Gas Main Sizing

To determine the correct pipe diameter for the gas main serving a specific Caravan 

system, proceed as follows:

a. Follow the building plans, find total length of straight pipe between supply from gas

meter and boiler gas header.

b. Using data in Table 4, calculate equivalent linear length of screw pipe fittings used in

fabrications of main. Add this to figure from step (a) to obtain equivalent total length.

c. Find Caravan gas consumption in cubic feet per hour from Table 3 in hot water 

systems.

d. Multiply the system total hourly gas consumption by flow correction value from 

Table 5.

e. Locate system’s total equivalent pipe length in right column of Table 6. 

f.

Move vertically to the system’s corrected flow rate calculated in step (c). If this value

falls between two of those listed, select larger value.

g. From this point move horizontally to the left column and read suggested pipe 

diameter for gas main.

GGT-600E

600

GGHT-700E

700

GGHT-750E

750

GGHT-800E

798

GGT-900E

900

GGHT-1050E

1050

GGHT-1125E

1125

GGHT-1200E

1197

GGT-1200E

1200

GGHT-1400E

1400

GGHT-1500E

1500

GGT-1500E

1500

GGHT-1600E

1596

GGHT-1750E

1750

GGHT-1875E

1875

GGHT-2000E

1995

GGHT-2100E

2100

GGHT-2250E

2250

GGHT-2400E

2394

GGHT-2450E

2450

GGHT-2625E

2625

GGHT-2800E

2793

GGHT-2800AE

2800

GGHT-3000E

3000

GGHT-3150E

3150

GGHT-3200E

3192

GGHT-3375E

3375

GGHT-3500E

3500

GGHT-3600E

3591

GGHT-3750E

3750

GGHT-4000E

3990

1/2

0.84

0.52

0.41

0.031

2.50

1.12

1.25

1.66

3/4

1.17

0.73

0.57

0.044

3.50

1.84

1.75

2.33

1

1.57

0.98

0.77

0.057

4.68

2.11

2.34

3.11

1-1/4

2.19

1.37

1.07

0.082

6.54

2.94

3.27

4.35

1-1/2

2.63

1.64

1.29

0.098

7.84

3.52

3.92

5.21

2

3.55

2.23

1.74

1.320

10.60

4.77

5.30

7.05

3

5.72

3.59

2.81

2.130

17.08

7.69

8.84

11.40

Model No.

Gas

Consumption In CFH

Table 3: Gas consumption rate

hot water boilers only

Table 4: Equivalent linear length in feet of standard iron pipe fittings for natural gas

Figure 11. Typical gas supply line installation

Pipe 

Size

Inches

Standard

Medium

Sweep

Long

Sweep

Gate

Globe

Angle

Return

Bend

Side

Outlet

Tee

Elbow

Valve

GAS PIPING

This section contains sizing and construction recommendations

for fuel supply piping to Caravan gas-fired modular boiler 

systems. Gas-fired equipment must conform not only to codes of

local regulatory agencies, but also to additional specifications that

may be imposed by the utility or gas supplier. Therefore, the 

following information should be considered only as a guideline.

Figure 11 illustrates a typical gas supply line installation. It 

consists of a main between the utility’s meter box and the boiler

system, a main shut-off valve sediment trap, gas header pipe and

drip legs on individual boilers.

Individual gas lines to individual boiler modules should be 

3

4

diameter. Size of gas main and header pipes depends on volume

of gas required and acceptable pressure drop between meter and

modules’ gas regulator valves. Minimum pressure required at each

valve is 5 inches of water column for natural gas and 11 inches for

propane gas, measured while all boilers and other gas-fired 

equipment on the same meter are firing. Small variations in gas

flow can be compensated for by adjusting gas regulator valves.

However, final pressure of gas header must vary no more than

+ 0.3 in. of water column.

