User manual - METER SRL-49
Register
Write
Range
Register description
A2h
1
Yes
-999 ÷ 9999 “
OUtH
” parameter in “
OUtP
” menu,
no decimal point included
A3h
1
Yes
0 ÷ 999
“
Lo r
” parameter in “
OUtP
” menu, expressed in 0.1%
A4h
1
Yes
0 ÷ 199
“
Hi r
” parameter in “
OUtP
” menu, expressed in 0.1%
A5h
1
Yes
0 ÷ 3
“
AL
” parameter in “
OUtP
” menu (current output value on critical
exception):
0
- no change;
1
- 22.1 mA;
2
- 3.4 mA;
3
- 0 mA
B0h
Yes
0 ÷ 1
Parameter“
tyPE
” of sub-menu “
bAr
” (display mode of the
bargraph),
0
- line;
1
- point
B1h
Yes
0 ÷ 6
Parameter “
FCol”
of sub-menu “
bAr
” (colours of the bargraph)
0
- bargraph off;
1
- option “
grEE
”;
2
- option “
rEd
”;
3
- option “
g r
”;
4
-option “
r g
”;
5
- option “
b g
”;
6
- option “
b r
”
B2h
Yes
-999 ÷ 9999 Parameter “
Lo C
” of sub-menu “
bAr
”, no decimal point
B3h
Yes
-999 ÷ 9999 Parameter “
Hi C
” of sub-menu “
bAr
”, no decimal point
B4h
Yes
0 ÷ 3
Parameter “
Pr1P
” of sub-menu “
bAr
” (relay's R1 thresholds'
markers):
0
– not showed;
1
- option ”
1St
”;
2
- option ”
2nd
”;
3
- option ”
botH
”;
B5h
Yes
0 ÷ 3
Parameter “
Pr2P
” of sub-menu “
bAr
” (relay's R2 thresholds'
markers):
0
– not showed;
1
- option ”
1St
”;
2
- option ”
2nd
”;
3
- option ”
botH
”;
B6h
Yes
0 ÷ 3
Parameter “
Pr3P
” of sub-menu “
bAr
” (relay's R3 thresholds'
markers):
0
– not showed;
1
- option ”
1St
”;
2
- option ”
2nd
”;
3
- option ”
botH
”;
B7h
Yes
0 ÷ 3
Parameter “
Pr4P
” of sub-menu “
bAr
” (relay's R4 thresholds'
markers):
0
– not showed;
1
- option ”
1St
”;
2
- option ”
2nd
”;
3
- option ”
botH
”;
B8h
Yes
0 ÷ 4
Parameter “
P1AL
” of sub-menu “
bAr
” (critical situation defined for
relay R1):
0
- no change;
1
- option “
morE
”;
2
- option “
LESS
”;
3
- option “
on
”;
4
- option “
oFF
”
B9h
Yes
0 ÷ 4
Parameter “
P2AL
” of sub-menu “
bAr
” (critical situation defined for
relay R2):
0
- no change;
1
- option “
morE
”;
2
- option “
LESS
”;
3
- option “
on
”;
4
- option “
oFF
”
BAh
Yes
0 ÷ 4
Parameter “
P3AL
” of sub-menu “
bAr
” (critical situation defined for
relay R3):
0
- no change;
1
- option “
morE
”;
2
- option “
LESS
”;
3
- option “
on
”;
4
- option “
oFF
”
BBh
Yes
0 ÷ 4
Parameter “
P4AL
” of sub-menu “
bAr
” (critical situation defined for
relay R4):
0
- no change;
1
- option “
morE
”;
2
- option “
LESS
”;
3
- option “
on
”;
4
- option “
oFF
”
1
- these registers are active only if device is equipped with active current output
2
- after writing to register no 20h the device responds with an “old” address in the message.
3
- after writing to register no 22h the device responds with the new baud rate.
4
- the value of the “
mbAc
” parameter is also connected to write to this register, so it is possible to block a writes, but
impossible to unblock writes via RS-485 interface, The unblocking of the writes is possible from menu level only.
5
-
the pairs of „
X
-
Y
” coordinates may be defined for any free point. The pair is “free” (it means that particular point is
not defined) if „
X
” coordinate of this point is equal 8000h. After writing both X and Y coordinate the point is defined
and used in calculation of result. The coordinates of any point can be changed at any time.
52