background image

14

®

STEP 5: SETUP SYSTEM FOR AUTOMATIC OPERATION

FOR INITIAL START-UP ONLY

• Remove jumper from across T1-T2 terminals and

reconnect wires to control board T1-T2 and A1-A2
terminals properly.

• Restore zone valves to automatic operation.
• Set thermostat(s) to call for heat.
• Set selector switches to AUTO, OP and HI.

FOR NORMAL SYSTEM START-UP

• Set selector switches to AUTO, OP and HI.

• Follow lighting instructions attached to boiler.
See index on Page 20 for reference lighting instructions
and sequence of operation.

Safe lighting and other performance criteria were met
with the gas manifold and control assembly provided on
the boiler when the boiler underwent tests specified in
ANSI Z21.13.

STEP 7: TEST COMMON VENTING SYSTEM (IF REQUIRED)

If existing boiler was removed from a common venting
system, common venting system may be too large for
proper venting of appliances remaining connected to it.

At the time of removal of existing boiler, the following
steps shall be followed with each appliance remaining
connected to common venting system placed in opera-
tion, while the other appliances remaining connected to
the common venting system are not in operation.

1. Seal any unused openings in common venting sys-

tem.

2. Visually inspect venting system for proper size and

horizontal pitch and determine there is no blockage
or restriction, leakage, corrosion and other deficien-
cies which could cause an unsafe condition.

3. Insofar as is practical, close all building doors and

windows and all doors between the space in which
the appliances remaining connected to the common
venting system are located and other spaces of build-
ing. Turn on clothes dryer and any appliance not con-
nected to common venting system. Turn on any
exhaust fans, such as range hoods and bathroom
exhausts, so they will operate at maximum speed.

DO NOT operate a summer exhaust fan. Close fire-
place dampers.

4. Place in operation the appliance being inspected.

Follow the lighting instructions. Adjust thermostat so
appliance will operate continuously.

5. Test for spillage at the draft hood relief opening after

5 minutes of main burner operation. Use the flame of
a match or candle, or smoke from cigarette, cigar or
pipe.

6. After it has been determined that each appliance

remaining connected to common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other gas-burning appliances to their previous
condition of use.

7. Any improper operation of common venting system

should be corrected so installation conforms with
National Fuel Gas Code ANSI Z223.1. When resizing
any portion of the common venting system, common
venting system should be resized to approach mini-
mum size as determined using appropriate tables in
Part II in National Fuel Gas Code ANSI Z223.1.

STEP 6: CHECK SYSTEM OPERATION

Purge Air One Final Time

• Let system water reach 160°. Temperature/pressure

gage should be between 12 and 25 psi.

• Bleed all air vents until water squirts out; start on low-

est floor with first air vent in the line of flow.

Check Exhaust and Air Intake Venting

• Check for and reseal any vent tubing leaks.
• Check for and remove any vent terminal obstructions.

Check Gas Valve Operation (With Burner Firing)

USE CAUTION - LINE VOLTAGE PRESENT.
• Disconnect flame sensor wire lead from flame sensor

tab. Gas valve should close.

• It is normal for boiler to re-try for ignition (3 times)

with wire removed from flame sensor, but gas valve
should only open for a few seconds during each re-try
and be closed between trials.

• Replace flame sensor wire lead on flame sensor tab.

Check High Limit Operation

HIGH LIMIT CANNOT BE SET BELOW 180°. HIGHEST
MAXIMUM ALLOWABLE SETTING IS 220°.
• Set thermostat high enough for the water temperature

to reach limit switch setting of 180°.

• When reached, limit switch should open and gas

valve should close.

Summary of Contents for Prodigy 21 KC-45

Page 1: ...11 Lighting Instructions 20 Measuring Equipment 12 Orifice Gas and Air Sizes 24 Purge Heating System 9 Replacement Parts 15 Safety Controls 14 Sequence of Operation 21 Thermostat Heat Anticipator 11 V...

Page 2: ...1 or applicable provisions of local building codes The boiler can be vented directly through a rear wall or through any wall within 10 feet of the right side left side or back of the boiler Venting i...

Page 3: ...flict in the above requirements then the more stringent require ment will apply WARNING LIQUEFIED PETROLEUM L P PROPANE GAS FIRED BOILER LOCATION REQUIRES SPECIAL ATTENTION Liquefied Petroleum L P pro...

