S4006-0001-8  8/2012

Power Ratings 

AC Input Ratings

 

Input Voltage

 

120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto-select

 

Input Current, Standard

 

2 A maximum @ 120 VAC input; 1.5 A maximum @ 240 VAC input

 

Input Current with  

Expansion Power Supply

 

4 A maximum @ 120 VAC input; 3 A maximum @ 240 VAC input

 

Power Supply Output Rating

 

3 A maximum @ 24 VDC in alarm (see NAC details on page 6)

 

Battery Charger

 

Temperature compensated charger is rated for up to 25 Ah per UL 864; up to 

12.7 Ah per ULC-S527

 

Standby Current

 

130 mA; with 5 IDCs fully loaded, tone-alert silenced, trouble LED on 

 

Standard Circuit Ratings (NOTE: Total DC current = 3 A maximum) 

Notification Appliance Circuits (NACs) 

NOTE:

 See details on page 6

 

2 A maximum @ 24 VDC, per circuit; available as Class A or Class B;  

Class B end-of-line resistor = 10 k

, 1/2 W; Model 4081-9008 (P/N 733-894)

 

Initiating Device  

Circuits (IDCs)

 

Supervisory Current

 

3 mA maximum

 

Alarm Current

 

60 mA maximum

 

Capacity

 

Each IDC supports up to 30 detectors (smoke or electronic heat) and manual 

stations as required; wiring distance is limited to 50 

 maximum

 

End-of-Line Resistor

 

3.3 k

, 1/2 W; Model 4081-9002 (P/N 733-893) for Class B IDCs

 

Annunciator 

Communications 

Quantity Supported  Up to four annunciator modules per panel (see page 5 for details) 

Wiring Type  Twisted pair, or twisted, shielded pair; 18 AWG (0.82 mm

2

Bus-Style Wiring  Up to 4000 ft (1219 m); 0.58 µF (580 nF) maximum capacitance; 35 

 max. 

“T-Tap” Wiring  Up to 10,000 ft (3048 m) total wiring; up to 2500 ft (762 m) to farthest device 

Line Matching Resistor 

Bus-style, connect one at panel and one at end of line  100 

, 1/2 W; 4081-9011;  

(part number 733-974) 

T-Tap, connect one at panel and one at farthest device 

Suppression  Use 2081-9044 Overvoltage Protectors where wiring leaves and enters a building 

(refer to data sheet S2081-0016) 

Auxiliary Power Output

 

500 mA maximum @ 24 VDC

 

Standard Auxiliary Relay Outputs  

 

Relay 1

 

Programmable operation

 

Contacts rated 2 A @ 30 VDC, 0.35 power factor; 

jumper selectable as N.O. or N.C.

 

Relay 2

 

Trouble operation

 

Wiring Connections for Above Circuits and  

AC Input

 

Terminals rated for 18 AWG to 12 AWG (0.82 mm

2

  to 3.31 mm

2

 )

 

Option Module Ratings 

Class A IDC Adapter Module

 

Five circuits per module, rated same as circuits

 

Ten Relay Auxiliary 

Module 4006-9803

 

Contact Ratings

 

2 A @ 30 VDC, 0.35 power factor; jumper selectable as N.O. or N.C.

 

Wiring

 

Terminals rated for 18 AWG to 12 AWG (0.82 mm

2

 to 3.31 mm

2

)

 

Environmental Ratings  

Operating Temperature Range

 

32° to 120°F (0° to 49° C)

 

Operating Humidity Range

 

Up to 93% RH, non-condensing @ 100.4° F (38° C) maximum

 

Compatible Simplex Detectors

 

Model 

Type 

Description 

Data Sheet 

4098-9601

 

Photoelectric smoke detectors 
for 2-wire and 4-wire bases

 

Standard detector (2.8% nominal)

 

S4098-0015

 

4098-9605

 

Reduced sensitivity detector (3.5% nominal)

 

4098-9602

 

Combination smoke and heat detector

 

S4098-0017

 

4098 Series

 

Duct detector housings

 

2-wire and 4-wire models

 

S4098-0029

 

4098 Series

 

Ionization Smoke Detectors

 

2-wire and 4-wire models

 

S4098-0018

 

4098-9612

 

Electronic heat detectors for 
2-wire and 4-wire bases 

 

135° F (57°C)

 

Fixed temperature heat detector

 

S4098-0014

 

4098-9614

 

200° F (93°C)

 

4098-9613

 

135° F (57°C)

 

Fixed temperature heat detector with 
rate-of-rise detection

 

4098-9615

 

200° F (93°C)

 

Compatible System Expansion Panels 

Model 

Type 

Description 

Data Sheet 

4003 Series

 

Voice Control Panel

 

Provides a remote voice control panel with on-board NACs, internal 
microphone, and remote microphone input

 

S4003-0002 

4009 Series 

 

Remote NAC Extender

 

Provides remote NACs; includes power supply and battery charger; 

4 extenders

 max/NAC; 

4006 uses NAC output to provide control 

 

S4009-0002 

Note:

 Contact your local Simplex Product Supplier for additional compatible peripherals. 

 Specifications 

(Refer to Installation Instructions 579-704 for additional information)

 

 

 Reference Information, Compatible Simplex Peripherals 

 

Summary of Contents for 4006 Series

Page 1: ... cabinet UL listed to Standard 864 Available option modules Door mounted 24 LED annunciator standard on ULC models 3 A Expansion Power Supply with two on board 2 A NACs that operate the same as standard NACs ALARM ACK SUPV ACK TROUBLE ACK ALARM SILENCE SYSTEM RESET FIRE ALARM SYSTEM SUPERVISORY SYSTEM TROUBLE ALARM SILENCED AC POWER 4006 9102 Beige Standard Control Panel ALARM ACK SUPV ACK TROUBLE...

Page 2: ...tional auxiliary power output of 500 mA Output operation is the same as on the standard power supply Expansion IDC Module Provides 5 additional Class B IDCs with operation the same as the standard IDCs Expansion Relay Module Provides 10 programmable relays jumper selectable as N O or N C Contacts are rated 2 A 30 VDC Typical application is to track status of each IDC See page 7 for relay program o...

Page 3: ...arm list SUPV ACK acknowledges system supervisory conditions logs the acknowledge silences the operator panel and all annunciator tone alerts and steps through the active Supervisory list TROUBLE ACK acknowledges system troubles logs the acknowledge silences the operator panel and all annunciator tone alerts and steps through the active Trouble list FIVE NAVIGATION KEYS MENU selects the on screen ...

Page 4: ...t 500 mA maximum 24 VDC Standard Auxiliary Relay Outputs Relay 1 Programmable operation Contacts rated 2 A 30 VDC 0 35 power factor jumper selectable as N O or N C Relay 2 Trouble operation Wiring Connections for Above Circuits and AC Input Terminals rated for 18 AWG to 12 AWG 0 82 mm2 to 3 31 mm2 Option Module Ratings Class A IDC Adapter Module Five circuits per module rated same as circuits Ten ...

Page 5: ...n Alarm 4006 9121 4006 9122 Control panel with 24 LED Annunciator 148 mA 210 mA 60 mA per IDC in Alarm 4006 9801 Expansion Power Supply 50 mA 60 mA 4006 9802 Expansion IDC Module 50 mA 50 mA 60 mA per IDC in Alarm 4006 9803 Expansion Relay Module 0 mA 10 mA per energized relay 0 mA 10 mA per energized relay 4006 9804 Five Circuit IDC Class A Adapter 0 mA normal 10 mA per IDC in trouble 0 mA normal...

Page 6: ...TROUBLE VSMOKE Verified fire alarm the abnormal current limited state causes the alarm verification cycle to start a short is an immediate alarm Normal Current Limited Short Open NORMAL VERIFY FIRE TROUBLE STYLEC Style C fire monitor Normal Current Limited Short Open NORMAL FIRE TROUBLE TROUBLE LATSUPV Latching supervisory monitor supervisory latches until system is reset Normal Current Limited Sh...

Page 7: ...West Front Center rear 5th Flr_1 Flr_2 Flr_3 Flr_4 Flr_5 RM_ Basement Floor Garage Hallway HVAC_Room Kitchen Lobby Office Patient upper lower main first 2nd 3rd 4th Boiler_RM Classroom Closet_ Corridor Elect_RM Elevator Entrance Restroom Room Stairway Storeroom Wing Zone History logs Three separate logs Alarm 100 entries Supervisory 100 entries and Trouble 300 entries logs can be queried separatel...

Page 8: ...Main board Knockouts are located on top and sides Expansion Power Supply extends under IDC Expansion Module space Display Assembly Box depth 4 3 4 121 mm 16 406 mm Door thickness 5 8 16 mm NOTE For semi flush mounting cabinet must extend 1 1 2 38 mm minimum from wall surface Tyco Fire Protection Products Westminster MA 01441 0001 USA S4006 0001 8 8 2012 www simplexgrinnell com 2012 Tyco Fire Prote...