User manual - CONTROLLER PUR-49D
Register
Write
Range
Register description
D1h
1
Yes
0 ÷ 3
“
Omod
” parameter in “
OUtP
” menu (active current output mode)
0
-
current output disabled
;
1
-
current output enabled
with
4
÷
20mA
mode;
2
-
current output enabled with
0÷20mA
mode
;
Yes
0 ÷ 2
“
Omod
” parameter in “
OUtP
” menu (passive current output mode)
0
-
current output disabled
;
1
-
current output enabled
with
4
÷
20mA
mode;
Yes
0 ÷ 5
“
Omod
” parameter in “
OUtP
” menu (active voltege output mode)
0
- voltage
output disabled
;
1
- voltage
output enabled
with
0
÷5V
mode;
2
- voltage
output enabled with
1÷5V
mode
;
3
- voltage
output enabled with
0÷10V
mode
;
4
- voltage
output enabled with
2÷10V
mode
;
D2h
1
Yes
-999 ÷ 9999 “
OUtL
” parameter in “
OUtP
” menu,
no decimal point included
D3h
1
Yes
-999 ÷ 9999 “
OUtH
” parameter in “
OUtP
” menu,
no decimal point included
D4h
1
Yes
0 ÷ 999
“
Lo r
” parameter in “
OUtP
” menu, for active current output and
active voltage output, expressed in 0.1%
Yes
0 ÷ 299
“
Lo r
” parameter in “
OUtP
” menu for passive current output,
expressed in 0.1%
D5h
1
Yes
0 ÷ 199
“
Hi r
” parameter in “
OUtP
” menu for active and passive current
output, expressed in 0.1%
Yes
0 ÷ 99
“
Hi r
” parameter in “
OUtP
” menu for active voltage output,
expressed in 0.1%
D6h
1
Yes
0 ÷ 3
“
AL
” parameter in “
OUtP
” menu (active current output value on
critical exception):
0
- no change;
1
- 22.1 mA;
2
- 3.4 mA;
3
- 0 mA
Yes
0 ÷ 2
“
AL
” parameter in “
OUtP
” menu (passive current output value on
critical exception):
0
- no change;
1
- 22.1 mA;
2
- 3.4 mA
Yes
0 ÷ 5
“
AL
” parameter in “
OUtP
” menu (active voltage output value on
critical exception):
0
- no change;
1
- 11 V;
2
- 5.5;
3
- 1.2 V;
4
- 0.6 V;
5
- 0 V
F0h
Yes
0 ÷ 4
“
modE
” parameter in“
CtrL
” menu:
0
- “
oFF
” option;
1
- opcja
Pid
” option;
2
- “
At-F
” option;
3
- opcja
At-H
” option;
4
- “
At-C
” option;
F1h
Yes
-999 ÷ 9999
“
SEtP
” parameter in“
CtrL
” menu, no decimal point included
F2h
Yes
0 ÷ 9999
“
P -H
” parameter in“
PArH
” menu, no decimal point included
F3h
Yes
0 ÷ 9999
“
tI-H
” parameter in“
PArH
” menu, no decimal point included
F4h
Yes
0 ÷ 9999
“
td-H
” parameter in“
PArH
” menu, no decimal point included
F5h
Yes
-999 ÷ 9999
“
OF-H
” parameter in“
PArH
” menu, no decimal point included
F6h
Yes
0 ÷ 999
“
Lo-H
” parameter in“
PArH
” menu, no decimal point included
F7h
Yes
1 ÷ 1000
“
Hi-H
” parameter in“
PArH
” menu, no decimal point included
F8h
Yes
0 ÷ 9999
“
P -C
” parameter in“
PArC
” menu, no decimal point included
F9h
Yes
0 ÷ 9999
“
tI-C
” parameter in“
PArC
” menu, no decimal point included
FAh
Yes
0 ÷ 9999
“
td-C
” parameter in“
PArC
” menu, no decimal point included
69