007-4243-002
1
Chapter 1
1.
VBOB Site Preparation and Specifications
The VBOB is shipped ready for rackmounting or it can be used as a table-top unit.
See Chapter 2, “Rackmounting and Hardware Overview” for information on mounting
a VBOB chassis in an SGI 3000 series rack.
Site Preparation
Table 1-1 provides site preparation information for a single VBOB chassis.
Table 1-1
Cooling and Power Requirements
Specification
Value Per Server
Cooling requirements
256 Btu/hour
Power consumption
128 watts maximum
AC input to power supply
100-120/200-240 Vac at 50-60 Hz, 4/2A (autoranging)
Inrush current
5 amps maximum
Nominal current draw
0.8 amps @ 100-120 Vac, 0.4 amps @ 200 -240 Vac
UPS volt-amp rating
250 VA