usable.height.of.the.water.trap.must.be.at.
least.150.mm.
2.7
FORCED EXHAUST
TYPE B23P - B53P
(fig. 9/a)
This. type. of. exhaust. pipe. is. installed. using.
the. special. kit,. code. 8089912/13.. For. kit.
assembly. instructions,. refer. to. point. 2.6..
Protect. the. intake. with. the. optional. acces-
sory,.code.8089501..
The.accessory.is.assembled.by.cutting.a.50.
mm. long. segment. from. an. ordinary. ø. 80.
extension.and.inserting.it.on.the.air.intake,.
on.which.the.accessory.is.then.fitted,.ancho-
red. to. the. pipe. segment. with. the. screws.
provided.(fig..9/a)...
Maximum flow resistance must be no more
than 10 mm H
2
O (version 12) - 15 mm H
2
O
(version 25-30-35) (ATTENTION: the total
length of each pipe should not exceed 25 m,
even if the total loss is below the maximum
applicable loss.)
As. the. maximum. pipe. length. is. determi-
ned. by. adding. up. the. flow. resistance. of.
the.various.individual.accessories.installed,.
refer.to.Table 1-1/a.for.calculation.
2.8
POSITIONING THE
OUTLET TERMINALS (fig. 10)
The. outlet. terminals. for. forced-draught.
appliances. may. be. located. in. the. external.
perimeter.walls.of.the.building..
To.provide.some.indications.of.possible.solu-
tions,.Table 3.gives.the.minimum.distances.
to.be.observed,.with.reference.to.the.type.of.
building.shown.in.fig..10.
2.9
ELECTRICAL
CONNECTION
The.boiler.is.supplied.with.an.electric.cable..
Should.this.require.replacement,.it.must.be.
purchased.exclusively.from.SIME..
The.electric.power.supply.to.the.boiler.must.
be.230V.-.50Hz.single-phase.through.a.fused.
main. switch,. with. at. least. 3. mm. spacing.
between.contacts..
Respect.the.L.and.N.polarities.and.the.earth.
connection.
NOTE: SIME declines all responsibility for
injury or damage to persons, animals or
things, resulting from the failure to provide
for proper earthing of the appliance.
2.9.1
Chronothermostat connection
Connect.the.chronothermostat.as.indicated.
in.the.boiler.electrical.diagram
.
(see figs. 11
e 11/a)
after. having. removed. the. existing.
bridge..
The. chronothermostat. to. be. used. must. be.
Fig..10
TABLE 3
Siting.of.terminal.
Appliances.from.7.to.35.kW
. . .
(distances.in.mm)
A. -. below.openable.window.
600
B. -. below.ventilation.opening.
600
C. -. below.eaves.
300
D. -. below.balcony.(1).
300
E. -. from.adjacent.window.
400
F. -. from.adjacent.ventilation.opening.
600
G. -. from.horizontal.or.vertical.soil.or.drain.pipes.(2).
300
H. -. from.corner.of.building.
300
I. -. from.recess.in.building.
300
L. -. from.ground.level.or.other.treadable.surface.
2500
M.-. between.two.terminals.set.vertically.
1500
N. -. between.two.terminals.set.horizontally.
1000
O. -. from.a.surface.facing.without.openings.or.terminals. 2000
P. -. as.above.but.with.openings.and.terminals.
3000
1). Terminals. below. a. practicable. balcony. must. be. located. in.
such.a.way.that.the.total.path.of.the.smoke.from.its.outlet.
point.from.the.terminal.to.its.outlet.point.from.the.external.
perimeter. of. the. balcony,. including. the. height. of. possible.
railings,.is.not.less.than.2000.mm.
2). When.siting.terminals,.where.materials.that.may.be.subject.
to.the.action.of.the.combustion.products..are.present.in.the.
vicinity,.e.g.,.eaves,.gutters.and.downspouts.painted.or.made.
of.plastic.material,.projecting.timberwork,.etc.,.distances.of.
not. less. than. 1500. mm. must. be. adopted,. unless. adequate.
shielding.is.provided.to.guard.these.materials.