Product 
Overview

The remote display assembly is a remote Flexible User Interface fitted in a specially sized box and 
connected to the master controller. These instructions cover the following units:.

4100-9401 Remote Display Assembly, Domestic, Red

4100-9402 Remote Display Assembly, Domestic, Beige

4100-9421 Remote Display Assembly, Canadian/French, Red

4100-9422 Remote Display Assembly, Canadian/French, Beige

4100-9441 Remote Display Assembly, International, Red

4100-9442 Remote Display Assembly, International, Beige

This product is compatible with both 4100U and 4100ES Fire Alarm Control Panels (FACP).

In This 
Document

This document covers the following subjects:

Reference

For instructions on programming the Flexible User Interface refer to the 

ES Panel Programmer’s 

Manual

 (574-849)

.

Cautions 

and 

Warnings

READ AND SAVE THESE INSTRUCTIONS

Follow the instructions in this installation manual. These instructions must be 

followed to avoid damage to this product and associated equipment. Product operation and reliability depend upon proper 
installation.

DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED

Upon unpacking your Simplex product, 

inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify 
an authorized Simplex product supplier.

ELECTRICAL HAZARD 

Disconnect electrical field power when making any internal adjustments or repairs. All repairs should 

be performed by a representative or authorized agent of your local Simplex product supplier.

STATIC HAZARD 

Static electricity can damage components. Handle as follows:

• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.

Description

Page

Overview 2

Installing the Remote Display Assembly 

5

Wiring the Remote Display Assembly 

8

Replacing the Remote Display Assembly 

10

Remote Display Assembly

 Installation Instructions

firealarmresources.com

Summary of Contents for 4100-9401

Page 1: ...refer to the ES Panel Programmer s Manual 574 849 Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual These instructions must be followed to avoi...

Page 2: ...s of surface mounting the enclosure to the wall and completing the RUI circuit connection The 4100 9401 Flexible User Interface remote display assembly contains the following Flexible User Interface p...

Page 3: ...ce keyboard using harness 166 226 P2 Connects to LCD with matching connector P3 Connects to LCD to provide power P5 Allows direct connection of PC to Flexible User Interface controller for down loadin...

Page 4: ...card includes the following components LED 1 Reports communication loss with FACP Master when lit LED 2 Illuminates when a RUI ground fault search is active LED 4 Illuminates to indicate an RUI Style...

Page 5: ...nnecting the TIC to the controller card can be unplugged by pressing the tab at the end of the wire The nut and washer holding the grounding cable must be unscrewed 5 To completely remove the panel pr...

Page 6: ...n the Flexible User Interface controller card to P2 on the TIC card 5 Replace the door on its hinge and reattach grounding strap Configure Switch Address Switches SW1 on the Flexible User Interface Co...

Page 7: ...28 ON ON OFF OFF OFF ON ON 88 OFF ON OFF OFF ON ON ON 29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF 30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON 31 ON ON OFF OFF OFF OFF OFF 91 OF...

Page 8: ...ser Interface box from the CPU motherboard to the TIC All wiring is between 18 AWG and 12 AWG All wiring is supervised and power limited Maximum distance from the RUI controller to any RUI device is 2...

Page 9: ...for the wiring diagram to connect one or more Flexible User Interface s to a FACP Power must be supplied to the Flexible User Interface by connecting TB1 of the TIC to an auxiliary power tap Figure 7...

Page 10: ...ower the Flexible User Interface door assembly 3 Detach harness 734 008 from P2 of the TIC 4 Detach the green grounding straps connected to the studs on the back of the panel assembly by removing the...

Page 11: ...swivel standoffs extending in from the side panels of the bay see Figure 8 3 Loop the ring at the end of each grounding strap to the corresponding studs extending from the back of the door assembly Fa...

Page 12: ...579 687 Rev D firealarmresources com...

Reviews: