TrueAlarm Information Details 

 

True Alarm sensor data

 can be displayed on the 

system LCD, on a remote maintenance PC, or printed on a 
remote printer. With the proper operator access, a 
TrueAlarm Service Report can be generated to list the 
specific details of each TrueAlarm device. This report, as 
well as the Status Report can either be displayed on the 
remote maintenance PC or captured permanently by using 
a remote 80 character printer. 

Status and Service Reports.

 The report samples 

below illustrate the format provided on either the remote 
maintenance PC or a printer. This information is available 
at the system LCD by identifying the specific point of 
interest and reading one point at a time. 

Compatible Printer.

 Model 4190-9013 is a UL 

Standard 864 listed 80 column, 24 pin dot matrix printer 
(refer to data sheet S4190-0011).  

4010 Fire Alarm

Control Panel

Printer (Simplex

model 4190-9013)

Remote authorized maintenance
computer connected via dial-up
Service Modem Connection

FIRE ALARM

CONTROL

D ISC ON NEC T

POWER  BEFORE

SER VIC ING

CAUTION

** SYSTEM IS NORMAL **

12:02:15pm                          Mon  8-Mar-99

S UPV
ACK

SYSTEM

SUPERVISORY

ALARM
A CK

FIRE
ALARM

 TROU BLE

ACK

SYSTEM
TROUBLE

ALARM
SILENCE

ALARM

SILENCED

SYSTEM
RES ET

AC

POWER

Local

maintenance

computer

One connection type per 4010,
selected by module choice; max.
wiring distance is 300 ft (91 m)
@ 9600 baud

 

RS-232 Connection Options  

(refer to module selection on page 6) 

 

 

 4 

S4010-0001-14 

 

6/2014

 

Simplex 4010 Fire Alarm System 

Page 1 

REPORT 4 : TrueAlarm Service Report 

2:56:09 pm  Tue 10-Jun-14 

 
 

 

 

 

 

 

 

 

Dev 
Num 

 
Custom Label 

 Alarm 

at: 

Avg 
val 

Current/  

% alarm 

Peak/ 

% alarm 

State

ANALOG PHOTO - CLEAN ROOM 

 0.5/ 83 

 67 

 68/ 1% 

 72/ 10% 

NOR 

ANALOG ION - CLEAN ROOM 

 1.3/209 

 94 

 97/ 2% 

101/  1% 

NOR 

ANALOG PHOTO - MAIN LOBBY 

 2.5/185 

117 

117/ 0% 

125/ 42% 

NOR 

ANALOG PHOTO - CONFERENCE ROOM 1 

 2.5/161 

 93 

 93/ 0% 

 93/  0% 

NOR 

10 

HEAT DETECTOR - GARAGE 

135F/253 

–-- 

 63/-67F 

 66/ 69F 

NOR 

11 

ANALOG PHOTO - KITCHEN 

 3.7/216 

116 

116/ 1% 

110/ 36% 

NOR 

END OF REPORT 

Typical TrueAlarm Service Report Information Printout and/or Maintenance PC Screen

 

 

Simplex 4010 Fire Alarm System 

Page 1 

REPORT 3 : TrueAlarm Status Report 

2:43:03 pm Tue 10-Jun-14 

 
 

 

 

 

 

Zone 
Name 

 
Custom Label 

 Sensi- 

tivity 

 
Device Status  

Almost 

Dirty

M1-1 

ANALOG PHOTO 

CLEAN ROOM 

0.5 % 

NORMAL 

M1-2 

ANALOG ION 

CLEAN ROOM 

1.3 % 

NORMAL 

M1-3 

ANALOG PHOTO 

MAIN LOBBY 

2.5 % 

NORMAL 

*YES*

M1-4 

ANALOG PHOTO 

CONFERENCE ROOM 1 

2.5 % 

NORMAL 

M1-10 

HEAT DETECTOR 

GARAGE 

135 F 

NORMAL 

M1-11 

ANALOG PHOTO 

KITCHEN 

3.7 % 

NORMAL 

*YES*

END OF REPORT 

Typical TrueAlarm Status Report Information Printout and/or Maintenance PC Screen

 

 TrueAlarm Status and Service Report Samples 

Summary of Contents for TrueAlarm

Page 1: ...with standard door Description TrueAlarm fire alarm control panels have the ability to provide location accuracy for monitoring and control When equipped with TrueAlarm analog sensing for smoke and he...

Page 2: ...recognizable audible notification signal audible WALKTEST operation 2 S4010 0001 14 6 2014 SUPV ACK SYSTEM SUPERVISORY ALARM ACK FIRE ALARM TROUBLE ACK SYSTEM TROUBLE ALARM SILENCE ALARM SILENCED SYS...

Page 3: ...ent levels of smoke obscuration in percent or for specific heat detection levels In order to evaluate whether the sensitivity should be revised the peak value is stored in memory and can be easily rea...

Page 4: ...ENCED SYSTEM RES ET AC POWER Local maintenance computer One connection type per 4010 selected by module choice max wiring distance is 300 ft 91 m 9600 baud RS 232 Connection Options refer to module s...

Page 5: ...ork Interface Modular Media Available for wired connections or fiber optic Require separate media modules May be both wired both fiber optic or one of each Optional Expansion Slot Modules Cont d Netwo...

Page 6: ...liances rated 2 A for Regulated 24 DC appliance power 4010 9823 240 VAC input Optional Features select as indicated 4010 9825 24 VDC Expansion Power Distribution Module provides two additional termina...

Page 7: ...each maximum up to 33 synchronized strobes maximum per NAC Current Ratings for Optional Modules and Remote LCD Annunciator Model Module Supervisory Current Alarm Current 4010 9810 DACT Common Event Re...

Page 8: ...1 2 368 mm WATERFLOW LEFT WING GROUND FAULT WATERFLOW RIGHT WING SUPV ACK SYSTEM SUPER VISORY ALARM ACK FIR E ALARM TROU BLE ACK SYSTEM TROUBLE ALARM SILENCE ALARM SILENC ED SYSTEM RESET AC POWER MENU...

Reviews: