Section 9: COMMISSIONING THE APPLIANCE
Turn on and test the gas supply up to the fire for any leaks, in accordance with current
Approved Codes of Practice (ACOPs)
Section 10: OPERATING THE APPLIANCE
(See Section 18 Users Instruction)
SECTION 11: SETTING PRESSURE
Remove the pressure test point sealing screw from the isolation elbow and attach a suitable pressure
gauge.
Check that the standing inlet gas pressure is at 20 mbar
Light the pilot and check the correct operation of the burner at all the flame settings.
Refer to the Operating instructions section 10.1
Check that the inlet gas pressure is at 20 mbar when the fire is at its highest setting.
Once the fire has been lit for 5 minutes, turn the gas OFF at the isolating elbow.
After a further 3 minutes turn the gas supply ON again, if the gas has stopped flowing, the Flame
Supervision Device (FSD) is operating correctly.
Always check that the gas has stopped flowing even if you hear the FSD valve close within the 3-minute
period.
Turn OFF the appliance and the gas supply and refit the pressure test point sealing screw.