Display 3:
Level
Parameter
Note
1
Operating mode
1: A and B at a measuring chamber, possibility of return identification.
2: A + B (measurement of the total volume).
3: A - B (measurement of the difference = consumption measurement).
2
Volume unit
Selection of the volume unit. When "mass" unit, then calculation of the
density
3
Time unit
Conversion of the flow rate into the selected time unit.
4
Digits after the deci-
mal point Q
Number of digits after the decimal point for Q display: 0 to 3 digits pos-
sible
5
Digits after the deci-
mal point V1 + V2
Number of digits after the decimal point for V1+V2 display: 0 to 3 digits
possible
6
K-factor A
Unit: Pulses per litre. This factor is used for sensor A
12
K-factor B
Unit: Pulses per litre. This factor is used for sensor B.
13
Density in kg/m³
Density at 20°C.
14
Medium temperature Display of current sensor temperature. Without sensor: 20
℃
Can be updated via the “
►
” key
23
Alpha value
[kg/m³/°C]
Without temperature sensor: No function.
With temperature sensor: Factor for density correction.
24
Pulse output scaling 0: Original pulses of sensor A. (pulse duration original pulses: 4ms).
1: 1 pulse per change of the right-hand position of V1 (right).
2: 1 pulse per change of the second position … .
25
Pulse duration
Pulse duration. Period duration = 2x pulse duration. [4, 12, 24, 48, 100].
34
Gate time flow display Period of time which the meter waits before updating the flow display.
35
Attenuation factor
Determination of the mean value via the last 1, 2, 4 or 8 mean values.
36
Total volume meter
reset
Resetting the main meter after changing the value from “0” to “1”
45
Max. frequency
Display of the maximum recorded frequency (drag indicator function)
46
Not used
56
Software version
Display of the available software version.
123
Current output lower
range value
Flow rate of the selected unit which outputs a current of 4mA. Decimal
point as for level 4
124
Current output upper
range value
Flow rate of the selected unit which outputs a current of 20 mA. Decimal
point as for level 4
125
Current simulation
0.00: Off, all other values between 4.00 and 20.00 result in a simulated
current output.
146
Password
Password can be entered and changed for programming protection.
0000 = off