Electrical wiring
7.7.3
Shut-down test
Sequence for shut-down test programming
➤
Programming allowed in OPERATING mode and in STAND-
BY.
➤
Press button for 5 sec.
≤
t < 10 sec.
➤
RED led Blinking 2 times (0.2s. ON; 0.2s. OFF).
➤
Release the button.
➤
The burner will begin a shut-down, followed by a restart.
After shut-down, the burner restarts automatically and the no. of
attempts of recycle are restored.
At the exit of shut-down test page menu there are no blinking led.
7.7.4
Post-purging
The post-purging time can be set for a maximum of 120 sec-
onds, proceeding as follows:
Sequence for post-purging programming
➤
Programming allowed in OPERATING mode and in STAND-
BY.
➤
Press button for 10 sec.
≤
t < 15 sec.
➤
GREEN led blinking 1 time
➤
Release the button
➤
GREEN led OFF
➤
Press the button from 1 - 5 times (*)
➤
GREEN led ON and OFF every time press and release
➤
After 10 sec. GREEN led blinking for the programmed times
(0.5s. ON; 0.5s. OFF)
Sequence for disable post-purging
➤
Reset allowed in OPERATING mode and in STAND-BY.
➤
Press button for 10 sec.
≤
t < 15 sec.
➤
GREEN led blinking 1 time
➤
Release the button
➤
GREEN led OFF
➤
Press the button 6 times (*)
➤
GREEN led ON and OFF every time press and release
➤
After 10 sec. GREEN led blinking for 6 times previously pro-
grammed (0.5s ON; 0.5s OFF)
If heat request stops during programming of post-purging
function, occur exit menu without save the setting value.
If heat request stops during the led blinking occur exit
menu, but the setting value is stored.
7.7.5
Intermittent operation
Sequence for enable/disable
➤
Programming allowed in OPERATING mode and in STAND-
BY.
➤
Press button for 20 sec.
≤
t < 25 sec.
➤
GREEN led blinking 3 times
➤
Release the button
➤
GREEN led OFF
➤
Press the button once to disable the function (*)
➤
Press the button 2 times to enable a shut-down every hour
(*)
➤
Press the button 3 times to enable a shut-down every hour
24 hours (*)
➤
GREEN led ON and OFF every time press and release
➤
After 10 sec. GREEN led blinking for the programmed times
(0.5s. ON; 0.5s. OFF).
The modification of the parameter setting for Intermittent opera-
tion takes effect:
➤
after the next heat request by the thermostat (HT)
➤
after the activation of a switch-off test
➤
after flame disappearance during operation
➤
after disconnecting and reconnecting the electrical supply
7.7.6
Displaying the last lockout that occurred
The control box allows the last lockout that happened and is
memorised to be displayed, by accessing “Programming
menu” a pag. 22.
Access to this page is possible both in STAND-BY, as well as in
the OPERATING status.
Display sequence of the last lockout that occurred
➤
Keep the button pressed for 25 sec. = t < 30 sec.
➤
The GREEN led blinks 4 times.
➤
Release the button.
➤
Displaying the type of lockout memorised for 10 sec.
The time displaying the type of lockout can be extended by re-
pressing the reset button during the display of the lockout (the
lockout display continues for another 10s).
NOTE:
(*) Always wait 1 sec. with each pressing and release of the
button to ensure the command is logged correctly.