Figure 4.6. Terminals description (relay outputs, device with current output)
Figure 4.7. Terminals description (OC-type outputs)
Contacts of relay outputs are not equipped with spark suppressors. While use
the relay outputs for switching of inductive loads (coils, contactors, power
relays, electromagnets, motors etc.) it is required to use additional
suppression circuit (typically capacitor 47nF/ min. 250VAC in series with
100R/5W resistor), connected in parallel to relay terminals or (better) directly
on the load. In consequence of using the suppression circuit, the level of
generated electromagnetic disturbances is lower, and the life of relay contacts
rises.
11
!
1
2
11 12 13 14
Power
supply
(depending on version)
GND
DATA+
DATA-
RS - 485
+
Uo
-
+24V
+5%, -10%
I
max = 100mA
3 4 5 6
7 8
R1
R2
(optional)
(optional)
9 10
optional ACTIVE
current output
-
+
n.c. n.c.
15 16 17 18 19
GND
GND
GND
GND
0-150mV
+
1
2
11 12 13 14
Power
supply
(depending on version)
GND
DATA+
DATA-
RS - 485
+
Uo
-
+24V
+5%, -10%
I
max = 100mA
3 4 5 6
7 8 9 10
OC1 ÷ OC4:
U
max = 30V DC,
I
max = 30mA,
P
max = 100mW
+ - - +
OC3
(optional)
OC4
(optional)
- +
OC2
(optional)
- +
OC1
(optional)
15 16 17 18 19
GND
GND
GND
GND
0-150mV
+