Diagram 5a
Verify the ground connection to the IFC module at terminal X5 and the valve.
Do not alter any ground wires as installed by the manufacturer.
IFC to Valve Ground
Connection
Ground from DFC wire harness to
valve
Diagram 5b
Remove the spark electrode wire from X2. Connect a jumper wire to the exposed spade terminal. Hold the opposite end of the
jumper 1/8” away from ground and turn the unit on. If there is a spark replace the electrode, if not replace the IFC.
SW1 Button
Step Motor “X6”
8 Pin Harness “X5”
ON/OFF Switch “X4”
Flame Sensor “X3”
Ignitor “X2”
Ground “X1”
Power Supply “X1”
Fan Kit
“X10”
Light Kit “X11”
Spark Electrode
Connection “X2”
38
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 2 TROUBLESHOOTING
SimTech Proflame II