TEST MODE - 3 LEDS PARTIALLY VISIBLE

The lamp will now illuminate for approximately 5 seconds every time movement is detected.
Walk across the detection area approximately 5 metres from the unit. Each time you are detected
the lamp will illuminate. Now stand still until the lamp extinguishes (this should take approx. 5
seconds)
Start moving again, when you are detected again the lamp will illuminate.
Repeat the above, walking at various angles and distances to the unit. This will help you to
establish the detection pattern.

If the detection area is too small for your requirements, try angling the sensor head up.
Angling the head downwards will reduce the detection area should a smaller range be required.

SETTING UP FOR SENSOR CONTROL MODE - 3 SCROLLING LED’S VISIBLE

When walk tests are complete, the unit will be switch into

Sensor Control Mode

.

Simply cease movement within the detection area for approximately 60 seconds, 

ensure the

lamp is not illuminated

. The unit will then switch to 

Sensor Control Mode

, this is indicated by

the illumination of three scrolling LEDS in the top transparent area of the sensor head. These
LED's will scroll from left to right during daylight and darkness.

The TIME setting controls how long the unit remains illuminated following activation and after all
motion ceases.
(See diagram G. the time adjustment knob is indicated by the "Clock" symbol).

The minimum time (fully anti-clockwise) is approx. 5 seconds, whilst the maximum time (fully
clockwise) is approx. 5 minutes. Set the control to the desired setting between these limits.

The DUSK control determines the level of darkness required for the unit to start operating. The
setting is best achieved by the procedure below:
(See diagram G. the Dusk adjustment knob is indicated by the "Moon" and "Sun symbols).
Set the DUSK control knob fully anti clockwise. Wait until darkness falls.
When the ambient light level reaches the level of darkness at which you wish the lamp to
become operative (i.e.: at dusk) SLOWLY rotate the control in a clockwise direction until a point
is reached where the lamp illuminates. Leave the control set at this point.

At this position the unit should become operative at approximately the same level of darkness
each evening. Observe the operation of the unit. If the unit is starting to operate too early (i.e.:
when it is quite light) adjust the control slightly anti-clockwise. If the unit starts to operate too late
(i.e.: when it is very dark). Adjust the control slightly clockwise.  Continue to adjust until the unit
operates as desired.  The LED's will scroll from left to right, day and night; indicating the unit is in

Sensor Control Mode

. The LED's will extinguish when the PIR activates the light for as long as

the lamp is illuminated.

MASKING THE SENSOR LENS

To restrict the sensor coverage, preventing detection in unwanted areas, mask the sensor lens
using the masks provided in the accessory pack (see diagram H). For your information, the top
section of the lens covers long range detection, the bottom covers short range. Similarly the left
and right lens sections cover the left and right detection areas respectively.

SETTING UP FOR MANUAL CONTROL - SINGLE LED ILLUMINATED

The light can be switched on for longer time periods by use of the 

Manual Control Mode

. This

can be activated at night by using the internal wall switch or circuit breaker.
Switch the internal wall switch/circuit breaker twice (off/on, off/on) within 2 seconds. The unit will
now illuminate continuously until it is switched back into 

Sensor Control Mode 

or until the unit

automatically resets itself into 

Sensor Control Mode

at dawn.

LHT0090&91 251012:newnlht009091.qxd  10/26/12  5:17 PM  Page 7

Summary of Contents for LHT0090

Page 1: ...LHT0090 LHT0091 LHT0152 SECURITY FLOODLIGHT INSTALLATION MANUAL LHT0090 91 251012 newnlht009091 qxd 10 26 12 5 17 PM Page 1 ...

Page 2: ...TOP VIEW 200º SIDE VIEW 12m 2 5m Less sensitive More sensitive A C B D LHT0090 91 251012 newnlht009091 qxd 10 26 12 5 17 PM Page 2 ...

Page 3: ...cement or repair of the Goods only at our option To the extent permitted by law we exclude liability for a consequential loss or any other loss or damage caused to property or persons arising from any cause whatsoever b damage to consumable items such as lamps and starters and c damage arising from normal wear and tear 4 In order to claim under this warranty you must within the Warranty Period ret...

Page 4: ...ctrician SECTION TWO SELECTING THE LOCATION The motion detector has a number of detection zones at various vertical and horizontal angles as shown see diagram A A moving human body needs to cross enter one of these zones to activate the sensor The best all round coverage is achieved with the unit mounted at the optimum height of 2 5m Careful positioning of the sensor will be required to ensure opt...

Page 5: ...re the bulb is correctly fitted in the lampholder before use Re attach the front cover do not overtighten the fixing screw IMPORTANT Switch off the electricity at the fuse box by removing the relevant fuse or switching off the circuit breaker before proceeding with the installation CONNECTION This unit is supplied with a hanging attachment tether to aid installation If it is not required simply re...

Page 6: ...e is set to a minimum If not set as shown in diagram G Max turn knob clockwise min turn knob anticlockwise Turn the power to the unit on The lamp will illuminate for approximately 30 seconds This indicates the unit is wired correctly After approximately 30 seconds the light will turn off The unit is now in Test Mode The diagram below also shows the required connections for the addition of slave lu...

Page 7: ...tment knob is indicated by the Moon and Sun symbols Set the DUSK control knob fully anti clockwise Wait until darkness falls When the ambient light level reaches the level of darkness at which you wish the lamp to become operative i e at dusk SLOWLY rotate the control in a clockwise direction until a point is reached where the lamp illuminates Leave the control set at this point At this position t...

Page 8: ...d time between 1 and 8 hours The time can be set by rotating the centre adjustment knob as required See diagram G the adjustment knob is identified by the letter T inside a circle Do not adjust this setting if you do not wish to use the Time Control Mode facility This time adjustment is factory set to 1 hour Please note Fully anticlockwise is 1 hour fully clockwise is 8 hours After the defined per...

Page 9: ... with one second and the unit will return to Sensor Control Mode The light will illuminate only when motion is detected Sensor Control Mode is indicated by scrolling LEDs from Left to right You may not be allowing the unit time to complete it s warm up period Stand well out of the detection range and wait the warm up period should never exceed 1 minutes Occasionally winds may activate the sensor S...

Page 10: ...lowly clockwise until the lamp illuminates Refer to previous section for more details The level of ambient light in the area may be too dark for the current DUSK setting During daylight adjust the DUSK control slightly anti clockwise When the lamp load extinguishes enter the detection area If the PIR still activates the setting is still too high Repeat the above procedure until the PIR does not ac...

Page 11: ...n Restrict short detection Restrict RHS detection Restrict LHS detection Dusk Dawn LUX Sensor on time control MOVEMENT TIMER Time Control Adjuster factory set to 1 hr min DUSK TIMER LHT0090 91 251012 newnlht009091 qxd 10 26 12 5 17 PM Page 11 ...

Page 12: ...this edge against wall and use diagram to estimate incoming cable length INCOMING WIRE TEMPLATE Use this diagram to estimate incoming cable length LHT0090 91 251012 newnlht009091 qxd 10 26 12 5 17 PM Page 12 ...