User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
7.8.7.
Logical Channels - Controller mode
This mode allows the user to set up the PID control loop which may control the objects
and Controller output signal for display on the screen, processed in any other logical channels
or it can be the data source for output to the control and settings of any object. To create
controlling process
the
Logical Channel
should be set in
Controller
mode as in
Fig. 7.54. Input channel configuration in Controller mode
To the parameters of
Logical channel
in
Controller
mode should be:
–
Name
- it gives the name to the logical channel,
–
Mode=Controller
- in this parameter user selects source of data for logical channel,
–
Unit
- this parameter allows the user to define the unit,
–
Controller number
- this parameter allows the user to select a controller from the list
(1÷8). User must configure the selected controller in the
Controllers
menu (overview
and configuration parameters that define the controllers can be found in
Chapter
–
Set point channel
- this parameter allows the user to select a logical channel with
Set point channel
defines input data for process
control,
–
Feedback channel
- this parameter allow the user to select a channel with data
returned from control system (see
Feedback channel
define input data
for process control,
105
disabled
Hardware input
Hardware output monitor
Modbus
Set point value
Math function
Controller
Profile/timer
Profile/timer (cycle counter)
Data from other channel
Logical channel
Device configuration
MENU
Mode