Standard Feature Details 

 

Five Class B IDCs

 are each capable of supporting up to 30 

Simplex current-limited smoke detectors or electronic heat 
detectors (see list on page 4) as well as manual stations and 
other compatible contact closure initiating devices. IDCs 
are capable of Class A operation with an optional adapter 
module and can be programmed as Style C (short or open 
initiates a trouble) for use with current limited devices only.  

Two, 2 A On-Board NACs

 provide conventional reverse 

polarity operation, selectable as Class A or Class B, with 
electronic control and overcurrent protection. Operation is 
selectable for synchronized strobe or SmartSync horn/strobe 
two-wire operation. Horn control can be selected at the panel 
for: Temporal pattern coding, Steady On, Slow March Time 
of 20 beats per minute (BPM), or Fast March Time of 
120 BPM. 

Note: 

When selected for SmartSync horn/strobe 

control, March Time produces 60 BPM. 

The 24 VDC Auxiliary output

 provides up to 500 mA 

for system use. (Auxiliary output current is counted for 
total power supply capacity.) 

Standard Auxiliary Relay Outputs.

 

Two relay outputs 

are available, selectable as normally open or normally 
closed, rated 2 A @ 30 VDC per below: 

Aux Relay 1 

is normally assigned to General Alarm 

operation but is programmable (see page 7) 

Aux Relay 2 (Trouble)

 is energized when Normal and is 

de-energized with a Trouble condition. 

On-Board Dual Line DACT.

 

Operation can be selected 

for Contact ID, SIA, 3/1, 4/2, and BFSK formats.

 

Reporting includes Alarm, Supervisory, Trouble, and AC 
Failure. Operation includes automatic 24 hour test and 
programmable power fail report delay. 

 

 

Standard Feature Details (Continued) 

 

Power Supply and Battery Charger

.

 DC power output 

is 3 A @ 24 VDC for panel use. The temperature 
compensated battery charger (sealed lead-acid batteries 
only) is rated for up to 25 Ah batteries per UL 864 and up 
to 12.7 Ah per ULC-S527. (Up to 12.7 Ah batteries fit in 
the cabinet, larger batteries require an external cabinet.) 
Panel electronics can measure and display voltage and 
current for the power supply, batteries and the battery 
charger (standard and expansion power supply). Depleted 
battery trouble is monitored and annunciated and depleted 
battery cutout can be selected. Active battery status 
monitor supervises charger operation. 

Optional Feature Details 

 

Expansion Power Supply.

 Provides 3 A total @ 

24 VDC, two additional 2 A NACs, and an additional 
auxiliary power output of 500 mA. Output operation is the 
same as on the standard power supply. 

Expansion IDC Module.

 Provides 5 additional Class B 

IDCs with operation the same as the standard IDCs. 

Expansion Relay Module.

 Provides 10 programmable 

relays, jumper selectable as N.O. or N.C. Contacts are 
rated 2 A @ 30 VDC. Typical application is to track 
status of each IDC. See page 7 for relay program options. 

Class A Adapter Module.

 Converts 5 IDCs from 

Class B to Class A operation. Two modules can be 
mounted for use with the Expansion IDC Module. 

City Circuit Modules

.

 These modules are available with 

or without on-board disconnect switches, depending on 
local requirements (either type can be disconnected 
through the front panel under password control). 
Connections are for Remote Station (reverse polarity) or 
Municipal Master (local energy). Reporting includes 
Alarm, Supervisory, and Trouble.

 

S4006-0001-8  8/2012

Control Panel

 

Model 

Color 

Description 

Listings 

Standard Feature Summary 

4006-9102 Beige 

Standard fire alarm control panel 

MEA 

UL, FM, 

& CSFM 

5 Class B IDCs, 2 Class B/Class A 

NACs, 3 A power supply with battery 

charger; on-board DACT; 120/240 VAC, 
50/60 Hz (autoselect) 

4006-9101 Red 
4006-9122 Beige  Fire alarm control panel with 24 LED 

Annunciator on front door  

ULC 

4006-9121 Red 

Option Modules 

Model 

Description 

4006-9801  Expansion Power Supply; 3 A, with 2 NACs, 120/240 VAC, 50/60 Hz 

Select up to one of each as required 

4006-9802  Expansion IDC Module; 5 Class B IDCs 
4006-9803  Expansion Relay Module; 10 relays selectable as either N.O. or N. C. 
4006-9804  Class A Adapter Module; converts 5 IDCs from Class B to Class A 

Select up to two maximum 

4006-9805  City Circuit Module with disconnect switch 

Select one if required 

4006-9806  City Circuit Module without disconnect switch 

Accessories 

Model 

Description 

2975-9811  Beige semi-flush trim kit; 1-7/16” (37 mm) wide; includes four corners and trim pieces for top, bottom, and sides 
2975-9812  Red semi-flush trim kit; 1-7/16” (37 mm) wide; includes four corners and trim pieces for top, bottom, and sides 

