Heating circuit:
– open the isolation and air bleeding valves in the highest points
of the system
– loosen the automatic bleed valve (3)
– open the isolation valves of the heating circuit (if present)
– Open the filling valve, which should be on the system return
– Fill until the water overflows from the air bleeding valves and
shut off the valves again
– Continue filling until the pressure reaches
1-1.2
bar (100-120
kPa) as shown on the display
– close the filling valve
– check that there is no air in the system by bleeding all the
radiators and the circuit on the high points of the system
– remove the front plug (6) of the pump and use a screwdriver
to check that the impeller is not blocked
– replace the plug (6)
6
3
Fig. 39
NOTE:
to completely remove all air from the system, it is
recommended that this operation is repeated a number of times.
– check the pressure on the display and if necessary top up until
the correct pressure reading appears
– close the automatic bleed valve (3).
Refit the front panel of the boiler hooking it on at the top,
pushing it forwards and securing it with the screw (1) which was
removed previously.
Fit the smoke outlet duct of the
Brava Slim 30 BFRe
.
8.13.2 EMPTYING operations
Boiler:
– loosen the automatic bleed valve (3)
– close the heating circuit isolation valves
– check that the filling valve is closed
– connect a rubber hose to the boiler drain valve (7) and open it
– when it has fully emptied, close the drain valve (7)
– close the automatic bleed valve (3).
7
3
Fig. 40
Summary of Contents for BRAVA SLIM 30 BFR
Page 4: ...4 ...
Page 46: ...46 12 EXPLODED VIEWS Brava Slim 30 BFRi ...
Page 47: ...47 Brava Slim 30 BFRe ...
Page 48: ...48 Brava Slim 30 BFRi Brava Slim 30 BFRe ...
Page 49: ...49 Brava Slim 30 BFRi Brava Slim 30 BFRe ...
Page 56: ...56 ...
Page 57: ...57 ...
Page 58: ...58 ...
Page 59: ...59 ...