8350-1 Temperature Transmitter

Temperature

27.9 ºC

ENTER

Signet Temperature

Transmitter

•  During normal operation, ProcessPro displays the VIEW menu.
•  When editing CALIBRATE or OPTIONS menus, ProcessPro returns to the VIEW menu if no activity occurs for 

10 minutes.

•  To select a VIEW display, press the 

 or 

 keys. The selections will scroll in a continuous loop.

•  Changing the display selection does not interrupt system operations.
•  No key code is necessary to change display selection.
•  Output settings cannot be edited from the VIEW menu.

• Proportional Pulsing

The Open Collector output will generate a 100 mS pulse at the 
rate de

fi

 ned by settings in the CALIBRATE menu (see page 6).

In the example below:
•  The output will be 0 pulses/min. at temperatures less than 5º.
•  The output will be 50 pulses/min. at 7.5º.
•  The output will be 100 pulses/min. at temperatures above 10º.

The starting point, endpoint and maximum pulse rate are 
selectable in the menu.

Hysteresis 

Time 

Low Setpoint 

Process 

Relay energized

Relay de-energized

Hysteresis 

Time 

High Setpoint

Process

10

5

Open Collector Output Rate:

0 to 100 Pulses/min.

endpoint

Pulse rate

0 pulses

100 pulses

Starting point

View Menu

3.3  Open Collector Output

The Open Collector output can be used as a switch that responds 
when the process value moves above or below a setpoint, or it 
can be used to generate a pulsing signal with a rate proportional 
to the process value. The output can be disabled when not in use.

• Low:

Output energizes when process variable is less than the setpoint. 
The output de-energizes when the process variable moves above 
the setpoint plus the hysteresis value.

• High:

Output energizes when process variable is greater than the 
setpoint. The output de-energizes when the process variable 
moves below the setpoint plus the hysteresis value.

Display

Description

Temperature:

27.9 °C

Monitor the temperature input from the sensor.
This is the permanent display.

The displays below are temporary. After 10 minutes the display returns to the permanent display.

Loop Output:

12.00 mA

Monitor the 4 to 20 mA Loop output.

Last CAL:

02-10-09

Monitor date for scheduled maintenance or date of last calibration.
(See description in Calibrate Menu.)

4. Menu 

Functions

Summary of Contents for 8350-1

Page 1: ...evels Electrical Power 12 to 24 VDC 10 regulated 21 mA max current Current output 4 to 20 mA isolated fully adjustable and reversible Max loop impedance 50 Ω max 12V 325 Ω max 18V 600 Ω max 24V Update rate 200 ms Output accuracy 0 03 mA Open collector output Optically isolated 50 mA max sink 30 VDC maximum pull up voltage Programmable for High Low with adjustable hysteresis Pulse operation maximum...

Page 2: ...d remove Outp ut Outp ut Syst em Pwr Loop Syst em Pwr Loop 2 1 4 3 Sens r Gnd SHI ELD Sens r IN RED Sens r V BLA CK 7 6 5 quick clips gasket panel terminals mounting bracket latch Panel Mount Installation Detail 3 Electrical Connections Caution Failure to fully open terminal jaws before removing wire may permanently damage instrument Wiring Procedure 1 Remove 0 5 0 625 in 13 16 mm of insulation fr...

Page 3: ... 12 24 VDC PLC or Recorder PLC Terminals Power Supply 12 24 VDC Power Supply 12 24 VDC Stand alone application no current loop used Connection to a PLC with built in power supply Connection to a PLC Recorder separate supply Example Two transmitters connected to PLC Recorder with separate power supply Transmitter Terminals Transmitter 1 Terminals Transmitter 2 Terminals Transmitter Terminals 7 6 5 ...

Page 4: ...resis Time High Setpoint Process 10 5 O p e n C o l l e c t o r O u t p u t R a t e 0 t o 1 0 0 P u l s e s m i n endpoint Pulse rate 0 pulses 100 pulses Starting point View Menu 3 3 Open Collector Output The Open Collector output can be used as a switch that responds when the process value moves above or below a setpoint or it can be used to generate a pulsing signal with a rate proportional to t...

Page 5: ... VIEW menu ProcessPro Editing Procedure Step 1 Press and hold ENTER 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with or arrow keys Step 4 Press to select menu item to be edited The first display element will begin flashing ...

Page 6: ... Off if not used Output Setpnt 25 0 C In Low or High Mode the Open Collector output will be activated when the temperature reaches this value Be sure to modify this setting if you change the Temperature Units Output Hys C The Open Collector output will be de energized at Setpoint Hysteresis depending on High or Low Setpoint selection Output Range 25 0 45 0 If the output is in PULSE mode set the st...

Page 7: ...Low Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active LOW This setting is used to turn a device OFF at the setpoint Loop Adjust 4 00 mA Adjust the minimum and maximum current output Use this setting to match the system output to any external device The display value represents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 m...

Page 8: ...er kit for relay use 3 0000 596 159 000 641 Heavy duty wall mount bracket 3 5000 598 198 840 225 Surface Mount Bracket 3 9000 392 159 000 368 Liquid tight connector kit for rear cover includes 3 connectors 3 9000 392 1 159 000 839 Liquid tight connector kit NPT 1 piece 3 9000 392 2 159 000 841 Liquid tight connector kit PG13 5 1 piece 3 9900 396 159 001 701 Angle Adjustment Adapter Kit Display Con...