Replacement Procedures
Service Manual
To replace the evaporator probe
Service Probe
A service probe is required when testing/running the refrigeration unit
outside of the cabinet and should be used for bench testing when the cabinet
control probe cannot be plugged into the unit. Refer to part details below:
The service probe plugs into the control probe socket on the RH side of the
refrigeration unit.
To use the service probe
1. Remove the front panel, isolate the chiller from the mains power supply and
remove the refrigeration unit (see page 33).
2. Detach the evaporator fan assembly from the evaporator coil by undoing the
four fixing screws (two at each end), and place the evaporator fan assembly
out of the way.
3. Withdraw the probe from the evaporator coil and detach the probe cable
from the refrigeration unit.
4. Remove the electronic controller (see page 36).
5. Detach the evaporator probe cable from the rear of the electronic controller
and withdraw the cable (and probe) from the refrigeration unit.
6. Fit the new probe cable following the same path as the original cable.
7. Feed the probe up
inbetween the fifth and
sixth fins and the first
and second pipes in the
evaporator coil. Crimp
the fins to hold the probe
in place.
8. Ensure the probe cable is securely attached to the unit and reassemble.
Description
Part No.
Service probe
FLX10106-99
1. Connect the probe to the
control probe plug on the
RH side of the
refrigeration unit. The
probe end can be placed
in areas of varying
temperature depending
on the type of testing
being completed.