44
To enter "
"refer to the indications
provided in the specific section.
Once the parameters in the table have been set, you must carry
Automatic calibration procedure
".
If the
gas valve
and/or the
ignition/detection electrode
and/or the
fan
are replaced, the user must still carry out the entire phase
Automatic calibration procedure
" described in the specific
section.
10.6 Possible faults and solutions
LIST OF MALFUNCTION/FAULT ALARMS
Type
No.
Fault
Solution
ALL
02
Low water pressure in
system
- Restore pressure
- Check for any leaks in
the system
ALL
03
High water pressure in
system
- Empty the system via
the drain valve on the
hydraulic assembly and
bring the pressure to
approximately 1.2 bar
(120 kPa)
ALL
04
-
ALL
05
Delivery sensor fault
- Check connections
- Replace the sensor
ALL
06
No flame detection
- Check the integrity of
the electrode and check
that it is not grounded
- Check gas availability
and pressure
- Check the integrity of
the gas valve and the
card
ALL
07
Intervention of the
second element of the
delivery sensor
- Check the delivery
sensor connections
- Deaerate the system
- Check the bleed valve
- Replace the delivery
sensor
- Check that the pump
impeller is not blocked
ALL
08
Fault in the flame
detection circuit
- Check the integrity of
the electrode and check
that it is not grounded
- Check gas availability
and pressure
- Check the integrity of
the gas valve and the
card
ALL
09
No water circulating in
the system
- Check the rotation of
the pump rotor
- Check the electrical
connections
- Replace the pump
ALL
10
Auxiliary sensor fault
- Check PAR
02 "hydraulic
configuration"
- Check the electrical
connection
ALL
11
Gas valve modulator
disconnected
- Check the electrical
connection
ALL
12
Incorrect configuration
of the open /sealed
chamber
- Set the parameter
tS 0.4 (Combustion
configuration) to 0
ALL
17
Fault regarding
maximum deviation
between the 2 NTC
heating sensors
- Replace the dual
sensor
ALL
28
Maximum number of
consecutive resets
reached
- Disconnect and
reconnect the power
- If the alarm persists,
contact the Technical
Assistance Centre
ALL
37
Fault due to low network
voltage.
- Check with tester
- Contact network
provider (ENEL)
ALL
40
Incorrect network
frequency detected
- Contact network
provider (ENEL)
ALL
41
Flame loss more than 6
consecutive times
- Check the detection
electrode
- Check the gas supply
(open valve)
- Check mains gas
pressure
ALL
42
Button fault
- Check that buttons are
working
ALL
43
Open Therm
communication fault
- Check the electrical
connection of the
remote control
ALL
44
Anomaly inside electronic
board
- Replace the board
ALL
62
The self-calibrating
procedure must be
carried out
- Carry out the self-
calibrating procedure
(see the specific
section)
ALL
72
Incorrect positioning of
the delivery sensor
- Check that the delivery
sensor is attached to
the delivery pipe
ALL
74
Fault in the 2nd element
of the delivery sensor
- Replace the sensor
ALL
80
Anomaly in gas valve
control line
- Check/replace the
connection cable to the
gas valve
ALL
81
Block due to combustion
during start-up
- Check for blockage in
chimney
- Bleed the air from the
gas circuit
ALL
83
Irregular combustion
(temporary error)
- Check for blockage in
chimney
ALL
88
Anomaly inside electronic
board
- Replace the board
ALL
96
Block due to clogging in
smoke outlet
- Check for blockage in
chimney
-
-
Frequent relief valve
intervention
- Check circuit pressure
- Check expansion vessel
-
-
Limited production of
domestic hot water
- Check the diverter valve
- Check that plate heat
exchanger is clean
- Check domestic hot
water circuit valve
Summary of Contents for BRAVA SLIM 30 BFR
Page 4: ...4 ...
Page 46: ...46 12 EXPLODED VIEWS Brava Slim 30 BFRi ...
Page 47: ...47 Brava Slim 30 BFRe ...
Page 48: ...48 Brava Slim 30 BFRi Brava Slim 30 BFRe ...
Page 49: ...49 Brava Slim 30 BFRi Brava Slim 30 BFRe ...
Page 56: ...56 ...
Page 57: ...57 ...
Page 58: ...58 ...
Page 59: ...59 ...