4
Overview,
continued
Transponder
Interface Card
(TIC)
The transponder interface card housed in the Flexible User Interface remote display assembly is a varia-
tion of the TICs used in the FACP Miniplex, and follows the same wiring guidelines as the Miniplex
TIC. Refer to
574-848 4100ES Fire Alarm System - Installation Guide
for the TIC wiring guidelines.
Figure 3. Transponder Interface Card
The transponder interface card includes the following components:
LED 1
Reports communication loss with FACP Master when lit.
LED 2
Illuminates when a RUI ground fault search is active.
LED 4
Illuminates to indicate an RUI Style 7 primary trouble.
LED 5
Illuminates to indicate an RUI Style 7 secondary trouble.
P2
Uses harness 734-008 to connect to either P7 or P9 on the Flexible User Interface
controller card.
SW-1
Sets the RUI address for the card.
TB1
Connects to the master controller to power the remote display assembly.
TB3
Connects to FACP master through RUI wiring.
SW-1
LEDS 1-2
TB1
P2
TB3
SCREW
SCREW
LEDS 4-5
firealarmresources.com