DOL Extension Box

8

Technical User Guide

Jumper setting

1. Adjust the jumpers (

A

) and (

B

)

ON

 = Emergency opening can override relay so inlet opens.

OFF

 = Factory setting. Emergency opening cannot override re-

lay.

AI

 = Analog input.

DI

 = Digital input

DOL 12

= DOL 12 input

0-10 V inputs on the I/O module are set to:

Setting

Application

Placement

TEMP-INPUT 
DOL 12 SENSOR

Temperature sensor input DOL 12

Topmost 2 pins

CONTACT-INPUT - Di 
1k PULL-DOWN

E.g., water meter (digital input) 
(

pull down resistance = ON

)

Lowermost 2 pins

ANALOG-INPUT - Ai 
0 – 10V

E.g., humidity sensor (0-10V input) 
(

pull down resistance = OFF

)

Lowermost 1 pin, or remove
the jumper.

Summary of Contents for DOL

Page 1: ...022 03 09 English For other language variants of this document we refer to Espa ol Para otras variantes del idioma de este documento visite Fran ais Pour les versions dans d autres langues de ce docum...

Page 2: ......

Page 3: ...ion box Small 10RL with 1 x IO type 3 10RL 8AI 8AO 136471 DOL extension box Small 20RL with 2 x IO type 3 10RL 8AI 8AO The structure of the manual follows the required work routines By following the i...

Page 4: ...t of the tools recommended for the installation Item Description Crosshead screwdriver Screwdriver straight slot 2 pcs Power drill Hammer Number Description 1 DOL extension box with one or two I O mod...

Page 5: ...controller 2 Knock out the required number of knock out pieces B in the bottom section of the cabinet and mount the plastic glands C 3 Prick drill holes for the 4 screws in the bottom section of the c...

Page 6: ...plug from I O module 1 in the controller to I O module 2 in the extension box A 2 Connect the flat cable plug from I O module 2 to I O module 3 in the extension box B 3 Set the jumper OFF ON C on the...

Page 7: ...FF ON D on the extension box I O module 2 to ON Set the rotary switch of the I O modules as follows I O module 1 I O module 2 Address 1 Address 2 1 Connect the extension box earthing contact F to the...

Page 8: ...og input DI Digital input DOL 12 DOL 12 input 0 10 V inputs on the I O module are set to Setting Application Placement TEMP INPUT DOL 12 SENSOR Temperature sensor input DOL 12 Topmost 2 pins CONTACT I...

Page 9: ...pply 24V DC 20 0 4 A Relays 10 x NO NC potential free max Max voltage current at resistive load 250 V AC 5 A AC Max voltage current at inductive load 250 V AC 2 A AC CosPhi 0 8 Mechanical Cable knock...

Page 10: ...DOL Extension Box 10 Technical User Guide 4 1 Dimensioned sketch...

Page 11: ......

Page 12: ...604066 2022 03 09 en US Made in Denmark SKOV A S Hedelund 4 Glyng re DK 7870 Roslev Tel 45 72 17 55 55 www skov com E mail skov skov dk...

Reviews: