User manual - METER SWE-N55L
“SEt2”
- second threshold of the relay (range -999 ÷ 9999). Negative values can be input
by selecting a “-” sign on first digit ( to change value use
[^]
and
[v]
buttons). This
threshold is accessible when “
modE”
parameter is set to
“in”
or
“out”
value.
Threshold is the medium value of relay hysteresis.
“HYSt”
- hysteresis of relay (range 0 ÷ 999). Full hysteresis of the relay is equal to 2x
“HYSt”
parameter. The relay state can change when an input signal is out of
threshold-hysteresis
to
thhysteresis
zone.
Presented parameters should be set to ensure that
“SEtP” + ”HYSt”,
“SEt2” + ”HYSt”, “SEtP” - ”HYSt”
or
“SEt2” - ”HYSt”
do not exceeds the
measure range. Additionally, in two threshold mode (
“modE”
=
“in”
or
“out”
),
the hysteresis for both thresholds must not cover each other (in other case relay
can't change its state).
“modE”
- relay operation mode:
“noAc”
- the relay is not active (doesn’t change state)
“on”
- one threshold mode, the relay turns
ON
when input signal exceeds from
the bottom
SEtP+HYSt
value
,
and turns
OFF
when exceeds from the top
SEtP-HYSt
,
“oFF”
- one threshold mode, the relay turns
ON
when input signal exceeds from
the top
SEtP-HYSt
value
,
and turns
OFF
when exceeds from the bottom
SEtP+HYSt
,
“in”
- two threshold mode, the relay turns
ON
when the input signal exceeds
from the bottom
“
lower threshold
+
HYSt”
or from the top
“
bigger threshold -
HYSt”
, and turns
OFF
when exceeds from the top
“
lower threshold
- HYSt”
or
from
the
bottom
“
bigger thr
HYSt”
. The
bigger threshold
means bigger one of
“SEtP”
and
“SEt2”
thresholds, the
lower threshold
means lower one of
“SEtP”
and
“SEt2”
thresholds.
“out”
- two threshold mode, the relay turns
ON
when the input signal exceeds
from the top
“
lower threshold
- HYSt”
or from the bottom
“
bigger thr
HYSt”
, and turns
OFF
when exceeds from the
bottom
“
lower threshold
+ HYSt”
or from the top
“
bigger threshold -
HYSt”
. The
bigger threshold
means bigger one of
“SEtP”
and
“SEt2”
thresholds, the
lower threshold
means lower one of
“SEtP”
and
“SEt2”
thresholds.
•
LED lights when “ON” part of the relay is closed
, independently of relay’s
mode.
•
When power supply fail, unit sets relay state accordingly to
“AL”
parameter.