II-A. Specifications
Capacity
1000KW at 240/480V
750KW at 208/416V
630KW at 380V
667KW at 240V, 1-ph
Power Factor
1.0
Full Load Amps
2404 at 240V
1202 at 480V
Load Type
Resistive
Cooling System
Airflow: 27,700 CFM
Motor: 10 HP
Voltages
240/480V, 3-ph.
Frequency
50, 60Hz standard
Connection
3-wire plus ground
Time Rating
Continuous
Ambient Air
Temperature
120°F
Fault Rating
Fuses are rated 200KAIC. The load bank has a 5KAIC short
circuit current rating.
Fan/Control Power
Provided by either internal transformer or 230/460V, 3-ph,
60Hz external power
- Description and Specification