The table below shows the maximum SLC wire lengths based on wire gauge and appliance  
current load. 

Table 5. 

 

Maximum SLC Wire Length to Farthest Appliance Based on Appliance Current Load

 

 

Distance in Feet (Meters) to the Last Appliance 

Alarm Current 

18 AWG (0.82 mm

2

14 AWG (2.08 mm

2

12 AWG (3.31 mm

2

0.11 A 

638 ft (194 m) 

1,614 ft (492 m) 

2,500 ft (762 m) 

0.25 A 

281 ft (86 m) 

710 ft (216 m) 

1,129 ft (344 m) 

0.60 A 

117 ft (36 m) 

296 ft (90 m) 

471 ft (144 m) 

0.80 A 

88 ft (27 m) 

222 ft (68 m) 

353 ft (108 m) 

1.0 A 

70 ft (21 m) 

178 ft (54 m) 

282 ft (86 m) 

1.3 A 

 

137 ft (42 m) 

217 ft (66 m) 

2.2 A 

 

81 ft (25 m) 

128 ft (39 m) 

3.0 A 

 

 

113 ft (34 m) 

Distances based on 2.0 V line drop 

 
If notification appliances on a given circuit are to be used for multiple notification zones for partial 
evacuation (selective signaling), then either a Class A loop circuit configuration and isolators must be 
used, with isolators bounding any wire segment that services a notification zone; or, the NAC riser 
must be installed in accordance with Survivability From Attack by Fire Requirements in NFPA 2002 
ED. Section 6.9.4, using one or more of the following: 

 

2 hour rated cable assembly 

 

a 2 hour rated shaft or enclosure 

 

2 hour rated stairwell in building fully sprinklered in accordance with NFPA 13 

 

The table below shows the maximum SLC wire length based on wire type and supervision 
communications. 

 

Table 6.  Maximum SLC Wire Length to Farthest Appliance Based on Supervision Communications 

 

 

Distance in Feet (Meters) to the Last Appliance 

Unit Load Range 

18 AWG (0.82 mm

2

14 AWG (2.08 mm

2

12 AWG (3.31 mm

2

1 to 3 

305 ft (93 m) 

772 ft (235 m) 

1,228 ft (374 m) 

4 to 7 

260 ft (79 m) 

657 ft (200 m) 

1,046 ft (319 m) 

8 to 13 

213 ft (65 m) 

538 ft (164 m) 

856 ft (261 m) 

14 to 20 

175 ft (53 m) 

444 ft (135 m) 

706 ft (215 m) 

21 to 30 

140 ft (43 m) 

355 ft (108 m) 

565 ft (172 m) 

31 to 40 

117 ft (36 m) 

296 ft (90 m) 

471 ft (144 m) 

41 to 50 

100 ft (30 m) 

254 ft (77 m) 

403 ft (123 m) 

51 to 60 

 

222 ft (68 m) 

353 ft (108 m) 

61 to 75 

 

187 ft (57 m) 

297 ft (91 m) 

 

Continued on next page 

 
 
 
 
 
 

Wiring Class A Circuits, 

Continued 

Class A Guidelines

 

firealarmresources.com

Summary of Contents for 4100-5120

Page 1: ...g a 4100 5121 refer to Enabling Low Battery Cutout Option in the ES Panel Programmer s Manual 574 849 for information on enabling this option 4100 5122 International version uses a 220 240 VAC power s...

Page 2: ...as been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interfer...

Page 3: ...A adapter board All SLCs are monitored for short and open circuits 24VDC AUX Power Provides up to 2 A of 24 VDC auxiliary power for use by the option cards Internal Battery Charger Charges up to 50 Ah...

Page 4: ...ts voltage is approximately 18 VDC Visual Synchronization A maximum of 46 MultiCandela addressable visuals may be synchronized per SLC All SLCs are synchronized across a TPS All TPSs are synchronized...

