2.6.1 Separate
ducts kit
(fig. 9)
The.diagrams.of.Figure.9.show.a.few.exam-
ples. of. the. permitted. exhausts. configura-
tions.
2.6.2 Connection to existing flues
The. ø. 80. or. ø. 60. exhaust. pipe. can. also. be.
connected.to.existing.flues..When.the.boiler.
runs.at.low.temperature,.it.is.possible.to.use.
standard.flues.provided.that:
-.. The.flue.is.not.be.used.by.other.boilers.
-...The.interior.of.the.flue.is.protected.to.pre-
vent. a. direct. contact. with. condensation.
from.the.boiler..The.products.of.combu-
stion.must.be.conveyed.through.a.flexible.
or. rigid. plastic. pipe. around. 100. to. 150.
mm.in.diameter,.and.condensation.must.
be.siphoned.off.at.the.foot.of.the.pipe..The.
277,5
67,5
169
14
8
11
2
13
4
236
CS
CA CA
11
9
222
ø 80
ø 60
Fig..7
KEY
CA. Inlet
CS. Outlet
Example.of.allowable.installation.vers..“25” calculation.in.that.the.sum.of.the.head.
losses.of.the.single.fittings.is.less.than.7.6.mm.H
2
O:
Inlet
Outlet
9.m.horizontal.pipe.ø.80.x.0.15.
1.35.
.
–
9.m.horizontal.pipe.ø.80.x.0.15.
–.
.
1.35
n°.2.90°.elbows.ø.80.x.0.20.
0.40.
.
–
n°.2.90°.elbows.ø.80.x.0.25.
–.
.
0.50
n°.1.terminal.ø.80.
0.10.
.
0.25
Total.head.loss.
1.85.
+.
2.10.
= 3.95 mm H
2
O
Fig..8
TABLE 1 - ACCESSORIES ø 80
Accessories.ø.80.
Total.head.loss.(mm.H
2
O)
.
12
25
30
35
.
Inlet
.
Outlet
.
.
.
Inlet
.
Outlet
.
Inlet
.
Outlet
.
Inlet
.
Outlet
.Coaxial.duct.kit
.
–.
–.
.
.
–.
–.
–.
–.
–.
–
90°.elbow.MF
.
0.05.
0.10.
.
.
0.20.
0.25.
0.25.
0.30.
0.30.
0.40
45°.elbow.MF
.
0.05.
0.05.
.
.
0.15.
0.15.
0.20.
0.20.
0.25.
0.25
Extension.L..1000.(horizontal)
.
0.05.
0.05.
.
.
0.15.
0.15.
0.20.
0.20.
0.25.
0.25
Extension.L..1000.(vertical)
.
0.05.
0.05.
.
.
0.15.
0.15.
0.20.
0.20.
0.25.
0.25
Wall.terminal
.
0.05.
0.15.
.
.
0.10.
0.25.
0.10.
0.35.
0.15.
0.50
Wall.coaxial.exhaust.*
.
.
Roof.outlet.terminal.*.
0.25.
0.05.
.
.
0.80.
0.10.
1.10.
0.15.
1.50.
0.20
*.
The loss of the accessorie in aspiration concludes the collector code 8091400/01
TABLE 1/a - ACCESSORIES ø 60
Accessories.ø.60.
Total.head.loss.(mm.H
2
O)
.
12
25
30
35
.
Inlet
.
Outlet
.
.
.
Inlet
.
Outlet
.
Inlet
.
Outlet
.
Inlet
.
Outlet
Coaxial.duct.kit
.
1.25.
0.25.
.
.
2.50.
0.50.
2.50.
0.50.
2.50.
0.50
90°.elbow.MF
.
0.15.
0.40.
.
.
0.40.
0.90.
0.50.
1.10.
0.60.
1.40
45°.elbow.MF
.
0.10.
0.25.
.
.
0.35.
0.70.
0.45.
0.90.
0.55.
1.20
Extension.L..1000.(horizontal)
.
0.10.
0.40.
.
.
0.40.
0.90.
0.50.
1.10.
0.60.
1.40
Extension.L..1000.(vertical)
.
0.10.
0.30.
.
.
0.40.
0.60.
0.50.
0.70.
0.60.
0.80
Wall.terminal
.
0.15.
0.70.
.
.
0.50.
1.20.
0.80.
1.40.
1.10.
1.60
Wall.coaxial.exhaust.*
.
.
Roof.outlet.terminal.*
.
0.25.
0.05.
.
.
0.80.
0.10.
1.10.
0.15.
1.50.
0.20
*.
The loss of the accessorie in aspiration concludes the collector code 8091400/01
OPERAZIONE.DA.ESEGUIRE
SOLO.NEL.MONTAGGIO.DEL
KIT.Ø.80.COD..8089912
A
B
4
1
3
2
6
4
5
C
A
B
4
1
3
2
ASSEMBLY OF THE KIT ø 80 code 8089912/ø 60 code 8089913
KEY
1. ø.125.Gasket
2. Fumes.exhausts.
.
flange.with.tap
3. Fastening.screw
4. ø.108.Gasket
5. Suction.collar.(only.for.
kit.code.8089913)
6. MF.ø.60.reduction.(only.
for.kit.code.8089913)
OPERATIONS. REQUIRED.
ONLY.FOR.THE.ASSEMBLY.
OF. THE. ø. 80. KIT. CODE.
8089912