User manual - CONTROLLER PUR-49D
Register
Write
Range
Register description
10h
Yes
0 ÷ 20
“
tyPE
” parameter in “
InPt
” menu (nominal input range):
0
- 0-20 mA range;
1
- 4-20 mA range;
2
- 0-5 V range;
3
- 1-5 V range;
4
- 0-10 V range;
5
- 2-10 V range;
6
- 0-60 mV range;
7
- 0-75 mV range;
8
- 0-100 mV range;
9
- 0-150 mV range;
10
- Pt-100;
11
- Pt-500;
12
- Pt-1000
13
-
thermocouple input
K;
14
-
thermocouple input
S;
15
-
thermocouple input
J;
16
-
thermocouple input
T;
17
-
thermocouple input
N;
18
-
thermocouple input
R;
19
-
thermocouple input
B;
20
-
thermocouple input
E;
11h
Yes
0 ÷ 3
“
CHAr
” parameter in “
InPt
” menu (characteristic type)
0
- linear ;
1
- square;
2
- square root;
3
- user defined
12h
Yes
0 ÷ 255
“
FiLt
” parameter in “
InPt
” menu (time constant in seconds)
13h
Yes
0 ÷ 3
“
Pnt
”parameter in “
InPt
” menu (the copy of 03h register, decimal
point position):
0
- “
0
”;
1
- “
0.0
”;
2
- “
0.00
”;
3
- “
0.000
”
14h
Yes
-999 ÷ 9999 “
Lo C
” parameter in “
InPt
” menu, no decimal point included
15h
Yes
-999 ÷ 9999 “
Hi C
” parameter in “
InPt
” menu, no decimal point included
16h
Yes
0 ÷ 999
“
Lo r
” parameter in “
InPt
” menu, in 0.1%
17h
Yes
0 ÷ 199
“
Hi r
” parameter in “
InPt
” menu, in 0.1%
18h
Yes
-99 ÷ 99
“
toFS
” parameter in “
InPt
” menu (shift of measurement scale),
expressed by 0.1°C (for RTD input) or by 1.0°C (for TC input)
19h
Yes
0 ÷ 2
“
Conn
” parameter in “
InPt
” menu (RTD input connection method):
0
- “
4 in
”;
1
- “
3 in
”;
2
- “
2 in
”
20h
2
Yes
0 ÷ 199
Device address
21h
No
Device identification code (ID)
22h
3
Yes
0 ÷ 7
“bAud”
parameter in
“rS”
menu (baud rate);
0
- 1200 baud;
1
- 2400 baud;
2
- 4800 baud;
3
- 9600 baud;
4
- 19200 baud;
5
- 38400 baud;
6
- 57600 baud;
7
- 115200 baud
23h
4
Yes
0 ÷ 1
“mbAc”
parameter in
“rS”
menu (permission to write registers via
RS-485 interface);
0
- write denied ;
1
- write allowed
24h
Yes
see descr.
Parameters of “
SECU
” menu (binary format (0 - „
oFF
”, 1 - „
on
”):
bit 0
- “
A r1
” parameter;
bit 1
- “
A r2
” parameter
bit 2
- “
A r3
” parameter;
bit 3
- “
A r4
” parameter;
bit 4
- “
A Pid
”
parameter;
25h
Yes
0 ÷ 5
“rESP”
parameter in
“rS”
menu (additional response delay);
0
- no additional delay;
1
- ”
10c
” option;
2
- ”
20c
” option;
3
- ”
50c
” option;
4
- ”
100c
” option;
5
- ”
200c
” option;
27h
Yes
0 ÷ 99
“mbtO”
parameter in
“rS”
menu (maximum delay between
received frames);
0
- no delay checking;
1
÷
99
- maximum delay expressed in seconds
28h
Yes
0 ÷ 1
“
AL
” parameter in “
bEEP
” menu:
0
- off;
1
- on
29h
Yes
0 ÷ 1
“
R1
” parameter in “
bEEP
” menu:
0
- off;
1
- on
2Ah
Yes
0 ÷ 1
“
R2
” parameter in “
bEEP
” menu:
0
- off;
1
- on
64