4009-9801  Beige External Battery Cabinet for up to 25 Ah batteries; mounts close-nippled to control panel cabinet; dimensions = 

16-1/4” W x 13-1/2” H x 5-3/4” D (413 mm x 343 mm x 146 mm) [depth increased for 25 Ah effective 7/2005] 

Batteries, 12 Volt 

(select one battery model per system standby requirements; order quantity of two) 

Model 

Size 

Model 

Size 

Location 

Model 

Size 

Location 

2081-9272 

6.2 Ah 

2081-9288  12.7 Ah 

For cabinet mount

2081-9275 18 

Ah Requires 4009-9801 External Battery 

Cabinet (UL listed only)  

2081-9274 10 

Ah 

 

 2081-9827 

25 

Ah 

 Product Selection 

Summary of Contents for 4006 Series

Page 1: ... cabinet UL listed to Standard 864 Available option modules Door mounted 24 LED annunciator standard on ULC models 3 A Expansion Power Supply with two on board 2 A NACs that operate the same as standard NACs ALARM ACK SUPV ACK TROUBLE ACK ALARM SILENCE SYSTEM RESET FIRE ALARM SYSTEM SUPERVISORY SYSTEM TROUBLE ALARM SILENCED AC POWER 4006 9102 Beige Standard Control Panel ALARM ACK SUPV ACK TROUBLE...

Page 2: ...tional auxiliary power output of 500 mA Output operation is the same as on the standard power supply Expansion IDC Module Provides 5 additional Class B IDCs with operation the same as the standard IDCs Expansion Relay Module Provides 10 programmable relays jumper selectable as N O or N C Contacts are rated 2 A 30 VDC Typical application is to track status of each IDC See page 7 for relay program o...

Page 3: ...arm list SUPV ACK acknowledges system supervisory conditions logs the acknowledge silences the operator panel and all annunciator tone alerts and steps through the active Supervisory list TROUBLE ACK acknowledges system troubles logs the acknowledge silences the operator panel and all annunciator tone alerts and steps through the active Trouble list FIVE NAVIGATION KEYS MENU selects the on screen ...

Page 4: ...t 500 mA maximum 24 VDC Standard Auxiliary Relay Outputs Relay 1 Programmable operation Contacts rated 2 A 30 VDC 0 35 power factor jumper selectable as N O or N C Relay 2 Trouble operation Wiring Connections for Above Circuits and AC Input Terminals rated for 18 AWG to 12 AWG 0 82 mm2 to 3 31 mm2 Option Module Ratings Class A IDC Adapter Module Five circuits per module rated same as circuits Ten ...

Page 5: ...n Alarm 4006 9121 4006 9122 Control panel with 24 LED Annunciator 148 mA 210 mA 60 mA per IDC in Alarm 4006 9801 Expansion Power Supply 50 mA 60 mA 4006 9802 Expansion IDC Module 50 mA 50 mA 60 mA per IDC in Alarm 4006 9803 Expansion Relay Module 0 mA 10 mA per energized relay 0 mA 10 mA per energized relay 4006 9804 Five Circuit IDC Class A Adapter 0 mA normal 10 mA per IDC in trouble 0 mA normal...

Page 6: ...TROUBLE VSMOKE Verified fire alarm the abnormal current limited state causes the alarm verification cycle to start a short is an immediate alarm Normal Current Limited Short Open NORMAL VERIFY FIRE TROUBLE STYLEC Style C fire monitor Normal Current Limited Short Open NORMAL FIRE TROUBLE TROUBLE LATSUPV Latching supervisory monitor supervisory latches until system is reset Normal Current Limited Sh...

Page 7: ...West Front Center rear 5th Flr_1 Flr_2 Flr_3 Flr_4 Flr_5 RM_ Basement Floor Garage Hallway HVAC_Room Kitchen Lobby Office Patient upper lower main first 2nd 3rd 4th Boiler_RM Classroom Closet_ Corridor Elect_RM Elevator Entrance Restroom Room Stairway Storeroom Wing Zone History logs Three separate logs Alarm 100 entries Supervisory 100 entries and Trouble 300 entries logs can be queried separatel...

Page 8: ...Main board Knockouts are located on top and sides Expansion Power Supply extends under IDC Expansion Module space Display Assembly Box depth 4 3 4 121 mm 16 406 mm Door thickness 5 8 16 mm NOTE For semi flush mounting cabinet must extend 1 1 2 38 mm minimum from wall surface Tyco Fire Protection Products Westminster MA 01441 0001 USA S4006 0001 8 8 2012 www simplexgrinnell com 2012 Tyco Fire Prote...

Reviews: