8350-1 Temperature Transmitter

5

Output Setpnt:

  2

0.00 

°

C  

Output Setpnt:

1

0.00 

°

C

ENTER

Output Setpnt:

   1

0

.00 

°

C  

Output Setpnt:

   1

9

.00 

°

C  

Output Setpnt:

Saving

Output Setpnt:

   19.00 

°

C   >

    

Notes on Steps 5 and 6:

•  All output functions remain active during editing.
•  Only the 

fl

 ashing element can be edited.

•  

 key advances the 

fl

 ashing element in a continuous loop.

•  Edited value is effective immediately after pressing ENTER key.
•  If no key is pressed for 10 minutes unit will restore the last saved value and return to step 3.
•  Step 6 (pressing ENTER key) always returns you to Step 3.
•  Repeat steps 3-6 until all editing is completed.

Notes on Step 2:

If no key is pressed for 5 minutes while display is showing "Enter 
Key Code", the display will return to the VIEW menu.

Notes on Steps 3 and 4:

•  Refer to pages 6 and 7 for complete listing of menu items and their use.
•  From the Step 3 display, pressing the 

 and 

 keys simultaneously will return 

the display to the VIEW menu.
•  If no key is pressed for 10 minutes, display will also return to the VIEW menu.

ProcessPro Editing Procedure:

Step 1.  

Press and hold ENTER:

 

 

•  2 seconds to select the CALIBRATE menu

 

 

•  5 seconds to select the OPTIONS menu.

Step 2.

  The Key Code is 

-

-

-

 keys in sequence.

 

 

•  After entering the Key Code, the display will show the 

fi

 rst item in the selected menu.

Step 3.

  Scroll menu with 

 or 

 arrow keys.

Step 4.  

Press 

 to select menu item to be edited.

  • 

 

The 

fi

 rst display element will begin 

fl

 ashing.

Step 5.

  Press 

 or 

 keys to edit the 

fl

 ashing element.

 

 

• 

 advances the 

fl

 ashing element.

Step 6. 

 Press ENTER to save the new setting and return to Step 3.

2s

5s

ENTER

OPTIONS

CALIBRATE

VIEW 

Press & 
hold for  
access: 

Step 5

Step 6

Notes on Step 1:

•  The View Menu is normally displayed.
•  The CALIBRATE and OPTIONS menus require a KEY CODE.

Step 4

First item in
CALIBRATE menu

Step 3

Step 3:  Finished Editing?

Press the 

 and 

 keys simultaneously after saving 

the last setting to return to normal operation.

Press the 

 and 

 keys simultaneously while 

any element is 

fl

 ashing. This will recall the last 

saved value of the item being edited and return 
you to Step 3.

Step 5: Made an Error?

CALIBRATE: ----

Enter Key Code

CALIBRATE: *---

Enter Key Code

CALIBRATE: **--

Enter Key Code

CALIBRATE: ***-

Enter Key Code

    

°

  >

Temp Units:

 20.0 

°

C  >

Output Setpnt:

   

°

C  

>

Temp Units:

Summary of Contents for 8350-1

Page 1: ...evels Electrical Power 12 to 24 VDC 10 regulated 21 mA max current Current output 4 to 20 mA isolated fully adjustable and reversible Max loop impedance 50 Ω max 12V 325 Ω max 18V 600 Ω max 24V Update rate 200 ms Output accuracy 0 03 mA Open collector output Optically isolated 50 mA max sink 30 VDC maximum pull up voltage Programmable for High Low with adjustable hysteresis Pulse operation maximum...

Page 2: ...d remove Outp ut Outp ut Syst em Pwr Loop Syst em Pwr Loop 2 1 4 3 Sens r Gnd SHI ELD Sens r IN RED Sens r V BLA CK 7 6 5 quick clips gasket panel terminals mounting bracket latch Panel Mount Installation Detail 3 Electrical Connections Caution Failure to fully open terminal jaws before removing wire may permanently damage instrument Wiring Procedure 1 Remove 0 5 0 625 in 13 16 mm of insulation fr...

Page 3: ... 12 24 VDC PLC or Recorder PLC Terminals Power Supply 12 24 VDC Power Supply 12 24 VDC Stand alone application no current loop used Connection to a PLC with built in power supply Connection to a PLC Recorder separate supply Example Two transmitters connected to PLC Recorder with separate power supply Transmitter Terminals Transmitter 1 Terminals Transmitter 2 Terminals Transmitter Terminals 7 6 5 ...

Page 4: ...resis Time High Setpoint Process 10 5 O p e n C o l l e c t o r O u t p u t R a t e 0 t o 1 0 0 P u l s e s m i n endpoint Pulse rate 0 pulses 100 pulses Starting point View Menu 3 3 Open Collector Output The Open Collector output can be used as a switch that responds when the process value moves above or below a setpoint or it can be used to generate a pulsing signal with a rate proportional to t...

Page 5: ... VIEW menu ProcessPro Editing Procedure Step 1 Press and hold ENTER 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with or arrow keys Step 4 Press to select menu item to be edited The first display element will begin flashing ...

Page 6: ... Off if not used Output Setpnt 25 0 C In Low or High Mode the Open Collector output will be activated when the temperature reaches this value Be sure to modify this setting if you change the Temperature Units Output Hys C The Open Collector output will be de energized at Setpoint Hysteresis depending on High or Low Setpoint selection Output Range 25 0 45 0 If the output is in PULSE mode set the st...

Page 7: ...Low Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active LOW This setting is used to turn a device OFF at the setpoint Loop Adjust 4 00 mA Adjust the minimum and maximum current output Use this setting to match the system output to any external device The display value represents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 m...

Page 8: ...er kit for relay use 3 0000 596 159 000 641 Heavy duty wall mount bracket 3 5000 598 198 840 225 Surface Mount Bracket 3 9000 392 159 000 368 Liquid tight connector kit for rear cover includes 3 connectors 3 9000 392 1 159 000 839 Liquid tight connector kit NPT 1 piece 3 9000 392 2 159 000 841 Liquid tight connector kit PG13 5 1 piece 3 9900 396 159 001 701 Angle Adjustment Adapter Kit Display Con...

Reviews: