background image

User manual - METER SRP-147-XC 

“out”

 

- two threshold mode, relay is turned 

ON

 when the input value is bigger

than    “

bigger threshold

  +  

HYSt”  

and lower  than  “

lower

 

threshold

  –

HYSt”

, and  turned on when the input signal is contained in the second

zone. The  

bigger threshold

  means bigger one of  

“SEtP”  

and  

“SEt2”

thresholds,   the  

lower threshold

”   means   lower   one   of  

“SEtP”  

and

“SEt2” 

thresholds.

“modb”

  - the relay is controlled via RS-485 interface, independently on the input 

signal. 

LEDs light when relays are closed

, independently of relays' mode.

When   power   supply  fail,   unit   do  not   store  relays  state   selected   by RS-485

interface.

“t on”

- turn on delay time, the relay is turned on with delay equal 

“t on” 

if

 

the input value

exceeds   appropriate  

border value

  (defined   with  

threshold  

and

 

hysteresis

),   at

least  

“t on”

 time. 

“t on”

 range  0 ÷ 99.9, defined with 0.1 sec. resolution. Unit of

this parameter is set by 

“unit” 

parameter.

“toFF”

 

- turn off delay time, the relay is turned off with delay equal 

“toFF” 

if

 

the input value

exceeds   appropriate  

border value

  (defined   with  

threshold  

and

 

hysteresis

),   at

least 

“toFF”

 time. 

“toFF”

 range  0 ÷ 99.9, defined with 0.1 sec. resolution. Unit of

this parameter is set by 

“unit” 

parameter.

If time when the input signal exceeds some border value is shorter than 

“t on”

 or

“toFF” 

time, the relay do not change his state

 

(see paragraph: 

CONTROL OF 

THE RELAY OUTPUTS

).

“unit”

- unit of time for 

“t on”

 i 

“toFF”

 parameters. Can be set on one of two values:

“min”

 

- minutes,

“SEC”

 

- seconds.

“AL”

- this parameter defines the relay reaction when some critical situations occurs:

“noCH”

- relay do not change his state,

“on”

 

- relay will be turned on,

“oFF”

- relay will be turned off.

If parameter 

“modE”

 is set  to 

“on”

 , 

“oFF”

“in”

 or

 “Out”

 the “critical situation”

means that allowable measurement range is exceeded.
If   parameter  

“modE”

  is   set   to  

“modb”

,   the   “critical   situation”   means

communication delay (when no data is received) longer than  

“mbtO”  

parameter

(see description: 

“rS” menu

).

If option “

noCH

” is selected for 

“AL”

 parameter, behaviour of the relay may 

depend on 

FiLt

” parameter 

in some cases

. If “

FiLt

” is set to big value and the 

input signal drops, result value of the measure will change slow, causes of 

turning on or off relay due to thresholds values. The critical situation is slowly 

detected, so it is impossible to predict the relay state in that situations.

24

i

i

i

Summary of Contents for SRP-147-XC

Page 1: ... XC Firmware v 5 18 or higher Input type 0 60 75 100 150 mV Large 4 x 38 mm display Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes without prior notice 2018 12 20 SRP 147 XC_INSSXEN_v 2 08 001 ...

Page 2: ...change mode 21 7 2 3 Switch parameters LIST type 22 7 3 MENU DESCRIPTION 22 7 3 1 rEL1 menu 23 7 3 2 bEEP menu 25 7 3 3 inPt menu 25 7 3 4 OutP menu 27 7 3 5 bri parameter 29 7 3 6 HOLd menu 29 7 3 7 SECu menu 29 7 3 8 rS menu 30 7 3 9 Edit parameter 31 7 3 10 dEFS parameter 31 7 3 11 SErv menu 31 7 4 MENU STRUCTURE 32 8 THE ALARM LED 34 9 DISPLAYED VALUES CALCULATION 34 9 1 ADDITIONAL CALCULATION...

Page 3: ...afety and EMC regulations GND input of device should be connected to PE wire The unit must be properly set up according to the application Incorrect configuration can cause defective operation which can lead to unit damage or an accident If in the case of a unit malfunction there is a risk of a serious threat to the safety of people or property additional independent systems and solutions to preve...

Page 4: ...kinds linear square square root and user defined max 20 points length Result is showed on 4 digit LED display Displayed values range can be selected by user from 999 to 9999 plus decimal point The device can be equipped with two or four relay or OC type outputs Optionally SRP 147 XC with two relays outputs can be equipped with active current output Device SRP 147 XC is equipped with RS 485 Modbus ...

Page 5: ...ng available Terminals protection IP 20 Housing type Housing material Housing dimensions Mounting hole Assembly depth Panel thickness panel NORYL GFN2S E1 144 x 72 x 100 mm 138 5 x 67 mm 102 mm max 5 mm Operating temperature depending on version 0 C to 50 C or 20 C to 50 C Storage temperature depending on version 10 C to 70 C or 20 C to 70 C Humidity Altitude 5 to 90 no condensation up to 2000 met...

Page 6: ...k for transportation damage Any transportation damage must be immediately reported to the carrier Also write down the unit serial number located on the housing and report the damage to the manufacturer Attached with the unit please find user s manual warranty assembly brackets 2 pieces 4 2 ASSEMBLY The unit is designed for mounting inside housings control panel switchboard insuring appropriate pro...

Page 7: ...User manual METER SRP 147 XC a b Figure 4 1 Mounting hole dimensions a recommended b allowable 7 138 5 mm max 5 mm 67 mm 137 mm 13 mm 8 mm 8 mm 13 mm 1 mm max 5 mm 67 mm 1 mm ...

Page 8: ...number of units 4 3 CONNECTION METHOD Caution Installation should be conducted by qualified personnel During installation all available safety requirements should be considered The fitter is responsible for executing the installation according to this manual local safety and EMC regulations 8 163 mm 91 mm 82 mm 5 mm 12 mm 10 mm 8 5 mm 16 mm ...

Page 9: ...g as bridges because this can cause damage to the equipment or electric shock If the unit is equipped with housing covers and sealing to protecting against water intrusion pay special attention to their correct tightening or clamping In the case of any doubt consider using additional preventive measures covers roofing seals etc Carelessly executed assembly can increase the risk of electric shock A...

Page 10: ...not be run with cables with interference e g circuits controlling relays or contactors Connections of power supply voltage and measurement signals are executed using the screw connections on the back of the unit s housing Figure 4 4 Method of cable insulation replacing and cable terminals All connections must be made while power supply is disconnected Figure 4 5 Terminals description relay outputs...

Page 11: ... in parallel to relay terminals or better directly on the load In consequence of using the suppression circuit the level of generated electromagnetic disturbances is lower and the life of relay contacts rises 11 1 2 11 12 13 14 Power supply depending on version GND DATA DATA RS 485 Uo 24V 5 10 Imax 100mA 3 4 5 6 7 8 R1 R2 optional optional 9 10 optional ACTIVE current output n c n c 15 16 17 18 19...

Page 12: ...ppression circuit connection a to relay terminals b to the inductive load Depending on version 85 230 260V AC DC or 19 24 50V DC 16 24 35V AC Figure 4 9 Connection of power supply and relays 12 N 3 4 3 4 L L N R4 FUSE 1 2 L N L N FUSE R1 R2 R3 3 4 5 6 7 8 9 10 ...

Page 13: ...ponents and shorten the fault free time of the unit s operation In cases where the unit gets dirty do not clean with solvents For cleaning use warm water with small amount of detergent or in the case of more significant contamination ethyl or isopropyl alcohol Using any other agents can cause permanent damage to the housing Product marked with this symbol should not be placed in municipal waste Pl...

Page 14: ...nt menu Modification of the parameter value Change of the display mode 6 PRINCIPLE OF OPERATION After turning the power supply on device ID and software version are showed on the display next the controller goes to the measurement mode 6 1 MEASUREMENT MODE In the measure mode the measurement results converted over selected characteristic are displayed on the LED display The measurement range equal...

Page 15: ...VICE PROGRAMMING Use the local keyboard or the remote controller to do it Note all parameters can be remote changed via RS 485 interface Configuration of the device via menu or RS 485 interface do not stops measures 6 2 DETECTION OF THE PEAK VALUES The SRP 147 XC controller is equipped with peaks detection function It can detect a peaks of the input signal and display their values Presets connecte...

Page 16: ...esholds Modes of the control can be changed depend on the values of parameters SEtP SEt2 HYSt modE t on toFF unit and AL Depend on modE parameter relays can be not used or controlled over one or two thresholds values If one threshold is used Figure 6 3 the relay can be turned on modE on or off modE oFF when the input signal value is contained in zone A If two thresholds are used Figure 6 4 the rel...

Page 17: ...ay LED outputs The relay outputs and LEDs named R can be controlled depend on both the current value and the peak value when peak detection is active of the input signal 17 zone A zone B measure SEtP parameter HYSt parameter state of relay LED zone B zone A zone B measure SEtP or SEt2 parameter HYSt parameter state of relay LED i ...

Page 18: ... hysteresis and threshold hysteresis respectively If t on and toFF parameters are set to 0 then the relay state will be changed as soon as input value exceeds any of the border values see points A and C Figure 6 5 a b c If values of t on or and toFF are positive then relay state will be turned on if the input value exceeds the border values and stay bigger or lower during at least t on see points ...

Page 19: ...rs connected with relay outputs are described in paragraph rEL1 menu 6 3 2 Two thresholds mode Objaśnienie A B C D E points where measured signal exceeds border values expected value allowed deviation BON BOFF CON COFF EON EOFF relays state changes moments for t on 0 toFF 0 tA tB tC tD tE time periods while input signal is in zone A or zone B Figure 6 6 Principle of LED relay output operation for ...

Page 20: ...cular parameters is described in paragraph MENU DESCRIPTION Some of the parameters can be accessed without menu entering quick view mode After pressing or v button name of the threshold e g rEL1 and his value will be displayed on the display in alternating mode If or v will be pressed in 5 sec again the next threshold will be displayed else the device comes back to the measurement mode If a free a...

Page 21: ...ange of current position flashing digit or the sign Short pressing of the ENTER button causes change of the position digit Press ENTER at least 2 seconds to accept the changes after that question SEt is displayed and user must to confirm or cancel the changes To conform changes and story it in EEPROM press ENTER button shortly after SEt is displayed To cancel the changes press ESC button shortly a...

Page 22: ...de change of value acceleration deceleration direction change While editing switch parameter selection of switch parameter If numerical parameter is being edited a short press of ENTER button change edited position A long press of ENTER button at lest 2 sec causes of display a SEt ask which allow user to make sure if change of the parameter value is correct If switch parameter is being edited a sh...

Page 23: ... in or out value Threshold is the medium value of relay hysteresis HYSt hysteresis of relay range 0 999 Full hysteresis of the relay is equal to 2x HYSt parameter The relay state can change when an input signal is out of threshold hysteresis to threshold hysteresis zone Presented parameters should be set to ensure that SEtP HYSt SEt2 HYSt SEtP HYSt or SEt2 HYSt do not exceeds the measure range Add...

Page 24: ...resis at least toFF time toFF range 0 99 9 defined with 0 1 sec resolution Unit of this parameter is set by unit parameter If time when the input signal exceeds some border value is shorter than t on or toFF time the relay do not change his state see paragraph CONTROL OF THE RELAY OUTPUTS unit unit of time for t on i toFF parameters Can be set on one of two values min minutes SEC seconds AL this p...

Page 25: ...0 voltage inputs expressed in mV Displayed values are defined by parameters Lo C Hi C or by user defined characteristic points and parameter Pnt CHAr this option presets type of the conversion characteristic and can be set to Lin linear Sqr square Sqrt square root When one of those characteristics is chosen display range is defined by Lo C and Hi C USEr user defined characteristic Maximal length 2...

Page 26: ...ecimal point on utmost right position is displayed If user defined characteristic is selected and if number of defined points is lower than 2 then warning Errc is displayed in measurement mode dELP this option allows user to delete any of the points of the user defined characteristic After selection current number of points of the user defined characteristic is displayed for about approx 1 5 sec A...

Page 27: ... of the DISPLAY VALUES CALCULATION paragraph the procedure of the permissible input range determining is presented in details If the measurement value do not exceeds permissible measurement range but displayed value exceeds range 999 9999 the warning Ov is displayed rather than the calculated result 7 3 4 OutP menu This menu contains parameters of current output control Menu is available if the de...

Page 28: ...exceeds defined range then current output generates the current equal to upper or lower border of the defined range The parameters define the percentage extension of nominal current range 4 20 mA with 0 1 resolution Parameter Lo r defines lower border of the range due to formula Imin 4 mA 4 mA Lo r This parameter can be set from 0 to 99 9 Parameter Hi r defines higher border of the range due to fo...

Page 29: ...ing peak value until ESC button is pressed If HdiS rEAL then value timE 0 0 means no holding HdiS type of displayed values rEAL current value is displayed HOLd peak drop value is displayed H r1 H r4 relay LED outputs R1 R4 operation mode rEAL relay LED operates depend on the current value HOLd relay LED operates depend on the peak drop value HOUt current output operation mode rEAL current output o...

Page 30: ...n configuration registers can be set via RS 485 interface oFF configuration registers can not be set via RS 485 interface The access to registers no 04h i 05h cant be denied by mbAc parameter see LIST OF REGISTERS mbtO this parameter defines maximal time sec between following frames received by the device If the delay will be greater than the value of mbtO parameter the relays and the current outp...

Page 31: ...hange the edition mode of numerical parameters dig the change to by digit mode Slid slide change mode 7 3 10 dEFS parameter This setting allows to restore the factory settings of the device To get the access to this option special password is required 5465 next the device displays acknowledge question SEt Press ENTER to acknowledge the restoring of factory settings or ESC to cancel 7 3 11 SErv men...

Page 32: ...easurement mode ENTER MENU ESC ENTER MENU ESC rEL3 MENU ESC MENU ESC bEEP MENU ESC inPt MENU ESC AL r1 r2 r3 r4 Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC tYPE CHAr FiLt Pnt Lo C Hi C AddP dELP Parameter edition EdtP Hi r ENTER MENU ESC ENTER ENTER MENU ESC SEtP SEt2 HYSt modE t on toFF unit AL Parameter edition See next page ENTER MENU ESC ENTER ENTER MENU ESC Omod OUtL OUtH Lo r Hi r ...

Page 33: ...rameter edition ENTER MENU ESC ENTER ENTER MENU ESC Addr bAud mbAc mbtO rESP Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC Scod A r1 A r2 A r3 A r4 ENTER MENU ESC ENTER ENTER MENU ESC modE PEA timE Hdis H r1 H r2 H r3 H r4 Parameter edition HOUt See previous page MENU ESC SEt 4 digit special password entering 0 _ _ _ ENTER ENTER Default settings restoring ...

Page 34: ...an be expressed by expression U n U inp 100 for 0 100 mV range where Uinp Means input voltage in mV and Un normalized result If measured value exceeds the nominal input range 60mV 75mV 100mV or 150mV and do not exceed the permissible input range then received normalized Un result will exceed 0 1 range e g input range 0 100 mV input voltage 1 mV the normalized result is equal 0 01 and for input vol...

Page 35: ...In such a case for an increasing value of input voltage the displayed value decreases Figure 9 1 Normal Lo C Hi C and inverted Lo C Hi C characteristic 9 1 2 Square characteristic The normalized result is squared and further conversion is done as for linear characteristic Conversion is made accordingly with the expression W U n 2 Hi C Lo C Lo C where W means the displayed value Figure 9 2 Normal L...

Page 36: ...Un the device computes specific segment e g for characteristic from figure below and Un 0 65 the segment between points X 50 0 and X 70 0 will be chosen Let s mark those points as PL point low and PH point high in this example PL 50 0 and PH 70 0 and the normalized result Un for the point PL as Up in this example Up Un PL 0 5 The displayed result is calculated accordingly to the expression W U n U...

Page 37: ... should be divided by the width of input range 100 mV Finally the normalized result Un 37 5 100 0 375 In case when input voltage exceeds nominal measurement range calculations are similar For example if input voltage is equal 9 38 mV then Un 9 38 100 0 0938 and if input voltage is equal 103 13 mV then Un 103 13 100 1 0313 Example 3 The linear characteristic Let the input mode 0 100 mV and paramete...

Page 38: ...r square characteristic 0 375 2 1200 300 211 and next the Lo C value is added to the result so the displayed value W 211 300 89 b Uin 9 38 mV and Un 0 0938 W 287 c Uin 103 13 mV and Un 1 0313 W 1295 Example 5 The square root characteristic Let the input mode 0 100 mV and parameters Lo C and Hi C equal to 300 and 1200 respectively The calculations will be done for there different input voltages fro...

Page 39: ...ee page 36 X6 PL 30 Y6 PL 30 X7 PH 40 Y7 PH 80 and Up 0 3 the displayed value W In I p Y PH Y PL X PH X PL 100 Y PL 0 375 0 3 80 30 40 30 100 30 67 b Uin 9 38 mV and Un 0 0938 because of the normalized Un value is lower than 0 the segment defined by X1 and X2 will be selected X1 PL 0 Y1 PL 50 X2 PH 10 Y2 PH 30 and Up 0 For these values the displayed value W 69 c Uin 103 13 mV and Un 1 0313 because...

Page 40: ...egisters can be read by 03h function and wrote by 06h single registers or 10h group of the registers accordingly to Modbus RTU specification Maximum group size for 03h and 10h functions can not exceeds 16 registers for single frame The device interprets the broadcast messages but then do not sends the answers 10 1 LIST OF REGISTERS Register Write Range Register description 01h No 999 9999 Measurem...