Page 5: ...ollowing temperature range 32 F 0 C and 120 F 49 C Humidity 90 F 32 C degrees at 93 Relative Humidity non condensing Note Add auxiliary and card power currents to standby current For each TrueAlert ap...

Page 6: ...against the back of the expansion bay a Connect to the PDI as shown below b Three PDI headers shown below must be pushed through the three open slots in the back of the TPS assembly c Align the two sc...

Page 7: ...a DIP switch SW1 which is a bank of eight switches From left to right see figure below these switches are designated as SW1 1 through SW1 8 The function of these switches is as follows SW1 1 This swit...

Page 8: ...FF ON OFF OFF ON ON ON 29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF 30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON 31 ON ON OFF OFF OFF OFF OFF 91 OFF ON OFF OFF ON OFF OFF 32 ON O...

Page 9: ...be kept to the right side of the cabinet in the non power limited area 2 Connect batteries to P5 on the PDM using Harness 734 015 3 Connect the PDM to the TPS using Harness 734 012 Connect the separa...

Page 10: ...928 Strobe 75 cd Ceiling Red 4904 9357 574 928 Strobe 75 cd Ceiling White 4904 9360 574 928 Strobe 110 cd Ceiling Red 4904 9358 574 928 Strobe 110 cd Ceiling White 4904 9361 574 928 A V 15 cd Red 4903...

Page 11: ...906 9229 579 808 A V Multi Candela 15 30 75 110 Ceiling Red 4906 9228 579 808 A V Multi Candela 15 30 75 110 Ceiling White 4906 9230 579 808 Speaker V Multi Candela 15 30 75 110 Red 4906 9251 579 808...

Page 12: ...ed in accordance with NFPA 70 All junctions must be insulated as soundly as the original jacket Continuity of shields where used must be maintained A system ground must be provided for Earth detection...

Page 13: ...y contacts power for these circuits must be provided by a power limited power supply that is UL listed for fire protective signaling use A UL listed EOL relay must be used to supervise the auxiliary p...

Page 14: ...iance nameplate voltage Total alarm current for all 3 channels plus all current draw from AUX power and option cards must not exceed 9 A Supervisory current is 0 20 mA per unit load Maximum length of...

Page 15: ...tion zone or the NAC riser must be installed in accordance with Survivability From Attack by Fire Requirements in NFPA 2002 ED Section 6 9 4 using one or more of the following 2 hour rated cable assem...

Page 16: ...16 firealarmresources com...

Page 17: ...reTag FD9 336 04 PORT 1 4905 9929 ISOLATOR PORT 2 PORT 1 4905 9929 ISOLATOR PORT 2 PORT 1 4905 9929 ISOLATOR PORT 2 TRUEALERT APPLIANCE TRUEALERT APPLIANCE Ferrite Bead Ferrite Bead Figure 7 Class A W...

Page 18: ...t add the capacitance of the drain wire to the conductor Voltage rating is 24 VDC 2 V peak to peak ripple maximum Maximum of six isolators between any appliance and SLC terminals Maximum 12 isolators...

Page 19: ...19 Continued on next page firealarmresources com...

Page 20: ...m For Class B wiring with no isolators T Tapping is allowed SLC wiring may be split multiple times to form SLC wiring branches Maximum wire distance of each of these SLC branches from the panel to any...

Page 21: ...wire branches join within 10 feet 3 m of the panel T tap wire stubs are allowed on the SLC wire branches but each tap must be less than 100 feet 30 m Equation 1 Maximum SLC Wire Branch Length Based o...

Page 22: ...liary Power to Power Limited Wiring The AUX Power output is defined by UL as Special Applications and is compatible with these devices 2088 Series relays and door handlers 2098 Series four wire smoke...

Page 23: ...onding LED CH1 through CH3 for that channel lit The Trouble Scroll Pushbutton allows an operator to scroll through multiple troubles A B C SYSTEM CODES SLC CHANNEL CODES D E Troubleshooting System Tro...

Page 24: ...579 336 Rev K firealarmresources com...

Reviews: