The TPS gets its power from the Power Distribution Module (PDM). The PDM takes power directly 
from a dedicated AC line and the two backup batteries, and distributes power to each bay in the 
cabinet. 
 

The Power Distribution Module (PDM) connects to every power supply in each back box.  Connect the 
734-012 Harness from the top connector on the PDM to the TPS. 
 
1.

 

Wire 120 VAC to the PDM, keeping AC wires at least one inch away from all other wires. 
AC power must be kept to the right side of the cabinet, in the non-power-limited area.  

2.

 

Connect batteries to P5 on the PDM using Harness 734-015. 

3.

 

Connect the PDM to the TPS using Harness 734-012. 

 

Connect the separate Red and Black wires (with Yellow female terminations) to Plugs P5 
(Black) and P4 (Red) on the TPS. 

 

Connect the White and Black wires, which terminate together in a White snap-on 
connector, to the bulkhead connector at the bottom of the TPS assembly, as shown below. 

 
 
 

Figure 4.  PDM/Battery Connections 

 
 

Power Distribution Module/Battery Connections 

Overview 

Power Distribution 
Module Connections 

220/230/240

PART NUMBERS 

APPEAR IN ITALICS.

 

firealarmresources.com

Summary of Contents for 4100-5120

Page 1: ...g a 4100 5121 refer to Enabling Low Battery Cutout Option in the ES Panel Programmer s Manual 574 849 for information on enabling this option 4100 5122 International version uses a 220 240 VAC power s...

Page 2: ...as been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interfer...

Page 3: ...A adapter board All SLCs are monitored for short and open circuits 24VDC AUX Power Provides up to 2 A of 24 VDC auxiliary power for use by the option cards Internal Battery Charger Charges up to 50 Ah...

Page 4: ...ts voltage is approximately 18 VDC Visual Synchronization A maximum of 46 MultiCandela addressable visuals may be synchronized per SLC All SLCs are synchronized across a TPS All TPSs are synchronized...

Page 5: ...ollowing temperature range 32 F 0 C and 120 F 49 C Humidity 90 F 32 C degrees at 93 Relative Humidity non condensing Note Add auxiliary and card power currents to standby current For each TrueAlert ap...

Page 6: ...against the back of the expansion bay a Connect to the PDI as shown below b Three PDI headers shown below must be pushed through the three open slots in the back of the TPS assembly c Align the two sc...

Page 7: ...a DIP switch SW1 which is a bank of eight switches From left to right see figure below these switches are designated as SW1 1 through SW1 8 The function of these switches is as follows SW1 1 This swit...

Page 8: ...FF ON OFF OFF ON ON ON 29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF 30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON 31 ON ON OFF OFF OFF OFF OFF 91 OFF ON OFF OFF ON OFF OFF 32 ON O...

Page 9: ...be kept to the right side of the cabinet in the non power limited area 2 Connect batteries to P5 on the PDM using Harness 734 015 3 Connect the PDM to the TPS using Harness 734 012 Connect the separa...

Page 10: ...928 Strobe 75 cd Ceiling Red 4904 9357 574 928 Strobe 75 cd Ceiling White 4904 9360 574 928 Strobe 110 cd Ceiling Red 4904 9358 574 928 Strobe 110 cd Ceiling White 4904 9361 574 928 A V 15 cd Red 4903...

Page 11: ...906 9229 579 808 A V Multi Candela 15 30 75 110 Ceiling Red 4906 9228 579 808 A V Multi Candela 15 30 75 110 Ceiling White 4906 9230 579 808 Speaker V Multi Candela 15 30 75 110 Red 4906 9251 579 808...

Page 12: ...ed in accordance with NFPA 70 All junctions must be insulated as soundly as the original jacket Continuity of shields where used must be maintained A system ground must be provided for Earth detection...

Page 13: ...y contacts power for these circuits must be provided by a power limited power supply that is UL listed for fire protective signaling use A UL listed EOL relay must be used to supervise the auxiliary p...

Page 14: ...iance nameplate voltage Total alarm current for all 3 channels plus all current draw from AUX power and option cards must not exceed 9 A Supervisory current is 0 20 mA per unit load Maximum length of...

Page 15: ...tion zone or the NAC riser must be installed in accordance with Survivability From Attack by Fire Requirements in NFPA 2002 ED Section 6 9 4 using one or more of the following 2 hour rated cable assem...

Page 16: ...16 firealarmresources com...

Page 17: ...reTag FD9 336 04 PORT 1 4905 9929 ISOLATOR PORT 2 PORT 1 4905 9929 ISOLATOR PORT 2 PORT 1 4905 9929 ISOLATOR PORT 2 TRUEALERT APPLIANCE TRUEALERT APPLIANCE Ferrite Bead Ferrite Bead Figure 7 Class A W...

Page 18: ...t add the capacitance of the drain wire to the conductor Voltage rating is 24 VDC 2 V peak to peak ripple maximum Maximum of six isolators between any appliance and SLC terminals Maximum 12 isolators...

Page 19: ...19 Continued on next page firealarmresources com...

Page 20: ...m For Class B wiring with no isolators T Tapping is allowed SLC wiring may be split multiple times to form SLC wiring branches Maximum wire distance of each of these SLC branches from the panel to any...

Page 21: ...wire branches join within 10 feet 3 m of the panel T tap wire stubs are allowed on the SLC wire branches but each tap must be less than 100 feet 30 m Equation 1 Maximum SLC Wire Branch Length Based o...

Page 22: ...liary Power to Power Limited Wiring The AUX Power output is defined by UL as Special Applications and is compatible with these devices 2088 Series relays and door handlers 2098 Series four wire smoke...

Page 23: ...onding LED CH1 through CH3 for that channel lit The Trouble Scroll Pushbutton allows an operator to scroll through multiple troubles A B C SYSTEM CODES SLC CHANNEL CODES D E Troubleshooting System Tro...

Page 24: ...579 336 Rev K firealarmresources com...