SIGMATEK FDD Step By Step Guide Size 5 to 9
5
Eng
D
STEP 4: Select supply / motor cables and fuses
The supply/motor cables and fuses or MCB’s used should follow the ratings provided in the table below:
*
These fuses are fast acting.
**
These fuses are class gR.
***
These fuses are class HSJ.
The voltage rating of fuses must be greater than or equal to the highest supply voltage of the system.
Fuses
: The AC supply to the drive must be installed with suitable protection against overload. Failure
to observe this requirement will cause risk of fire.
Model
Maximum
continuous
input
Fuses
Cables
IEC Class
UL
IEC60364-5-52
UL 508C
A
A
A
Input
Output
Input
Output
05200250
31
40
40
10
8
06200330
48.8
63
60
16
4
06200440
56.6
63
70
25
3
05400270
29
40
35
6
8
05400300
29
40
35
6
8
06400350
36
63**
40
10
6
06400420
46
63**
50
16
4
06400470
60
63**
70
25
3
07400660
74
100
80
35
1
07400770
88
100
100
50
2
07401000
105
125
125
70
1/0
08401340
155
250**
225***
2 x 50
2 x 1
08401570
177
250**
225***
2 x 70
2 x 1/0
09402000
232
315**
300***
2 x 70 (B1)
2 x 95 (B2)
2 x 3/0
2 x 2/0
09402240
267
315**
350***
2 x 95 (B1)
2 x 120 (B2)
2 x 4/0
The product is UL listed for use on a circuit up to 100 kA maximum supply symmetrical fault current,
when protected by fuses.
IEC cable sizes assume Copper conductor, PVC insulation, Installation method B2 and ambient
temperature of 40 °C (104 °F). UL cable sizes assume Copper conductor with insulation rated at 75 °C
(167 °F).
WARNING
NOTE
NOTE