Page 41: ...bAc parameter in rS menu permission to write registers via RS 485 interface 0 write denied 1 write allowed 24h Yes see descr Parameters of SECU menu binary format 0 oFF 1 on bit 0 A r1 parameter bit 1 A r2 parameter bit 2 A r3 parameter bit 3 A r4 parameter 25h Yes 0 5 rESP parameter in rS menu additional response delay 0 no additional delay 1 10c option 2 20c option 3 50c option 4 100c option 5 2...

Page 42: ...eter register no 3Dh 3Ch Yes 0 999 toFF parameter in rEL2 menu expressed in tenth of seconds or tenth of minutes depend on unit parameter register no 3Dh 3Dh Yes 0 1 unit parameter in rEL2 menu 0 seconds 1 minutes 3Eh Yes 0 2 AL parameter in rEL2 menu 0 no changes 1 on 2 off 3Fh Yes 999 9999 SEt2 parameter in rEL2 menu no decimal point included 40h Yes 999 9999 SEtP parameter in rEL3 menu no decim...

Page 43: ...timE parameter in HOLd menu maximum peaks or drops display time expressed in seconds 53h Yes 0 1 HdiS parameter in HOLd menu 0 rEAL mode 1 HOLd mode 54h Yes 0 1 H r1 parameter in HOLd menu 0 rEAL mode 1 HOLd mode 55h Yes 0 1 H r2 parameter in HOLd menu 0 rEAL mode 1 HOLd mode 56h Yes 0 1 H r3 parameter in HOLd menu 0 rEAL mode 1 HOLd mode 57h Yes 0 1 H r4 parameter in HOLd menu 0 rEAL mode 1 HOLd ...

Page 44: ...e from menu level only 5 the pairs of X Y coordinates may be defined for any free point The pair is free it means that particular point is not defined if X coordinate of this point is equal 8000h After writing both X and Y coordinate the point is defined and used in calculation of result The coordinates of any point can be changed at any time 10 2 TRANSMISSION ERRORS DESCRIPTION If an error occurs...

Page 45: ...ition can be read from reg 03h b The answer if an error occur ADDR FUNC ERROR CRC L H 01 83 60 41 18 ERROR error code 60h bottom border of the measurement range is exceeded 2 Read of device ID code ADDR FUNC REG H L COUNT H L CRC L H 01 03 00 21 00 01 D4 00 The answer ADDR FUNC BYTE C DATA H L CRC L H 01 03 02 20 FD 60 05 DATA identification code 20FDh 3 Change of the device address from 1 to 2 wr...

Page 46: ...s 1 2 and 3 in one message example of reading a number of registries in one frame ADDR FUNC REG H L COUNT H L CRC L H 01 03 00 01 00 03 54 0B COUNT L the count of being read registers max 16 The answer ADDR FUNC BYTE C DATA H1 L1 DATA H2 L2 DATA H3 L3 CRC L H 01 03 06 00 0A 00 00 00 01 78 B4 DATA H1 L1 reg 01h 10 displayed value 1 0 DATA H2 L2 reg 02h 0 no errors DATA H3 L3 reg 03h 1 decimal point...

Page 47: ... Hysteresis of relay R2 0 0 23 modE Operation mode of relay R2 on 23 t on Turn on delay of relay R2 0 0 24 toFF Turn off delay of relay R2 0 0 24 unit Unit of t on toFF parameters of relay R2 SEC 24 AL Reaction for critical situation of relay R2 oFF 24 Parameters of relay R3 operation rEL3 menu SEtP Relay R3 threshold 60 0 23 SEt2 Relay R3 second threshold 80 0 23 HYSt Hysteresis of relay R3 0 0 2...

Page 48: ...o 0 25 Pnt Decimal point position 0 0 25 Lo C Minimum displayed value for nominal range 000 0 26 Hi C Maximum displayed value for nominal range 100 0 26 Hi r Extension of the top of the nominal input range 5 0 26 Active current output configuration OUtP menu Omod Current output mode 0 20 mA 27 OUtL Display value for 0 mA or 4 mA depend Omod current output 0 0 28 OUtH Display value for 20 mA curren...

Page 49: ...edge on 30 A r2 Permission to changes of relay R2 threshold without of the user password knowledge on 30 A r3 Permission to changes of relay R3 threshold without of the user password knowledge on 30 A r4 Permission to changes of relay R4 threshold without of the user password knowledge on 30 RS 485 interface configuration menu rS Addr Device address 0 30 bAud Baud rate 9 6 30 mbAc Permission to ch...

Page 50: ...User manual METER SRP 147 XC 50 ...

Page 51: ...User manual METER SRP 147 XC 51 ...

Page 52: ...SIMEX Sp z o o ul Wielopole 11 80 556 Gdańsk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl ...

Reviews: