25
NOTE: The outputs for this counter activate regardless of count direction in all count
modes.
1)
To set the Output Control modes, enter the Programming Mode, and press until the
oput 1 setup menu category is reached.
2)
Press to continue to the Parameter Name mmode1. The display will flash between
mmode1 and the default value of latch. When the display shows latch, press .
3)
Use the arrow keys to select the correct mode. Press when the correct mode is se-
lected to accept value, and to the next parameter, Output 1 Bindings. Other choices may
appear, depending on which Output 1 Mode is selected. See Appendix B for which op-
tions correspond to which parameters.
4)
Press until oput 2 setup is displayed, to make similar selections for Output 2 Mode.
5)
When all selections are entered and accepted into counter memory, counter will proceed
to next menu category, Set Point Setup.
4.6 Set Point Parameters (Set Point Setup)
The S663 has four set point parameters and a special value referred to as Reset Position.
The Reset Position can be referred to as Count Reset Value.
SP1 and SP2 are used only with Output 1, and SP3 and SP4 are used only with Output 2.
The SP1 and SP3 parameters are used as Latched or Timed “trigger” values. When a Boundary
Output is selected, SP1 and SP3 become the low boundary value.
The SP2 and SP4 parameters are used as high boundary value or ‘turn-off’ values when used
with other alarm types (i.e. latched until SP4).
The values for all set points are -99999 to 999999. The decimal point will appear according to
the current decimal point setting.
Set Point Parameters
1)
To set the Set Point parameters, enter the Programming Mode, and press until the
setpnt setup menu category is reached.
2)
Press to continue to the Parameter Name sp 1. The display will flash between sp 1
and the default value of 000010. When the display shows 000010, press .
3)
Use the arrow keys to enter the correct value of the flashing digit. Use the key to
advance to the next digit. Press
when the correct set point is selected to accept value
and proceed to the next parameter, SP 2.
4)
Repeat these steps for SP 2, SP 3, and SP 4. The counter will proceed to the next menu
category, Reset Setup.
ENTER
ENTER
ENTER
ENTER
ENTER
RESET
ENTER
ENTER