8.
EXAMPLES OF PRESCALER PARAMETERS CALCULATION
Problem:
to measure length of the line with assumed precision.
Essential data
:
- number of pulses per revolution given by sensor
- circumference of measurement circle
- assumed measurement resolution
Example 1
Data:
- circumference of measurement circle:
25
cm
- number of pulses:
100
pulses/revolution
- resolution
1 cm
25 cm = 1 revolution = 100 pulses
it means 1 cm=4 pulses
Settings :
mul=”1”
div = “4”
decimal point = “0.”
Obtained range of measured distances 1 cm
to 10 m.
Example 2
Data:
- circumference of measurement circle:
10
cm
- number of pulses:
100
pulses/revolution
- resolution
10 cm
10 cm = 1 revolution = 100 pulses
Settings:
mul=”1”
div = “100”
decimal point = “0.0”
Obtained range of measured distances 10 cm
to 100 m.
Example 3
used in batcher function (see: Figure 6.1, 6.2)
Data:
–
flow meter:
100
pulses / L
–
main valve flow (valve 1): about
10
L / sec.
–
additional valve flow (valve 2): about
1
L / sec.
–
measurement precision: up to
0,1
L.
–
valves are open while relays are closed
Settings:
mul=”1”
div = “10”
decimal point = “0.0”
Pr2
= ”1.0”
- control advance (main valve will be closed when counter reach
Pr1
-
Pr2
)
Pr1
- desired volume of medium
“mod”
=
“ bat”
- batcher mode
„
dir
”
=
„UP”
-
upcounting – counter shows current volume of medium
Pouring starts after pressing of external button [
START pouring
]
(Figure 6.2)
.
33