venting Figures 5 and 6 show typical horizontal venting For combustible wall passage of vent piping a U L listed thimble must be used See Fi...

Page 6: ...ltitudes 5500 to 7000 Ft Altitudes 7000 to 10 000 Ft Altitudes Equivalent Length of each 90 Elbow Ft Max Equivalent Length Ft VH 30 30 30 30 6 2 60 90 and 120 VH 150 30 30 15 6 2 VH 180 30 15 15 6 2 F...

Page 7: ...VICTORY II 7 Figure 6 Figure 5 VICTORY II HORIZONTAL VENTING All joints must be liquid and pressure tight Use U L listed single wall 3 dia AL29 4C S S venting materials See page 5...

Page 8: ...VICTORY 8 Figure 7...

Page 9: ...VICTORY Figure 8 9...

Page 10: ...lined masonry chimney If a masonry chimney is exposed to the outdoors on one or more sides below the roof line exposed chimney it must be re lined with a UL listed metallic liner system See Table 2 in...

Page 11: ...height and connector 11 9 VH 180 length restrictions 2 Connector may have to be upsized to 6 diameter to meet requirement of 11 9 Additional National Fuel Gas Code Boiler Gas Appliance Reference Tabl...

Page 12: ...VICTORY 12 Figure 9...

Page 13: ...VICTORY Figure 10 13...

Page 14: ...ional Fuel Gas Code ANSI Z223 1 latest edition C The boiler and its gas connection must be leak tested before placing the boiler in operation Use liquid soap solution for all gas leak testing DO NOT u...

Page 15: ...g arrangement 1 Supply and Return For tapping sizes see dimensions on page 2 Shut off valves are recommended 2 Circulating Systems Victory II boilers are equipped with a water circulating pump mounted...

Page 16: ...VICTORY 16...

Page 17: ...VICTORY Figure 14 Figure 15 Piping Arrangement 17...

Page 18: ...quipment PIPING A HEATING COOLING SYSTEM TO A WATER BOILER AND CHILLER Figure 16 illustrates a method of piping a heating cooling sys tem to a water boiler and a chiller Hand valves shown or automatic...

Page 19: ...sired setting 10 If appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service or gas supplier To Turn Off Gas to Appliance 1 Set thermostat to lowest settin...

Page 20: ...op of main burner tube C Main Burner Ignition Checkout and Pilot Adjustment 1 The pilot flame must not smother or snuff out when tested as follows a Main burner ignition from cold start repeat b Conti...

Page 21: ...m meter to burner including gas valve gas piping manifold and pilot burner DO NOT use open flame CARE AND MAINTENANCE This section must be brought to the attention of the o wner by the installer so th...

Page 22: ...ers are not firing 3 Annual Inspection and Cleaning The following must be done by a competent serviceperson to help insure safe and reliable operation A Flue passage cleaning See Figure 23 It is sugge...

Page 23: ...LVE OPENS IGNITOR OFF BOILER HEATING PERIOD WAIT FOR AIR PROVING SWITCH TO OPEN NO NO NO PILOT AND MAIN VALVE CLOSE NO YES YES YES YES YES NO NO Victory II Boiler Sequence of Operations BOILER WATER T...

Page 24: ...2 High limit of electronic Aquastat open nor mal condition 3 No power 4 Defective Aquastat 5 Defective transformer 6 Harnesses plug in connector is not securely connected at both ends 7 Damaged harne...

Page 25: ...at to call heat Remove connector marked B2 B1 R on Aquastat Check terminal B2 B1 for 24V Follow Smart Valve system troubleshooting in Smart Valve Honeywell Instruction Manual to find out if Smart Valv...

Page 26: ...nting system 4 Condensation trap is not full of water 4 Check and fill with water 5 Venting system is physically damaged 5 Check carefully and repair Also see Venting System Regular Inspection 6 Over...

Page 27: ...Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe conditi...

Page 28: ...VICTORY SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com...

Reviews: