3. Installation
•
The sensor may be installed in any position,although
horizontal fl ow is recommended (the sensor mounted upright).
If the sensor is not installed upright, the linearity error may be
greater in the lower part of the sensor's measurement range.
•
Mounting tabs are provided using M4 or #8 self-tapping
screws (customer supplied). See Dimensions illustration for
mounting tab hole pattern specifi cations.
•
Install sensor with the arrow pointing in the direction of fl ow.
•
Always maximize distance between the sensor and pump
source. Never install immediately downstream of valves,
fi ttings, etc. For optimum performance, a straight fl ow run of
at least 100 mm to 150 mm (4 to 6 in.) should be provided
before and after the sensor.
• Two
pipe
fi tting adapters (included) convert the G 1/4 in.
straight threads to 1/4 in. NPT pipe threads. Hand tighten
only! Apply 1-2 turns of PTFE sealing tape to all threaded
connections to prevent leaks..
Installation Hints
•
Avoid vibrations and shocks.
•
Avoid solids in the fl uid.
• Install
a
fi lter or line strainer upstream to protect sensor.
1
2
Sensor
Ground
(silver wire)
Sensor Power:
5 to 24 VDC
(black wire)
Sensor Signal Output
(Red wire)
Max cable length:
300 m (1000 ft)
Sensor
Plug (side)
Disregard ground
symbol on connector
95 mm
65 mm
FLOW
FLOW
68 mm
4. Wiring
Details
Cable Extensions
• 2507
fl owmeters distributed in the U.S. include 7.6 m (25 ft)
of
cable.
The cable can be extended to 300 m (1000 ft).
•
Always maintain cable shield through cable splice.
• 2507
fl owmeters distributed in Europe do not include cable.
Refer to the sensor plug connection diagram (at right) for
connection details.
FLOW
100 to 150 mm (4 to 6 in.)
100 to 150 mm (4 to 6 in.)
FLOW
Pipe Fitting
Adapters
(included)
Hand
tighten
only!
Coupling
Pipe or
tubing
Mounting
tabs (3)
Sensor Plug Connection Diagram