DA 60-820
58
Technical User Guide
445038 DA 820-12 LPC 1x230 V
DA 60-820 roof
inlet with inter-
mediate plate
DA 60-820 roof
inlet without in-
termediate
plate
DA 60-820
ceiling with in-
termediate
plate
DA 60-820
ceiling without
intermediate
plate
Air output at -50 Pa
m
3
/h
26850
24350
29450
26050
Air output at -40 Pa
m
3
/h
26200
23600
28500
25300
Air output at -30 Pa
m
3
/h
25450
22900
27900
24800
Air output at -20 Pa
m
3
/h
25050
22350
27200
24200
Air output at -10 Pa
m
3
/h
24350
21700
26500
23400
Air output at 0 Pa
m
3
/h
23750
21150
25800
23000
Air output at 10 Pa
m
3
/h
23050
20350
25100
22100
Air output at 20 Pa
m
3
/h
22250
19650
24300
21400
Power consumption at -10 Pa
W
1307
1346
1244
1336
Specific output at -10 Pa
m
3
/kWh
18600
16150
21300
17500
Specific energy at -10 Pa
Watt/1000
m
3
/h
53.7
62
46.9
57.1
Testing body
SKOV A/S
Environment
Temperature, operation
°C
÷ 40 to + 40
Start temperature
°C
÷ 40 to + 50
Storage temperature
°C
÷ 40 to + 70
Ambient humidity, operation
% RH
10 - 95
Protection class
IP
Motor controller: IP 65 Fan motor: IP 55
Fan noise, outside
(2 m, 45 degrees)
dB (A)
73
Shipment
Motor controller - dimensions
H x W x D
mm
266 x 185 x 90
Fan - dimensions (H x W x D)
mm
278 x 800 x 800
Weight
g
21432
Shipping weight
g
26117