    SIGMATEK FDD Step By Step Guide Size 5 to 9

Appendix A UL listing information

A.1   UL file reference

All models are UL Listed to both Canadian and US requirements. 
Products that incorporate the Safe Torque Off function have been investigated by UL. 

A.2   Option modules, kits and accessories

Option Modules, Control Pods, Installation Kits and other accessories for use with these drives are UL Listed.

A.3   Enclosure ratings

Open Type

With the exception of free-standing cubicle drives, all models are Open Type as supplied. The drive housing is not 
rated as a fire enclosure. A separate fire enclosure must be provided.

Type 1

When fitted with a conduit box the drives meet the requirements for UL Type 1. Type 1 enclosures are intended for 
indoor use, primarily to provide a degree of protection against limited amounts of falling dirt. 

Plenum rating with conduit box

When fitted with a conduit box, the drives comply with the requirements in the Standard for Fire Test for Heat and 
Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces, UL 2043.

Through-hole mounting

The drives meet the requirements for UL Type 12 when installed inside a Type 12 enclosure with the heatsink 
through-hole mounted using the sealing kit and the high-IP insert (where provided).
When through-hole mounted, the drives have been evaluated as suitable for use in surrounding air temperatures 
up to 40 °C.
When the drive is through-panel mounted, the main terminal cover(s) must be removed in order to provide access 
to the mounting holes. Once the drive has been mounted, the terminal cover(s) can be replaced. 
The tightening torque of the securement brackets shall be advised as being 3 N m (26.6 lb.in).

Remote Keypads

Remote keypads are UL Type 12 when installed with the sealing washer and fixing kit provided.

A.4   Mounting

Drives may be surface, through-panel or tile mounted using the appropriate brackets. Drives may be mounted 
singly or side by side with suitable space between them (bookcase mounting).

A.5   Environment

Drives must be installed in a Pollution Degree 2 environment or better (dry, non-conductive pollution only).
The drives have been evaluated for use at ambient temperatures up to 40 °C. The drives have additionally been 
evaluated for 50 °C and 55 °C ambient air temperatures with a derated output.

 

A.6   Electrical Installation

OVERVOLTAGE CATEGORY

Drives have been evaluated for OVC III.

SUPPLY

The drives are suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 
600 Volts AC Maximum.

TERMINAL TORQUE

Terminals must be tightened to the rated torque as specified in the Installation Instructions. 

WIRING TERMINALS

Drives must be installed using cables rated for 75 °C operation, copper wire only. 
Where possible, UL Listed closed-loop connectors sized according to the field wiring shall be used for all field 
power wiring connections. 

Summary of Contents for FDD 3054.00270

Page 1: ...t is essential to read the control User Guide prior to using the SafeTorque O function in safety systems Section 4 6 Diese Anleitung bietet Informationen f r eine schnelle Inbetriebnahme eines einfach...

Page 2: ...1 Feature diagram PE DC DC U V W L1 L2 L3 6 5 5 1 41 42 2 3 4 77 8 9 DC BRAKE 8 10 11 13 7 8 9 12 5 1 2 7 U V W 5 12 12 12 12 9 10 8 12 1 1 2 3 13 11 4 5 6 7 6 5 Key 1 Rating label 2 Relay connection...

Page 3: ...eck model and voltage The model number can be found on the identification label on the top of the drive Please check that the model and the drive voltage range is suitable for the installation KIT BOX...

Page 4: ...m 1 18 in 0 mm 0 00 in 100 mm 4 0 in 100 mm 4 0 in 7 45 mm 1 77 in 30 mm 1 18 in 60 mm 2 37 in 100 mm 4 0 in 8 45 mm 1 77 in 30 mm 1 18 in 60 mm 2 37 in 100 mm 4 0 in 9 45 mm 1 77 in 60 mm 2 37 in 60...

Page 5: ...UL 508C A A A Input Output Input Output 05200250 31 40 40 10 8 06200330 48 8 63 60 16 4 06200440 56 6 63 70 25 3 05400270 29 40 35 6 8 05400300 29 40 35 6 8 06400350 36 63 40 10 6 06400420 46 63 50 16...

Page 6: ...kwise by approximately 30 2 Slide the terminal cover down 3 Remove terminal cover in direction shown Input phase conductor size Minimum ground conductor size 10 mm Either 10 mm or two conductors of th...

Page 7: ...ound terminals 2 0 N m 1 4 lb ft 6 Power and ground terminals 6 0 N m 4 4 lb ft 7 Power and ground terminals 12 N m 8 85 lb ft 8 and 9 Power and ground terminals 15 N m 11 1 lb ft A 1 2 2 1 2 1 2 1 2...

Page 8: ...inal block 2 is used for Motor connection On size 5 the supply and motor ground connections are made using the M5 studs located near the plug in power connector Refer to Figure 6 1 Optional heatsink m...

Page 9: ...ide Size 5 to 9 9 English Deutsch Figure 6 2 Size 6 power and ground connections On a size 6 the supply and motor ground connections are made using the M6 studs located above the supply and motor term...

Page 10: ...ize 5 to 9 Figure 6 3 Size 7 and 8 power and ground connections size 7 shown On size 7 and 8 the supply and motor ground connections are made using the M8 studs located by the supply and motor connect...

Page 11: ...5 to 9 11 English Deutsch Figure 6 4 Size 9A power and ground connections On size 9A the supply and motor ground connections are made using the M10 studs located by the supply and motor connection te...

Page 12: ...regulations The drive must be grounded by a connection capable of carrying the prospective fault current until the protective device fuse etc disconnects the AC supply The ground connections must be...

