User manual - METER SRT-73
Register Write
Range
Register description
20h
2
Yes
0 ÷ 199
Device address
21h
No
20B7h
20B3h
Device identification code (ID)
Device identification code (IP65 version)
22h
3
Yes
0 ÷ 7
bAud
parameter in
rS
menu (baud rate);
0
- 1200 baud;
1
- 2400 baud;
2
- 4800 baud;
3
- 9600 baud;
4
- 19200 baud;
5
- 38400 baud;
6
- 57600 baud;
7
- 115200 baud
23h
4
Yes
0 ÷ 1
mbAc
parameter in
rS
menu (permission to write registers via
RS-485 interface);
0
- write denied ;
1
- write allowed
24h
Yes
see descr.
Parameters of
SECU
menu (binary format (0 -
oFF
, 1 -
on
):
bit 0
-
A r1
parameter;
bit 1
-
A r2
parameter
bit 2
-
A r3
parameter;
bit 3
-
A r4
parameter
25h
Yes
0 ÷ 5
rESP
parameter in
rS
menu (additional response delay);
0
- no additional delay;
1
-
10c
option;
2
-
20c
option;
3
-
50c
option;
4
-
100c
option;
5
-
200c
option;
27h
Yes
0 ÷ 99
mbtO
parameter in
rS
menu (maximum delay between
received frames);
0
- no delay checking;
1
÷
99
- maximum delay expressed in seconds
2Dh
Yes
1 ÷ 8
bri
parameter (display brightness);
1
- the lowest brightness;
8
- the highest brightness
2Eh
Yes
0 ÷ 1
SCoL
parameter in
CoL
menu (main colour of display);
0
- green;
1
- red
2Fh
Yes
0 ÷ 1
Edit
parameter (numerical parameters edit mode);
0
-
dig
mode;
1
-
SLid
mode
30h
Yes
-999 ÷ 9999
SEtP
parameter in
rEL1
menu, no decimal point included
31h
Yes
-999 ÷ 999
HySt
parameter in
rEL1
menu, no decimal point included
32h
Yes
0 ÷ 5
modE
parameter in
rEL1
menu:
0
-
noAC
mode;
1
-
on
mode;
2
-
oFF
mode;
3
-
in
mode;
4
-
out
mode;
5
-
modb
mode
33h
Yes
0 ÷ 999
t on
parameter in
rEL1
menu, expressed in tenth of seconds or
tenth of minutes depend on
unit
parameter - register no. 35h)
34h
Yes
0 ÷ 999
toFF
parameter in
rEL1
menu, expressed in tenth of seconds
or tenth of minutes depend on
unit
parameter - register no. 35h)
35h
Yes
0 ÷ 1
unit
parameter in
rEL1
menu:
0
- seconds;
1
- minutes
36h
Yes
0 ÷ 2
AL
parameter in
rEL1
menu:
0
- no changes;
1
- on;
2
- off
37h
Yes
-999 ÷ 9999
SEt2
parameter in
rEL1
menu, no decimal point included
38h
Yes
-999 ÷ 9999
SEtP
parameter in
rEL2
menu, no decimal point included
39h
Yes
-999 ÷ 999
HySt
parameter in
rEL2
menu, no decimal point included
3Ah
Yes
0 ÷ 5
modE
parameter in
rEL2
menu:
0
-
noAC
mode;
1
-
on
mode;
2
-
oFF
mode;
3
-
in
mode;
4
-
out
mode;
5
-
modb
mode
31