Functional Description
AP10S
Date: 12.05.2020
Art. No. 90304
Mod. status 110/20
Page 18 of 44
3.3.1.9
Device options
The following parameters can be set in the "Additional device options" menu:
Description
Display
Chapter
SENSOR
K TIME
K CAL
K INC
OPMODE
PIN
LOAD P
CODE
Table 12: "Additional device options" menu
3.3.2
Parameterization via interface
The position indicator can be completely parameterized in the IO-Link interface
(see chapter
3.4
Calibration
Calibration is only possible if the chain dimension is not active and the
actual value is not 0.
Two steps are required for executing calibration:
Write calibration value: Parameter CalibrationValue (see chapter
Execute calibration (using operating keys, see chapter
Since the measuring system is an absolute system, calibration is necessary only once with
commissioning. With calibration, the CalibrationValue is adopted for calculation of the actual
value. The following equation is applied in case (time) of calibration:
Actual value =
ActualValue
= 0 + CalibrationValue