User manual - METER SRT-73
Figure 6.1. Process of peaks detection
6.3.
CONTROL OF THE RELAY OUTPUTS
The control of the object (measured signal) is realized via relay outputs. Front panel
LEDs named
R
indicates the state of particular relay output.
If device is not equipped with one or more relay outputs, menus refer to this relays
are available, but apply to LED indicators only. In such case LEDs indicates
exceeding of particular thresholds.
Modes of the control can be changed depend on the values of parameters
SEtP
,
SEt2 ,
HYSt
,
modE
,
t on
,
toFF
,
unit
and
AL .
Depend on
modE
parameter, relays
can be not used or controlled over one or two thresholds values.
If one threshold is used (Figure 6.2) the relay can be turned on (
modE
=
on
) or off
(
modE
=
oFF
) when the input signal value is contained in
zone A.
If two thresholds are
used (Figure 6.3) the relay will be turned on when value of input signal is contained in
zone A
(
modE
=
in
) or
zone B
(
modE
=
out
) and turned off if the signal is contained in the
second one.
Figure 6.2. One threshold control of the relay/LED outputs
15
timE
measure
time
timE
PEA
PEA
real measurement result
display value
zone A
zone B
measure
SEtP parameter
HYSt parameter
state of
relay/LED
i