37
7.3
Parameter setting and display
To go into the parameter menu:
– from the selected mode (eg. WINTER)
– press the buttons
<
and
o
(approximately 5 seconds) at the
same time until
"tS"
(installer) appears on the 2 digits of the
display which alternate with
"0.1"
(parameter number) and a
"2"
(set value)
– press the button
>
to scroll up the list of parameters and then
<
to scroll down the list
NOTE:
holding the buttons
>
or
<
increases the speed of the
scrolling movement.
– once the required parameter has been reached, press the
button
o
for approximately 3 seconds to confirm and access
the set value which will then flash and can then be modified
– to modify the value in the permitted range, press the buttons
>
to increase it or
<
to decrease it
– once the required value has been reached, press the button
o
to confirm.
When all the parameter modifications have been made, exit the
parameter menu by pressing and holding down the buttons
<
and
o
at the same time
for approximately 5 seconds until the
initial screen is displayed.
7.4
List of parameters
Type
No. Description
Range
U/M
Step
Default
CONFIGURATION
tS
0.1 Index showing boiler power in kW
2 = 30 kW
3 = 35 kW
-
1
2 o 3
tS
0.2 Hydraulic configuration
0 = combi
1 = N/A
2 = N/A
3 = N/A
4 = N/A
5 = N/A
6 = N/A
-
1
0
tS
0.3 Gas Type Configuration
0 = G20
1 = G31
2 = G230
-
1
0
tS
0.4 Combustion configuration
0 = sealed chamber with combustion control
-
-
0
tS
0.8 External sensor value correction
-5 .. +5
°C
1
0
tS
0.9 Ignition fan speed
80 .. 160
RPMx25
1
128
DOMESTIC HOT WATER - HEATING
tS
1.0 Boiler Antifreeze Threshold
0 .. +10
°C
1
3
tS
1.1 External Sensor Antifreeze Threshold
-- = Disabled
-9 .. +5
°C
1
-2
tS
1.2 Heating Curve Incline
0 .. 80
-
1
20
tS
1.3 Minimum Heating Temperature Adjustment
20 .. Par tS 1.4
°C
1
20
tS
1.4 Maximum Heating Temperature Adjustment
Par tS 1.3 .. 80
°C
1
80
tS
1.5 Maximum power in CH mode
0 .. 100
%
1
100
tS
1.6 Heating Post-Circulation Time
0 .. 99
seconds
x 10
1
3
tS
1.7 Heating Pump Activation Delay
0 .. 60
seconds
x 10
1
0
tS
1.8 Heating Re-ignition Delay
0 .. 60
Min
1
3
tS
1.9 Domestic Hot Water Modulation with Flow meter
0 = Disabled
1 = Enabled
-
1
1
tS
2.0 Maximum power domestic hot water
0 .. 100
%
1
100
tS
2.1 Minimum power heating/domestic hot water
(premixed)
0 .. 100
%
1
0
tS
2.2 Domestic hot water preheating enabling
0 = OFF
1 = ON
-
1
0
tS
2.5 Auxiliary TA function
0 = according to TA
1 = TA Antifreeze
2 = domestic hot water disabled
-
1
0