2 of 12
ÐSIGNET
5600 Batch Controller
Technical Notes:
• Maximum alarm contact ratings: 5 A @ 30 VDC, 5 A @ 125
VAC, or 3 A @ 250 VAC
• To reduce the possibility of noise interference, isolate AC power
lines from signal lines.
7. Option Contact Wiring Options
A. Two Stage Shutdown
(advanced mode only, sec. 9.2)
8. Current Output Wiring Options
A. Batch Completion
(simple or advanced mode, sec. 9)
B. Valve Control
(advanced mode only, sec. 9.2)
Technical Notes:
• Output compatible with the following George Fischer electronic
actuators/PE 22P positioner models: EA 20, EA 30, EA 41
and EA 50
flow
to tank
Bypass line
Main line
AC or DC
power
NC
C
NO
NC
C
NO
Batch
Option
Valve
5600
Terminals
-
+
Current
output
-
+
4 - 20 mA
5600
Terminals
Fuse**
1/8A
*
-
+
Current
output
#6 ( - )
4 - 20 mA
George Fischer electronic
actuator
with PE 22P
positioner
required
#5 ( + )
5600
Terminals
B. Missing Signal Alarm
(simple or advanced mode, sec. 9)
OR
Overrun Alarm
(advanced mode only, sec. 9.2)
AC or DC
power
Alarm
device
NC
C
NO
NC
C
NO
Batch
Option
5600
Terminals
Technical Notes:
• Maximum alarm contact ratings: 5 A @ 30 VDC, 5 A @ 125
VAC, or 3 A @ 250 VAC
• To reduce the possibility of noise interference, isolate AC power
lines from signal lines.
+
Gnd
CNT/EOB
output
External
Counter
Gnd
IN
5 - 30
VDC
-
+
10 k
Ω
Rsm
RTN
Start
Stop
Remote
+
Gnd
CNT/EOB
output
First 5600
Second 5600
B.
Daisy chaining two 5600
batch controllers together
A.
External counter connection
5600
Terminals
Technical Notes:
• Use 2-conductor
shielded twisted-pair
cable for output lines
up to 30 m (100 ft.) max.
6. End of Batch/Counter Pulse Output Wiring
See section 9 for simple and advanced mode configuration
options.
Start
Stop
Resume
Rsm
RTN
Start
Stop
Remote
Momentary Switch Contacts
(customer supplied)
5600
Terminals
Technical Notes:
•
Use 4-conductor
shielded
cable for remote control lines up to
30 m (100 ft) max.
5. Remo)te Control Wiring
Rear START, STOP, and RESUME
(Rsm) terminals can provide remote
batch control from a distance using
one of four methods:
• Mechanical switch closures (shown)
• End of batch pulse from a second
5600 (sec. 6)
• End of batch contact closure from a
second 5600 (sec. 7C).
• End of batch current pulse from a
second 5600 (sec. 8C).
Technical Notes:
**1/8A fuse recommended (customer supplied)
* 4-20 mA output is
internally powered
(non-isolated),
maximum loop impedance 350 ý with a 12 V instrument supply
voltage, 950 ý with a 24 V instrument supply voltage.
To isolate output and prevent ground loop problems:
1. Use monitor device with isolated inputs, or
2. Use separate DC supply for 5600 and monitor device, or
3. Power 5600 with 12 - 24 VAC step down transformer