Page 13: ...TOP RESET the drive in keypad mode It can also be used to reset the drive in terminal mode ESCAPE Is used to exit from the parameter edit view mode rdy START Is used to start the drive in keypad mode...

Page 14: ...h tuning while the drive is performing the autotune Wait for the drive to display inh and for the motor to come to a standstill Remove the drive enable and run signal from the drive Ready to run Analo...

Page 15: ...he final drive run is not active Disabled The drive is stopped holding zero speed Enabled Supply loss condition has been detected Enabled The drive is applying dc injection braking Enabled The drive h...

Page 16: ...luated as suitable for use in surrounding air temperatures up to 40 C When the drive is through panel mounted the main terminal cover s must be removed in order to provide access to the mounting holes...

Page 17: ...tection does not provide branch circuit protection Branch circuit protection must be provided in accordance with the National Electrical Code NEC The Canadian Electrical Code and any additional local...

Page 18: ...dung 1 1 Anschlussdiagramm PE DC DC U V W L1 L2 L3 6 5 5 1 41 42 2 3 4 77 8 9 DC BRAKE 8 10 11 13 7 8 9 12 5 1 2 7 U V W 5 12 12 12 12 9 10 8 12 1 1 2 3 13 11 4 5 6 7 6 5 Legende 1 Typenschild 2 Relai...

Page 19: ...er tetyp und Spannung pr fen Den Ger tetyp finden Sie auf dem Identifikationsschild oben am Umrichter berpr fen Sie dass Ger tetyp und Spannungsbereich des Umrichters f r die Anwendung geeignet sind S...

Page 20: ...nstallationshandbuch Tabelle 3 1 enth lt die einzuhaltenden Abst nde Tabelle 3 1 Empfohlener Abstand Baugr e Abstand zwischen Umrichter und Schaltschrank EMV Filter Abstand zwischen Umrichtern Abstand...

Page 21: ...r gR UL Klasse CC J oder T IEC60364 5 52 mm UL 508C AWG A A A Eingang Ausgang Eingang Ausgang 05200250 31 40 40 10 8 06200330 48 8 63 60 16 4 06200440 56 6 63 70 25 3 05400270 29 40 35 6 8 05400300 29...

Page 22: ...ersinn 2 Schieben Sie die Klemmenabdeckung nach unten 3 Entfernen Sie die Klemmenabdeckung in der dargestellten Richtung Leitungsquerschnitt des Netzanschlusses Minimaler Leitungsquerschnitt der Erdve...

Page 23: ...mmen 6 0 N m 7 Strom und Erdanschlussklemmen 12 N m 8 und 9 Strom und Erdanschlussklemmen 15 N m A 1 2 2 1 2 1 2 1 2 1 3 2 B C D A Baugr en 5 bis 9 B Nur Baugr e 5 C Nur Baugr e 6 D Baugr en 7 bis 9 L...

Page 24: ...ird f r den Motoranschluss verwendet Bei Umrichtern der Baugr e 5 wird die Erdung von Netz und Motoranschluss durch die M5 Erdungsbolzen neben den Netzanschlussklemmen vorgenommen Siehe Abbildung 6 1...

Page 25: ...h Deutsch Abbildung 6 2 Baugr e 6 Strom und Erdungsanschl sse Bei Umrichtern der Baugr e 6 wird die Erdung von Netz und Motoranschluss durch die M6 Erdungsbolzen vorgenommen die sich ber den Netz und...

Page 26: ...gr en 7 und 8 Strom und Erdungsanschl sse Abbildung zeigt Baugr e 7 Bei Umrichtern der Baugr e 7 bis 8 wird die Erdung von Netz und Motoranschluss durch die M8 Erdungsbolzen vorgenommen die sich ber d...

Page 27: ...utsch Abbildung 6 4 Baugr e 9A Leistungswerte und Erdverbindungen Bei Umrichtern der Baugr e 9A wird die Erdung von Netz und Motoranschluss durch die M10 Erdungsbolzen vorgenommen die sich ber den Net...

Page 28: ...Umrichter muss so geerdet werden dass ein eventuell auftretender Fehlerstrom so lange abgeleitet wird bis eine Schutzeinrichtung Sicherung usw die Netzspannung abschaltet Die Erdungsanschl sse m ssen...

Page 29: ...bestimmten Parameters oder zur Bearbeitung von Parameterwerten STOPP RESET des Umrichters im Tastaturmodus Kann auch zum R cksetzen des Umrichters im Modus f r Klemmen ansteuerung verwendet werden Sta...

Page 30: ...24 V an Klemme 12 Rechtslauf oder Klemme 13 Linkslauf Am Display blinkt tuning w hrend der Umrichter die automatische Abstimmung durchf hrt Warten Sie bis der Umrichter inh angezeigt und der Motor zum...

Page 31: ...ert ist Deaktiviert Der Umrichter ist gestoppt wird auf Nulldrehzahl gehalten Freigegeben Es wurde ein Verlust der Stromversorgung erfasst Freigegeben Die Gleichstrombremsung ist aktiv Freigegeben Ein...

Page 32: ...eckmontage sind die Umrichter f r Umgebungstemperaturen bis 40 C geeignet Bei Umrichtern in Durchsteckmontage m ssen die Klemmenabdeckungen unten entfernt werden damit der Zugang zu den Montagebohrung...

Page 33: ...triebsanleitung Steuereinheit entnommen werden Damit der Motorschutz ordnungsgem arbeitet muss der Motornennstrom in Pr 06 oder Pr 05 007 eingegeben werden Der berlastschutz kann auch unterhalb von 15...

Page 34: ...0478 0637 04...

Reviews: