Electrical wiring
20123476
22
GB
7.7
Programming menu
7.7.1
General notes
The programming menu can be accessed via the integrated reset
button during OPERATION and in STAND-BY.
If in page menu the reset button is not pressed within 10 seconds
the page will be automatically be exited and there will be a green
led blinking for the time set.
If the number of presses on the reset button exceeds the maxi-
mum allowable, the value that stays in memory will be the maxi-
mum one.
If the reset button is pressed for more than 60 seconds, a button
error will be displayed and the control-box will restart.
7.7.2
Block diagram for entering the menu
Tab. G
Function
Button release
time
No. of blinks of
the led per
menu page
No. of pressings
of the reset button
No. of blinks of
the
Led (green)
Quitting the menu
Shut-down test
5s
≤
t < 10s
2 blinks
RED
/
none
/
none
Automatic, at the
end of the blink
Post-
purging
10s
≤
t < 15s
1 blink
GREEN
1 = 10 sec.
2 = 20 sec.
3 = 30 sec.
4 = 60 sec. (default)
5 = 120 sec.
6 = 0 sec. (deactivated)
1 blink
2 blinks
3 blink
4 blinks
5 blinks
6 blinks
10 sec. after the release of
the button
Intermittent
operation
20s
≤
t < 25s
3 blinks
GREEN
1 = 0 disabled
2 = 1 hour
3 = 24 hours (default)
1 blink
2 blinks
3 blinks
10 sec. after the release of
the button
Last lockout
memorised
25s
≤
t < 30s
4 blinks
GREEN
/
none
Display of the lock-
out type; see para-
graph “Fault
diagnostics - lock-
outs” on page 19
10 sec. after the release of
the button
S9510
OPERATION (WITH FLAME) AND STAND-BY
OPERATION
TEST
POST
INTERMITTENT
2 RED
1 GREEN
3 GREEN
OUTLET
AUTOMATIC
10 SEC. AFTER
RELEASE
10 SEC. AFTER
RELEASE
SWITCHING OFF
PURGING
20 SEC.
LAST LOCKOUT
MEMORISED
25 SEC.
4 GREEN
10 SEC. AFTER
RELEASE
5 SEC.
10 SEC.
BURNER STATE
TYPE OF
FUNCTION
NUMBER
OUTLET
BLINKS
Fig. 18
RELEASE
TIME
BUTTON