Summary of Contents for CARAVAN GGHT-1050E

Page 1: ...al electri cal codes The unit must be electrically grounded if an external power source is used In Canada the installation must be in accordance with standards CGA B149 1 and B149 2 installation codes...

Page 2: ...394 1932 11202 1680 57 7 80 60 61 8 3660 301 16 665 8 10 1323 32 253 16 115 16 15 10 3 GGHT 2450E 7 GG 350HES 2450 1995 11571 1736 59 6 81 40 72 1 4270 301 16 671 8 9 1323 32 253 16 115 16 18 6 3 GGHT...

Page 3: ...3 Design Data Max ASME Working Pressure 100 psi Power Requirements 120 volts 60 HZ 34 amps per module Figure 1 Gas Caravan dimensions and typical piping hot water models...

Page 4: ...r piping for variable circulation Figure 3 Supply and return piping locations Figure 4 Instantaneous tankless coil two temperature with recirculation Figure 5 Storage tank from tankless coil with reci...

Page 5: ...cify 30 50 or 100 psi Control header unmounted one per system Draft hoods unmounted OPTIONAL EQUIPMENT Hot water supply and return header assemblies Control panel with automatic lead lag Spark ignitio...

Page 6: ...opening near the floor below burner air inlet and one louvered opening near the ceiling above the highest draft regulator each opening with a minimum FREE air passage area of 1 square inch per 4000 B...

Page 7: ...7 Figure 8 Typical layouts for gas fired systems...

Page 8: ...p obstruction A vent cap should be used where permitted for additional protection against adverse wind conditions and precipitation The National Board of Fire Underwriters recommend that the chimney s...

Page 9: ...Table 2a depicts the proper diameter Dim C of the connec tor rise depending upon its total length top of the draft hoods to the breeching above Based on single row of modules with no elbows NOTE For c...

Page 10: ...1 2 34 3 11 1 1 4 2 19 1 37 1 07 0 082 6 54 2 94 3 27 4 35 1 1 2 2 63 1 64 1 29 0 098 7 84 3 52 3 92 5 21 2 3 55 2 23 1 74 1 320 10 60 4 77 5 30 7 05 3 5 72 3 59 2 81 2 130 17 08 7 69 8 84 11 40 Model...

Page 11: ...ize only as many modules as the system load requires Only one stage cycles at a time The other stages remain off or operate continuously thereby performing at peak efficiency For example in a 10 modul...

Page 12: ...increases The control activates only the number of stages required to maintain the required supply water temperature 2 Setpoint temperature The control maintains a set supply water temperature The co...

Page 13: ...13 FIELD WIRING AT MODULES...

Page 14: ...14 SC 3 SYSTEM WIRING DIAGRAM...

Page 15: ...15 SC 3 LADDER WIRING DIAGRAM...

Page 16: ...16 SC 9 SPACE HEATING WIRING DIAGRAM...

Page 17: ...17 SC 9 SPACE HEATING LADDER WIRING DIAGRAM...

Page 18: ...18 SC 9 SPACE AND DOMESTIC HOT WATER WIRING DIAGRAM...

Page 19: ...19 SC 9 SPACE AND DOMESTIC HOT WATER LADDER WIRING DIAGRAM...

Page 20: ...stallation If any parts are found to be defective in material or workmanship Slant Fin will repair or replace the defective parts SECOND THROUGH TENTH YEAR LIMITED WARRANTY FOR CAST IRON SECTION ASSEM...

Page 21: ...bustion chamber tankless heater exhaust and air inlet pip ing burner enclosure mixing elbow gas and air orifice blower assembly air filter and electrical and mechanical components fur nished to Slant...

Page 22: ...22 NOTES...

Page 23: ...CARAVAN SYSTEM RATING PLATE System rating plate format for Caravan modular boiler system System rating plates are available upon request using the form on the back cover 23...

Page 24: ...s shipped with a rating plate bearing the model serial number capacities and certifications for that module A modular boiler system is a single boiler To meet local requirements a system rating plate...

Reviews: