5600 Batch Controller

10.3  Auto Calibration Procedure

The auto calibrate procedure (sec. 10.2C) calculates a custom flow sensor/batch K-Factor based on volumetric measurement for more
precise batching.  This process will compensate for installation abnormalities or nonstandard pipe sizes for maximum batch accuracy.
An accurate measurement reference container (e.g. known tank volume) is required for this procedure.  If auto calibration is impractical
for your batch system, perform manual calibration using the K-Factors published in your flow sensor manual.

Requirements:

A. The flow sensor must be installed in the actual batch pipeline.
B. The flow control valve can be connected to the common (C)

and normally open (NO) batch contact terminals (sec. 4) or
the current output terminals (sec. 8B).

C. Either the batch contact or current output

 

MUST

 

be used to

energize and de-energize the main flow control valve which
starts and stops fluid flow into the known reference container.

D. Follow the steps outlined in the auto calibration procedure

(sec.10.2C) to obtain your batch system's custom K-Factor.

   Batch K-Factor
       1234.3

C.

Modify 

K-Factor?

   Auto Cal Volume:
   XX.XXX   Gallons

   Batch K-Factor:
       1234.5

B.

Accept 

K-Factor?

   Auto Calibrate:
 <ENTER> to Stop

CALIBRATE: -- -- -- --
Enter Key Code

Press keys in sequence   

 

         to continue,

****  will appear during code entry.

     Batch Units:
        Gallons      >

A.

B.

C.

Batch

   Flow Timebase:
           m           >

Choose:

1

Change:

2

Save:

3

Set batch units:  
Aa - Zz, 0 - 9, 
/, _ 

Batch units

Set timebase:
S=seconds, 
M=minutes, 
H=Hours, 
D=Days

Flow timebase

  Auto Calibrate:
  Batch K-Factor   >

   Auto Calibrate:
 <ENTER> to Start

Auto Calibrate

Procedure

Accurate reference 

container required.  

See procedure

(sec. 10.3)

Start

Stop

ENTER

ENTER

ENTER

Save

S

ave

Enter volume

A.

Reenter

volume?

     Batch Units:
         Liter

   Flow Time Base:
  s S m M h H d D

ENTER

D.

   Batch K-Factor:
        60.000    >

Set batch 
K-Factor:
0.0001 - 99999. 
(see note*)

Batch K-Factor

G.

Last CAL:  Sets user
defined date

Last calibration

E.

Set totalizer 
units: Az - Zz, 
0 - 9, /, _
(Label use only)

Totalizer units

       Total Units:
     Gallons  x 1  >

      Last CAL:
      01-01-98

      Total Units:
     Liters  X100

      Last CAL:
      01-01-98

   Batch K-Factor:
     3456.7

To return 
to VIEW:

To restore original value:

quick 

press

quick 

press

To return 
to VIEW:

To restore original value:

quick 

press

quick 

press

To step A

To step D

 

Back to step C

F.

Set totalizer 
K-Factor:
0.0001 - 99999. 
(see note*)

Totalizer K-Factor

    Total K-Factor:
        60.000     >

     Total K-Factor:
        3456.7

  Overrun Volume: 
  XX.XXX Gallons

D.

  Overrun comp.

     Display shown only 

when advanced mode 

(sec.10.4E) and manual 

overrun comp. (sec.10.4G)

is selected.

OR

Cancel

ENTER

ENTER

G

ENTER

"SAVING"

briefly

displays

"SAVING"

briefly

displays

10.2  CALIBRATE Menu

 

(factory defaults shown in menu column 1)

*Note:

 

 Batch and totalizer K-Factor settings represent the

number of pulses generated by the +GF+ SIGNET flow sensor for
each engineering unit of fluid measured (published in the flow
sensor manual).

WARNING!

The auto calibration procedure generates a custom batch K-Factor.  The batch and Totalizer K-Factors are independent from
one another.  ALWAYS reenter your totalizer K-Factor after performing the auto calibration procedure.

5600

Flow Sensor

Flow control valve

20 

40 

60 

80 

100 

Batch contact terminals (sec. 4) OR
4-20 mA valve control terminals (sec. 8B)

Reference Container

EN TER

Batch %

Batch

Option

0

20

40

60

80

100

+GF+ SIGNET

Summary of Contents for GF 5600

Page 1: ...mpedance sec 8A is affected by the supply voltage To reduce the possibility of noise interference isolate AC power lines from signal lines Double Insulated DC or AC power Contents 1 Wiring terminals 2 Power Connection 3 Compatible Sensor Wiring 4 Batch Contact Wiring 5 Remote Control Wiring 6 End of Batch Counter Pulse Output Wiring 7 Option Contact Wiring Options Technical Notes To reduce the pos...

Page 2: ... EOB output External Counter Gnd IN 5 30 VDC 10 kΩ Rsm RTN Start Stop Remote Gnd CNT EOB output First 5600 Second 5600 B Daisy chaining two 5600 batch controllers together A External counter connection 5600 Terminals Technical Notes Use 2 conductor shielded twisted pair cable for output lines up to 30 m 100 ft max 6 End of Batch Counter Pulse Output Wiring See section 9 for simple and advanced mod...

Page 3: ...on sec 8A This function is offered in the simple or advanced operation mode The output is a linear increase from 4 mA at batch start to 20 mA at batch end 9 2 Advanced Operation Mode Batch Contact sec 4 The batch contact is dedicated for on off control and is either manually or automatically compensated for batch overrun Manual overrun compensation allows the operator to compensate for valve closu...

Page 4: ... batch start up An adjustable time delay entry in seconds is offered which specifies how long the instrument will wait after batch start up before initiating the missing signal alarm See simple operation mode sec 9 1 for alarm operation details Option Contact On Off sec 10 4H This function enables or disables the option contact and front panel option LED When the option contact is configured Off t...

Page 5: ...t 1 min ENTER to Stop 10 Menu Functions Note BATCH VIEW Menu steps B E MUST be selected for CALIBRATE Menu sec 10 2 or OPTIONS Menu sec 10 4 access OPTIONS CALIBRATE VIEW 2s 5s Press hold for access ENTER 10 1 BATCH VIEW Menu example Menu steps B E cannot be accessed when a batch is running Press ENTER to stop batch cycle Steps B E MUST be selected for CALIBRATE Menu sec 10 2 or OPTIONS Menu sec 1...

Page 6: ...ctor Auto Calibrate ENTER to Start Auto Calibrate Procedure Accurate reference container required See procedure sec 10 3 Start Stop ENTER ENTER ENTER Save Save Enter volume A Reenter volume Batch Units Liter Flow Time Base s S m M h H d D ENTER D Batch K Factor 60 000 Set batch K Factor 0 0001 99999 see note Batch K Factor G Last CAL Sets user defined date Last calibration E Set totalizer units Az...

Page 7: ...Alarm 1 00000 Gallons Set overrun alarm volume 0 00001 999999 Option Contact Overrun Alarm 0002 50 Gallons Overrun Alarm mode selected Missing Signal Alarm On Missing signal alarm On or Off Option Contact Missing Signal Alarm Off On Two Stage Overrun Alarm End of Batch or Off mode selected ENTER SAVING briefly displays Option Contact End of Batch End of Batch Option Contact Two Stage Two Stage Opt...

Page 8: ...ading Input Optically isolated Enclosure Rating NEMA 4X IP65 front Dimensions 1 4 DIN 96 x 96 x 88 mm 3 8 x 3 8 x 3 5 in Case materials ABS plastic Keypad material Sealed 4 key silicone rubber Weight Approximately 500 g 18 oz Display Type Microprocessor controlled air core meter movement and alphanumeric 2 x 16 LCD Update rate 200 ms Contrast User selected Alarm annunciators green batch LED left r...

Page 9: ...24 V 10 W GF SIGNET Model 3 5600 Rsm RTN Gnd Start Stop Remote CNT EOB output Current output Dimensions 13 Quick Reference Menu Parameters 13 1 VIEW Menu Setup Parameters sec 10 1 Menu Parameters Factory Default Range Display Description Press ENTER to start stop or resume batch Programmed batch volume Resettable totalizer Permanent totalizer Overrun mode Overrun volume See programmed batch volume...

Page 10: ... Batch Count up or down 3 Off Advanced Totalizer Manual 0 00000 Gallons Missing signal 95 0 1 00000 Gallons On 0 10 seconds Batch Completion Count up A B C D E F G H I J K Contrast 3 Total Decimal Lock OFF Operating Mode Advanced Pulse Output Totalizer Display Decimal Option Contact Missing Signal Current Output BatchCompletion Two Stage Setpoint 95 0 Missing Signal Delay 30 0 sec Count Direction ...

Page 11: ... 10 2D can not be zero be zero Total K Factor Totalizer K Factor can not be Enter K Factor greater than zero sec 9 2E can not be zero zero Must be between Missing signal time delay must be se Enter missing signal time delay within 0 10 999 seconds sec 10 4I 0 10 999 for 0 10 999 seconds Overrun Volume Overrun alarm volumetric setting Enter overrun alarm volumetric setpoint within 0 00100 999999 ca...

Page 12: ...nue El Monte CA 91731 2882 U S A Tel 626 571 2770 Fax 626 573 2057 For Worldwide Sales and Service visit our website www gfsignet com Or call in the U S 800 854 4090 GEORGE FISCHER Piping Systems 3 5600 090 1 D 6 03 English Signet Scientific Company 2001 Printed in U S A on recycled paper ...