Page 4: ...all finishing work 4 Secure the mounting panel see Figure 1 to wall using appropriate hardware 5 16 lag bolts provid ed for frame construction wall studs 5 16 wall anchors or expansion plugs if constr...

Page 5: ...Figure 4 provided with boiler and install assembly on boiler air intake inlet pointing toward outside wall opening 9 For extended rear wall venting only complete both of the tubing runs through outsid...

Page 6: ...type 4 Measure the distance from floor or ceiling whichev er is most level to the outside side wall to center of 9 x5 vent cutout on the wall panel 5 Measure the same distance on the outside side wal...

Page 7: ...If necessary cut the tubing to proper length and remove all burrs 13 Seal all tubing run joints and boiler con nections with a high temperature RTV sealant provided APPLY SEALANT TO OUTSIDE OF MALE T...

Page 8: ...proper sealing to wall c Check that the terminal itself is level and that its position ensures a 1 4 per foot downward pitch of the tubing from the boiler d Mark and drill out the location of the fou...

Page 9: ...d Standing Iron Radiant Systems A boiler by pass loop or equivalent will be required to avoid flue gas condensation on cast iron sections for low temperature application i e radiant floor systems Zone...

Page 10: ...toff valve recommend a full port ball type valve approved for use with gas a ground joint union and full size sediment trap Piping Supports Horizontal piping must be supported by hangers not by the bo...

Page 11: ...ne valves indirect fired water heater and reference boiler diagram OPTIONS AVAILABLE Domestic Hot Water Installation The boiler will run at high fire mode for maximum recovery of the Storage Tank when...

Page 12: ...RATION EQUIPMENT Pressure measurement fittings There are 3 service fittings with caps provided on this boiler for convenient calibration of the air gas ratio and input in the field See Figure 18 for t...

Page 13: ...NECESSARY Turn Blower Speed Adjustment Pot HI for high fire or LO for low fire in small increments clockwise to increase input or coun terclockwise to decrease input Allow for stabilization of operati...

Page 14: ...perate a summer exhaust fan Close fire place dampers 4 Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously 5 Test...

Page 15: ...Shutdown Controls Check operation as detailed on Page 14 in this manual Air Filter Replace recommended or clean annually more often if conditions dictate Slant Fin replacement air filter part number...

Page 16: ...off If the boiler does not restart the diagnostic light will return to either Steady On or the series of flashes Boiler Failure Codes Page Continuous Flashing Electronic Control Failure 17 1 Flash Hig...

Page 17: ...ration as shown in Part 3 in manual Check gas and air orifice size see How To Do It on Page 19 Check power wiring to electronic board hot wire to L1 neutral to L2 ground wire in junction box and to el...

Page 18: ...Water Level Too Low Circulator Not Running Zone Valves Not Opening Set high limit to lowest setting 180 run boiler to get water temperature above 180 Check for continuity across high limit contacts Ch...

Page 19: ...crews securing mixing elbow to burner enclosure and remove mixing elbow For gas orifice unscrew counterclockwise gas ori fice tube from mixing elbow Note identifying stamp on tube for size For air ori...

Page 20: ...No 65 0641 22 Zoning With Zone Valves DHW Included 20 For Lighting Instructions Locate lighting instructions label attached to your boiler A Slant Fin part number is printed in the lower right corner...

Page 21: ...CONTINUES TO RUN BLOWER OFF DISPLAY FAULT CIRCULATOR CONTINUES TO RUN BLOWER OFF DISPLAY FAULT CIRCULATOR CONTINUES TO RUN BLOWER OFF DISPLAY FAULT CIRCULATOR AND BLOWER CONTINUE TO RUN HOT SURFACE IG...

Page 22: ...22...

Page 23: ...cess panel OPERATING INSTRUCTIONS Label 65 0645 STOP Read the safety information above on this label Set the thermostat to lowest setting Turn off all electric power to the appliance This appliance is...

Page 24: ...r Orifice Size Identifying Plate Notches BOILER PACKING LIST Boiler Instruction Manual Replacement Parts List User s Information Manual Lifetime Limited Warranty Wall Mounting Panel 5 16 Lag Bolts 4 5...

Reviews: