Installation Instructions

 

Specifi cations are subject to change without notice  

Page 2

[email protected] | www.manrose.co.nz 

Distributed by Simx Limited

Inline Extraction Fan Kits - 150mm Std Profi le

REGULATIONS AND STANDARDS

Choosing the Right Fan to Comply

Fans cannot be selected on the basis of free-air performance only. Fans must now be selected on the basis of the complete installed system 
performance for a designated room as per the table below.

1)  Toilets only require ventilation if they have no openable windows
2)  Simx recommends 40 l/s for laundries with unvented non-condensing tumble dryers as covered in AS 1668: Part 2 2012

Recent unregulated extract fan practices in New Zealand has trended to basic, low pressure axial fan products, as installed system performance has 
not been defined for independent inspection testing and compliance signed off by local authorities. 

New Zealand Building Code and Healthy Homes

The following two category requirements have been established for mandatory extraction ventilation in New Zealand.

The New Zealand Building Code for New Building Consents

The building regulatory system sets out a framework to promote good quality decisions being made during the Building Consent process. The 
legislation and regulations work together, as the building regulatory system. The functional clauses of the NZ Building Code are grouped and 
described by a letter and number. Clause G of the NZ Building Code covers services, with G4 setting out the performance requirements for 
ventilation. The Building Code is enshrined in law. The New Zealand Building Code, G4, has been changed. This is supported by Acceptable Solution 
G4/AS1 Fourth Edition that specifies mechanical ventilation in accommodation units that contain cooktops, showers and baths. 

Residential Tenancy Regulations to the Healthy Homes Standards

Residential Tenancy Regulations for rental properties only is changing to the Healthy Homes Standards, sub part 4 - Ventilation Standards.

Complying with the Acceptable Solution G4/AS1

To comply, the mandatory mechanical extract system must deliver minimum airflow rates for the complete installed ventilation system. This means 
that airflow rates must deliver the airflow after resistance of the ducting, internal and external grilles, as well as all other accessories, such as 
backdraught shutters, are included.

Fan selection is important as some types are far better at overcoming ducting system pressure drops.

Additionally, the quality of the ducting system installation can be all important. Rigid duct systems (see page 102) are best as they are the most 
efficient. Good installation practice is vital for flexible duct systems.

Room

Airflow Rate (min.)

Intermittent

Continuous

Toilet

1)

25 l/s

10 l/s

Bathroom/shower

25 l/s

10 l/s

Laundry

2)

40 l/s

-

Kitchen

50 l/s

12 l/s

Duct Supports

Exterior Grille

Airflow

Airflow

Interior Grille

Sealant

Cavity

Sleeve

Maximum length of
flexible ducting

Minimum radius =
diameter of ducting

Bathroom

Kitchen

25 l/s

Metres of Ducting

50 l/s

Metres of Ducting

1

2

3

4

5

6

7

8

9

10

1

2

3

4

5

6

7

8

9

10

No. of 

Bends

1

No. of 

Bends

1

2

2

3

3

4

4

5

5

Fan Selection

Hyper150 EC

Mixflo 150

Blue Jet

Preferred flexible 

ducting route

Peaks and troughs

Restrictions

Summary of Contents for Manrose

Page 1: ...anrose inline extraction fan kit is designed for ventilation within a shower cubicle The high performance fan provides high levels of extraction and enables additional ducting to be added to this syst...

Page 2: ...for ventilation The Building Code is enshrined in law The New Zealand Building Code G4 has been changed This is supported by Acceptable Solution G4 AS1 Fourth Edition that specifies mechanical ventil...

Page 3: ...se of damage to the supply cord switch off the device and do not tamper with it Damaged supply cords must only be repaired or replaced exclusively by the manufacturer or by an appointed representative...

Page 4: ...manrose co nz www manrose co nz Distributed by Simx Limited Inline Extraction Fan Kits 150mm Std Profile ELECTRICAL CONNECTIONS BROWN BLUE LIVE EARTH NEUTRAL GREEN YELLOW F N TIMER FAN2444 LIVE NEUTR...

Page 5: ...nding slots in the black housing adjacent to the ends of the bridge piece in the housing 4 Select a suitable place for the fan to be screwed to a joist and secure using two screws through the fixing b...

Page 6: ...Switching model FAN0102 Diagram 2 The fan can be connected to the light switch so that the fan will start when the light is switched on or a dedicated fan switch not supplied The fan should not be acc...

Page 7: ...for a consequential loss or any other loss or damage caused to property or persons arising from any cause whatsoever b damage to consumable items such as lamps and starters and c damage arising from...

Reviews: