LOGICA REMOTE CONTROL

All the boiler's functions can be managed

by  a  optional  digital  multifunctional  device

code 8092204 for the remote of the boi-

ler  itself  and  for  regulating  room  climatic

conditions  with  an  operational  reserve  of

12 hours.

The heating circuit is controlled by the room

temperature  sensor  built-in  the  equipment

or  by  the  atmospheric  conditions,  with  or

without environmental inflow, if the boiler is

connected to an external sensor.

Characteristics:

– Ergonomic control unit divided according

to function (control levels)).

– Clear division of basic functions:

operating  regime,  correction  of  set

value and presence button are directly

accessible;

Dif fer ent  r eal  curr ent  values  ar e

accessible through the "info" button;

other  functions  can  be  programmed

after the cover has been opened;

special  service  level  with  protected

access;

– Each  setting  or  modification  is  displayed

and confirmed.

– Tome  setting  (special  line  for  changing

BST/CET).

– Heating programme with max. 3 heating

periods per day, individually selectable.

– Copy  function  for  easy  transfer  of  hea-

ting  programme  to  the  next  or  pre-

vious day.

– Holiday  programme:  the  programme  is

interrupted  for  the  holiday  period  and

automatically  restar ted  on  returning

home.

– Option to return the heating program to

default values.

– Programming lock (child safety).

Functions:

– Delivery  temperature  control  guided  by

the  atmospheric  conditions,  taking  into

account the dynamics of the building.

– Delivery  temperature  control  guided  by

atmospheric  conditions  with  influence  of

ambient temperature.

– Ambient temperature control only.

– Adjustable influence of ambient tempera-

ture shift .

– Switch-on and switch-off optimisation.

– Rapid lowering.

– ECO functions (daily heating limiter, auto-

matic summer/winter switch-over).

– Controllable  maximum  delivery  tempera-

ture limit (specifically for floor plants).

– Limitation  of  increase  in  pre-set  delivery

temperature.

– Anti-freeze protection for buildings.

– Hourly  programming  of  the  tank  unit

temperature  on  two  levels:  comfort  and

reduced.

– Domestic hot water control with nominal

value requirement and enable.

– Connection to room sensor or switching

of operating regime through the telepho-

ne  sys t em  wit h  ext ernal  cont act  or

through a window contact.

– Anti-bacterial.

2.10.1 Installation

The  unit  must  be  installed  in  the  main  living

room.  For  installation,  follow  the  assembly

instructions  inserted  in  the  package.  At  this

point,  with  the  selector  knob  on  (

),  the

installer can adjust the basic parameters set-

tings according to the individual needs (point

2.10.2). 

If  there  is  a  thermostatic  radiator

valve fitted, this must be set to maximum.

2.10.2 Installation settings

The  settings  for  the  basic  operating  para-

meters for individual needs are reported in

the  instruction  leaflet  supplied  with  the

"Logica Remote Control" and in the section

reserved for the user in this manual.

For  further  adjustments  which  can  be  car-

ried out by the installer, the "Logica Remote

Control"  offers  a  level  of  service  and  para-

meterising  which  can  only  be  accessed

through a special combination of buttons.

To  activate  this  level  of  service  or  parame-

terising  press  buttons

and

least  5

seconds.  This  will  activate  the  parameteri-

sing level. Then use the same arrow buttons

to select the individual input lines and adjust

the values with

or

.

Antifreeze protection 

"Pre-set ambient 

temperature value"

Summer/Winter switch-over 

temperature

Type of control:

0 = with ambient influence

1 = without ambient influence

Influence of ambient temperature

Heating takes place up to this pre-set value if the plant is activated in standby

(e.g. holidays). 

In this way, the building antifreeze function is active, preventing an excessive

lowering of the ambient.

This parameter regulates the temperature of the automatic summer/win-

ter switch-over.

This  parameter  de-activates  the  ambient  influence  and  as  a  result  all  the

optimisations and adaptations. 

If a valid external temperature is not transmitted , the controller switches to

the  pure ambient control guide variable.

If the ambient controller is used only as a remote control (placed in the refe-

rence room and without an external sensor connected), the value must be

set at 0 (zero). 

If  the  change  in  ambient  temperature  from  the  pre-set  value  remains  high

during the entire day, the influence must be increased. If the ambient tem-

perature is around the pre-set value (control oscillation), the influence must

be reduced. 

Note: If the ambient temperature influence constant is set at 0, the adap-

tation of the heating curve is deactivated. In this case, parameter 57 will

have no effect at all.

54

HEATING CIRCUIT SETTINGS

52

53

51

Summary of Contents for PLANET DEWY 30 BFR

Page 1: ...is unobstructed and has been pro perly installed Make sure that any shutoff valves are open Make sure that the system is charged with water and is thoroughly vented Check that the circulating pump is...

Page 2: ...H return 3 4 M C H flow 3 4 G Gas connection 3 4 C1 System filling optional 1 2 S3 Condensation outlet 25 1 3 TECHNICAL FEATURES 30 BFR Heat output Nominal 80 60 C kW kcal h 28 3 24 300 Minimum 80 60...

Page 3: ...ixing jig 19 90 C limit stat 20 Condensation water trap 21 Gas rate adjuster 22 System filling optional 23 Aqua Guard 24 Non return valve 1 5 MAIN COMPONENTS Fig 3 KEY 1 Control panel 2 Gas rate adjus...

Page 4: ...e data plate is sticked inside the front panel it contains all the technical data identifying the boiler and the type of gas for which the boiler is arranged 2 3 1 Connection of condensation water tra...

Page 5: ...ow eaves 300 D below balcony 1 300 E from adjacent window 400 F from adjacent ventilation opening 600 G from horizontal or vertical soil or drain pipes 2 300 H from corner of building 300 I from reces...

Page 6: ...on calculation in that the sum of the head losses of the single fittings is less than 15 5 mm H2O Inlet Outlet 7 m horizontal pipe 80 x 0 20 1 40 7 m horizontal pipe 80 x 0 30 2 10 n 2 90 elbows 80 x...

Page 7: ...eed 15 5 mm H2O When calculating the lengths of pipe take into account the parameters given in the Table 2 2 8 60 PIPING SYSTEM A special kit allows to separate smoke outlet and air intake pipes The 8...

Page 8: ...cables of section 0 5 mm2 First of all assemble and wire the socket 2 then insert the equipment which will start up as soon as it receives current To gain access to connector 3 remove the control pan...

Page 9: ...electrode ER Sensing electrode TS 100 C safety stat V Fan TPA Water pressure transducer P Pump SE External sensor optional TA Room stat SM C H sensor blue TR Transformer 230 24V FL Flowmeter CR Logic...

Page 10: ...rough a window contact Anti bacterial 2 10 1 Installation The unit must be installed in the main living room For installation follow the assembly instructions inserted in the package At this point wit...

Page 11: ...nute of the prescribed delivery temperature value sent in C is limited to the imposed value With the activation of the adaptation the pre set value transmitted to the boiler regulator is adapted to th...

Page 12: ...o par metro 64 1 0 activa s a sonda interna 0 externa 100 interna 50 valor m dio da sonda externa interna 100 activa s a sonda externa Para a regula o ambiente e a visualiza o utilizada a mistura pro...

Page 13: ...egulated so as to obtain a pressure of approx 3 mbar at the burner for methane gas and 7 mbar for propane gas G31 To increase pressure turn the trimmer clockwise to reduce pres sure turn the trimmer c...

Page 14: ...up There could have a break in the wire of the sensing electrode or the electrode itself is touching earth the electrode is worn out and needs replacing The con trol box is defective When there is a...

Page 15: ...function of the flow in graph in fig 21 3 7 MAINS ELECTRICITY CONNECTION Use a separate electricity supply to con nect the room stats and relative zone val ves or pumps The micro or relay contact con...

Page 16: ...2 Gas valve 3 Mixer intake 4 Ventilator intake 5 Nozzle 6 Fan 7 Air gas mixer 8 Air pressure switch 9 Digital pressure gauge Fig 24 0 30 20 10 p aria mm H2O Potenza termica kW 25 20 10 15 50 40 60 5 3...

Page 17: ...G31 boilers it is a good idea to check that the position of the GPL bridge on the control board is correct Diaphragm code 6028640 Drawing 7 is assembled on the Dewy 25 model functioning on PROPANE G3...

Page 18: ...sliding them out of their slots 4 6 CLEANING AND MAINTENANCE Preventive maintenance and checking of efficient operation of equipment and safety devices must be carried out exclusively by authorized te...

Page 19: ...ing of the water C H TEMPERATURE ADJUSTMENT fig 2 The C H temperature can be adjusted by turning the knob of the C H potentiometer The set temperature is indicated on the red led scale from 35 80 C an...

Page 20: ...out occurs again call local authorised Service Centre for technical assistance Other anomalies fig 6 When one of the red 40 80 C leds start flashing switch off the boiler and then try to ignite again...

Page 21: ...utton automatic operation 4 Operating mode button manual operation 5 Operating mode button availability 6 Cover with instruction compartment 7 Temperature knob 8 Presence button Fig 8 KEY 1 Display ti...

Page 22: ...l lowing list of items one after the other are displayed The thermo feeler continues to function independently of the display Day hour room temperature External temperature Hot water service temperatu...

Page 23: ...ity boiler unit temperature desired for hot water service at reduced level To have access to the reduced hot water service temperature parameter press the and keys at the same time for at least 5 seco...

Page 24: ...rature set in parameter 3 1 standard Hot water according to the daily heating programme In the comfort periods of the heating the temperature of the boiler unit is regulated at the value set via para...

Page 25: ...of the heating characteristics curve When the room temperature set is not reached choose the gradient indicated in point 2 9 3 Display of the current boiler temperature Display of the current power of...

Page 26: ...fficient water pressure Reset operation using the boiler charge valve fig 4 Plant overpressure Call an authorised Service Centre Safety thermostat trips Call an authorised Service Centre Fan air press...

Reviews: