90
2.11
ELECTRICAL CONNECTION
The boiler is supplied with an electric cable.
Should this require replacement, it must be
purchased exclusively from SIME.
The electric power supply to the boiler must
be 230V-50Hz single-phase through a
fused main switch, with at least 3 mm spa-
cing between contacts.
Respect the L and N polarities and the
earth connection.
NOTE: Device must be connected to an
efficient earthing system.
.
SIME declines
all responsibility for injury or damage to
persons, animals or things, resulting from
the failure to provide for proper earthing
of the appliance. Device must be connec-
ted to an efficient earthing system.
2.11.1
Timer-thermostat connection
(fig. 13 pos. A)
To gain access to the electronic board con-
nector (3), remove the control panel cover
and connect the timer-thermostat to the ter-
minals TA after having removed the jumper.
The timer-thermostat, recommended for
better room temperature control, must be
class II as specified by standard EN 60730.1
(clean contact).
WARNING: Applying mains voltage to the
terminals of connector (3) will irreparably
damage the control board. Make sure
that any connections to be made are not
carrying mains voltage.
2.11.2 “Logica Remote Control”
connection (fig. 13 pos. B)
The electrical plant must comply with
local standards and all cables must com-
ply with low safety voltage requirements
of EN 60730. For lengths up to 25 m,
use cables of section 0.25 mm
2
, for lon-
ger lengths up to 50 m use cables of sec-
tion 0.5 mm
2
. First of all, assemble and
wire the socket (2), then insert the equip-
ment which will start-up as soon as it recei-
ves current. To gain access to connector
(3) remove the control panel cover and
connect the climate regulator to terminals
CR (6-7).
WARNING: External voltage must not be
connected to terminals 1-2-3-4 of the
spcket (2). On terminals 3-4 can be con-
nected a telephone remote switch with a
zero potential contact or a window con-
tact . Equipment for the checking of civil
plants via a telephone line includes the
model TEL 30.4 LANDIS & STAEFA.
2.11.3 External temperature sensor
connection (fig. 13 pos. C)
The cables must comply with low safety vol-
tage requirements of EN 60730.
For lengths up to 25 m, use cables of sec-
tion 0.25 mm
2
, for longer lengths up to 50
m use cables of section 0.5 mm
2
. To gain
access to boiler connector (3) remove the
control panel cover and connect the external
temperature sensor to terminals SE (8-9).
1
2
A
C
LOGICA REMOTE
CONTROL
SONDA
ESTERNA
CRONOTERMOSTATO
LOGICA REMOTE
CONTROL
B
3
Fig. 13
KEY
1
Control panel
2
“Logica Remote Control” socket
3
J2 connector
TA Timer-thermostat (not supplied)
CR Logica Remote Control (optional)
SE External temperature sensor (optional)
EXTERNAL
SENSOR
TIMER-THERMOSTAT